ABB 1SBL136060R2301 Block Contactor - IEC 60947-4-1
Part Number: 1SBL136060R2301
Quick Summary
ABB 1SBL136060R2301 block contactor is a 3-pole device designed to reliably start and stop motors up to 4 kW at 400 V AC (AC-3) with a 690 V rating for main circuits. In modern panels, voltage variations and unstable networks can cause nuisance trips and inconsistent performance; this device addresses that by incorporating AF technology and a wide control voltage range. It carries industry-recognized standards such as IEC/EN 60947-1, IEC/EN 60947-4-1, and UL 60947-4-1, ensuring robust safety and compliance for global applications. With its compact 45 mm width and built-in surge protection, it simplifies installation and reduces panel space while delivering dependable motor control. Secondary benefits include easy integration with add-on auxiliary blocks and a broad accessory ecosystem for customization.
Product Information
Extended Description
1SBL136060R2301 ABB: The AF09ZB-30-01RT-23 is a 3 pole - 690 V IEC or 600 UL contactor with 1 built-in auxiliary contact and Ring-Tongue Terminals, controlling motors up to 4 kW / 400 V AC (AC-3) or 5 hp / 480 V UL and switching power circuits up to 25 A (AC-1) or 25 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
Motor control and protection for Rolling stock application_PDF
Instructions and Manuals
Installation instructions AF09...38(Z)B-..RT Contactors, NF(Z)B..ERT Contactor relays and CA4..RT, CAL4..RT, CAT4..RT, LDC4RT Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
45 mm
Product Net Depth / Length
77 mm
Product Net Height
86 mm
Product Net Weight
0.32 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
1
Number of Poles
3P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives.
Rated Operational Voltage
Auxiliary Circuit 690 V | Main Circuit 690 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 Hz | Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 35 A | acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 25 A | (690 V) 60 °C 25 A | (690 V) 70 °C 22 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 9 A | (440 V) 60 °C 9 A | (500 V) 60 °C 9.5 A | (690 V) 60 °C 7 A | (380 / 400 V) 60 °C 9 A | (220 / 230 / 240 V) 60 °C 9 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 9 A | (440 V) 60 °C 9 A | (500 V) 60 °C 9.5 A | (690 V) 60 °C 7 A | (380 / 400 V) 60 °C 9 A | (220 / 230 / 240 V) 60 °C 9 A
Rated Operational Current AC-15 (Ie)
(500 V) 2 A | (690 V) 2 A | (24 / 127 V) 6 A | (220 / 240 V) 4 A | (400 / 440 V) 3 A
Rated Operational Current DC-1 (Ie)
(110 V) 1-Pole, 40 °C 10 A | (110 V) 1-Pole, 60 °C 10 A | (110 V) 1-Pole, 70 °C 10 A | (110 V) 2 Poles in Series, 40 °C 25 A | (110 V) 2 Poles in Series, 60 °C 25 A | (110 V) 2 Poles in Series, 70 °C 22 A | (110 V) 3 Poles in Series, 40 °C 25 A | (110 V) 3 Poles in Series, 60 °C 25 A | (110 V) 3 Poles in Series, 70 °C 22 A | (220 V) 2 Poles in Series, 40 °C 10 A | (220 V) 2 Poles in Series, 60 °C 10 A | (220 V) 2 Poles in Series, 70 °C 10 A | (220 V) 3 Poles in Series, 40 °C 25 A | (220 V) 3 Poles in Series, 60 °C 25 A | (220 V) 3 Poles in Series, 70 °C 22 A | (72 V) 1-Pole, 40 °C 25 A | (72 V) 1-Pole, 60 °C 25 A | (72 V) 1-Pole, 70 °C 22 A | (72 V) 2 Poles in Series, 40 °C 25 A | (72 V) 2 Poles in Series, 60 °C 25 A | (72 V) 2 Poles in Series, 70 °C 22 A | (72 V) 3 Poles in Series, 40 °C 25 A | (72 V) 3 Poles in Series, 60 °C 25 A | (72 V) 3 Poles in Series, 70 °C 22 A
Rated Operational Current DC-3 (Ie)
(110 V) 1-Pole, 40 °C 6 A | (110 V) 1-Pole, 60 °C 6 A | (110 V) 1-Pole, 70 °C 6 A | (110 V) 2 Poles in Series, 40 °C 25 A | (110 V) 2 Poles in Series, 60 °C 25 A | (110 V) 2 Poles in Series, 70 °C 22 A | (110 V) 3 Poles in Series, 40 °C 25 A | (110 V) 3 Poles in Series, 60 °C 25 A | (110 V) 3 Poles in Series, 70 °C 22 A | (220 V) 2 Poles in Series, 40 °C 6 A | (220 V) 2 Poles in Series, 60 °C 6 A | (220 V) 2 Poles in Series, 70 °C 6 A | (220 V) 3 Poles in Series, 40 °C 25 A | (220 V) 3 Poles in Series, 60 °C 25 A | (220 V) 3 Poles in Series, 70 °C 22 A | (72 V) 1-Pole, 40 °C 25 A | (72 V) 1-Pole, 60 °C 25 A | (72 V) 1-Pole, 70 °C 22 A | (72 V) 2 Poles in Series, 40 °C 25 A | (72 V) 2 Poles in Series, 60 °C 25 A | (72 V) 2 Poles in Series, 70 °C 22 A | (72 V) 3 Poles in Series, 40 °C 25 A | (72 V) 3 Poles in Series, 60 °C 25 A | (72 V) 3 Poles in Series, 70 °C 22 A
Rated Operational Current DC-5 (Ie)
(110 V) 1-Pole, 40 °C 4 A | (110 V) 1-Pole, 60 °C 4 A | (110 V) 1-Pole, 70 °C 4 A | (110 V) 2 Poles in Series, 40 °C 10 A | (110 V) 2 Poles in Series, 60 °C 10 A | (110 V) 2 Poles in Series, 70 °C 10 A | (110 V) 3 Poles in Series, 40 °C 25 A | (110 V) 3 Poles in Series, 60 °C 25 A | (110 V) 3 Poles in Series, 70 °C 22 A | (220 V) 2 Poles in Series, 40 °C 4 A | (220 V) 2 Poles in Series, 60 °C 4 A | (220 V) 2 Poles in Series, 70 °C 4 A | (220 V) 3 Poles in Series, 40 °C 9 A | (220 V) 3 Poles in Series, 60 °C 9 A | (220 V) 3 Poles in Series, 70 °C 9 A | (72 V) 1-Pole, 40 °C 9 A | (72 V) 1-Pole, 60 °C 9 A | (72 V) 1-Pole, 70 °C 9 A | (72 V) 2 Poles in Series, 40 °C 25 A | (72 V) 2 Poles in Series, 60 °C 25 A | (72 V) 2 Poles in Series, 70 °C 22 A | (72 V) 3 Poles in Series, 40 °C 25 A | (72 V) 3 Poles in Series, 60 °C 25 A | (72 V) 3 Poles in Series, 70 °C 22 A
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W | (48 V) 2.8 A / 134 W | (72 V) 1 A / 72 W | (110 V) 0.55 A / 60 W | (125 V) 0.55 A / 69 W | (220 V) 0.27 A / 60 W | (250 V) 0.27 A / 68 W | (400 V) 0.15 A / 60 W | (500 V) 0.13 A / 65 W | (600 V) 0.1 A / 60 W
Rated Operational Power AC-3 (Pe)
(415 V) 4 kW | (440 V) 4 kW | (500 V) 5.5 kW | (690 V) 5.5 kW | (380 / 400 V) 4 kW | (220 / 230 / 240 V) 2.2 kW
Rated Operational Power AC-3e (Pe)
(415 V) 4 kW | (440 V) 4 kW | (500 V) 5.5 kW | (690 V) 5.5 kW | (380 / 400 V) 4 kW | (220 / 230 / 240 V) 2.2 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A | for 0.1 s 140 A | for 1 s 100 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 V | acc. to IEC 60947-5-1 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-15) 1200 cycles per hour | (AC-2 / AC-4) 300 cycles per hour | (AC-3) 1200 cycles per hour | (DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 100 ... 250 V | 60 Hz 100 ... 250 V | DC Operation 100 ... 250 V
Power Loss
at 6 A per Pole 0.1 W | at Rated Operating Conditions AC-1 per Pole 0.8 W | at Rated Operating Conditions AC-3 per Pole 0.1 W
Operate Time
Between Coil De-energization and NC Contact Closing 13 ... 98 ms | Between Coil De-energization and NO Contact Opening 11 ... 95 ms | Between Coil Energization and NC Contact Opening 38 ... 90 ms | Between Coil Energization and NO Contact Closing 40 ... 95 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 screws placed diagonally
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP10 | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP10 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Tightening Torque
Auxiliary Circuit 1.2 N·m | Control Circuit 1.2 N·m | Main Circuit 1.5 N·m
Terminal Type
Ring-Tongue Terminals
Product Name
Block Contactor
NEMA Size
00
Continuous Current Rating NEMA
9 A
Horsepower Rating NEMA
(115 V AC) Single Phase 1/3 Hp | (200 V AC) Three Phase 1-1/2 Hp | (230 V AC) Single Phase 1 Hp | (230 V AC) Three Phase 1-1/2 Hp | (460 V AC) Three Phase 2 Hp | (575 V AC) Three Phase 2 Hp
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 25 A
Horsepower Rating UL/CSA
(120 V AC) Single Phase 3/4 hp | (200 ... 208 V AC) Three Phase 2 hp | (220 ... 240 V AC) Three Phase 2 hp | (240 V AC) Single Phase 1-1/2 hp | (440 ... 480 V AC) Three Phase 5 hp | (550 ... 600 V AC) Three Phase 7-1/2 hp
Tightening Torque UL/CSA
Auxiliary Circuit 11 in·lb | Control Circuit 11 in·lb | Main Circuit 13 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 13.8 A | (200 ... 208 V AC) Three Phase 7.8 A | (220 ... 240 V AC) Three Phase 6.8 A | (240 V AC) Single Phase 10 A | (440 ... 480 V AC) Three Phase 7.6 A | (550 ... 600 V AC) Three Phase 9 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -25 ... 60 °C | Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Shock and Vibration Withstand acc. to IEC 61373
Category 1, Class B
Pollution Degree
3
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
5ca232c8-b5ab-47aa-b05d-cff96856a8f0 China (CN)
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
End Of Life Disassembling Instructions
End of life instruction AF(S)09/12/16/26/30/38(Z)(B)(K)(RT) Contactors & NF(Z)(B)(K)(RT) Contactors relays
Environmental Product Declaration - EPD
Environmental Product Declaration - AF09/12/16(Z)(B) Contactors and NF(Z) Contactor relaysAF(S)09/12/16(Z)(B) Contactors and NF(Z)(B) Contactors Relays (FR) | Environmental Product Declaration - AF09/12/16(Z)(B) Contactors and NF(Z) Contactor relays
Sustainable Material Content in Packaging (wt. %)
Recycled Cardboard - 86 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 28 %
CB Certificate
CB Certificate AF09, AF12, AF16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
CCC Certificate
CCC Certificate AF09, AF12, AF16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
CQC Certificate
CQC Certificate AF(C)09, AF(C)12, AF(C)16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
Declaration of Conformity - CCC
CCC Declaration of Conformity, Contactor, AF*09, AF*12, AF*16, Made in France
Declaration of Conformity - CE
EU Declaration of Conformity AF09 to AF38(Z)B..RT 3 and 4-pole contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09 to AF38(Z)B..RT 3 and 4-pole contactors
UL Listing Card
UL_E312527
UR Certificate
UR Certificate of Compliance AF09...AF38(Z)B..RT 3-pole contactors with ring tongue terminals
Package Level 1 Units
box 1 piece
Package Level 1 Width
87 mm
Package Level 1 Depth / Length
79 mm
Package Level 1 Height
47 mm
Package Level 1 Gross Weight
0.32 kg
Package Level 1 EAN
3471523127739
Package Level 2 Units
box 27 piece
Package Level 2 Width
250 mm
Package Level 2 Depth / Length
300 mm
Package Level 2 Height
315 mm
Package Level 2 Gross Weight
17.28 kg
Package Level 3 Units
1296 piece
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
Feature → Business Impact → Application: The 3P configuration with 3 main NO contacts and 1 NC auxiliary contact provides reliable motor switching and status signaling, reducing downtime and enabling precise control in conveyors and pumps. This translates to higher line productivity and clearer fault diagnostics in factory automation. The AF technology delivers a wide control voltage range of 100–250 V AC/ DC, minimizing control circuit mismatches during commissioning and in networks with fluctuating mains, which lowers energy waste and improves reliability in process lines. The built-in surge protection and compact block design reduce panel footprint and protection wiring, yielding faster assemblies and easier compliance with space-constrained control panels across water treatment and packaging lines. The ability to extend with add-on auxiliary contact blocks supports scalable logic expansion and future-proofing as control schemes evolve in HVAC, material handling, and material flow systems. With DIN-rail mounting, narrow width, and Ring-Tongue terminal connections, wiring is quicker, more secure, and less prone to loosening under vibration. The device meets IEC/EN 60947-1 and UL 60947-4-1, offering confidence for global installations and end-user audits, while the RoHS and REACH declarations help simplify supplier compliance documentation. In practice, this translates to lower installation costs, faster commissioning, and a shorter path to compliance in industrial control cabinets.
Get a Quick Quote for a ABB 1SBL136060R2301
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SBL136060R2301?
Enquire Now
FAQs
The ABB AF contactor supports DIN rail mounting on TH35-15 or TH35-7.5 rails. To install, snap the device onto the rail, ensure proper alignment, and secure with the included or specified mounting accessories. Use Ring-Tongue terminals for main and auxiliary connections and torque values of 1.5 N·m for main terminals and 1.2 N·m for auxiliary and control circuits. This ensures reliable electrical contact and vibration resistance in industrial environments.
For AC-1 operation at 690 V, the rated current is 25 A (at 60 °C) and 22–25 A depending on ambient temperature. For AC-3 operation, the device supports approximately 7 A at 690 V (60 °C). These values enable correct sizing for motor start/stop tasks and ensure safe coordination with contactors, overload relays, and circuit protection in high-voltage motor circuits.
Yes. The product complies with relevant standards including IEC/EN 60947-1 and 60947-4-1, UL 60947-4-1, and EN 50155 applicable parts for rail applications. It features robust insulation, surge protection, and a compact block design suitable for rugged environments. For rail or other demanding environments, verify the exact applicable parts and mounting configuration with ABB to ensure full regulatory compliance.
The device carries CE, UKCA, CCC, CQC and UL listings, RoHS and REACH declarations, and environmental documentation such as EPDs and CMRT. These certifications streamline supplier declarations and support regulatory audits, reducing time-to-compliance and simplifying RoHS/REACH compliance reporting for global deployments.
Consider the device’s built-in surge protection, wide control voltage tolerance, and 3P/1NC configuration for reduced downtime and fewer control faults. The compact DIN-rail mount and ring-tongue terminations simplify installation and reduce wiring errors. Over time, energy savings arise from stable control circuit operation and reduced panel wiring complexity, while longer equipment life results from reliable switching performance and minimized arcing.