ABB AF09ZB-30-01-22 Block Contactor - IEC/UL 690V

Part Number: 1SBL136061R2201
Manufacturer
ABB
Part number
1SBL136061R2201

Quick Summary

AF09ZB-30-01-22 is a three-pole contactor used to control motors in industrial automation panels. It addresses voltage variations and network instability that can cause nuisance trips and energy waste. The device complies with IEC 60947-4-1, IEC 60947-5-1 and UL 60335-2-40 (LZGH2 A2L) with CSA recognition, ensuring robust safety and global acceptance. Its built-in surge protection and AF technology support scalable panel designs while reducing wiring complexity and space. For engineers seeking reliable, compact motor control with broad compatibility, this product delivers predictable performance and long-term operational efficiency in demanding environments.

Product Information

Extended Description

1SBL136061R2201 ABB: The AF09ZB-30-01-22 is a 3 pole - 690 V IEC or 600 UL contactor with 1 built-in auxiliary contact and screw terminals, controlling motors up to 4 kW / 400 V AC (AC-3) or 5 hp / 480 V UL and switching power circuits up to 25 A (AC-1) or 25 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (48-130 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
Motor control and protection for Rolling stock application_PDF
Instructions and Manuals
Installation instructions AF(C)09...38(Z)(B) Contactors, NF(C)(Z)(B)22...80E Contactor relays and CA4, CAL4, CAT4, CC4, LDC4 Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
45 mm
Product Net Depth / Length
77 mm
Product Net Height
86 mm
Product Net Weight
0.31 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
1
Number of Poles
3P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives.
Rated Operational Voltage
Auxiliary Circuit 690 V | Main Circuit 690 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 Hz | Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 35 A | acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 25 A | (690 V) 60 °C 25 A | (690 V) 70 °C 22 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 9 A | (440 V) 60 °C 9 A | (500 V) 60 °C 9.5 A | (690 V) 60 °C 7 A | (380 / 400 V) 60 °C 9 A | (220 / 230 / 240 V) 60 °C 9 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 9 A | (440 V) 60 °C 9 A | (500 V) 60 °C 9.5 A | (690 V) 60 °C 7 A | (380 / 400 V) 60 °C 9 A | (220 / 230 / 240 V) 60 °C 9 A
Rated Operational Current AC-15 (Ie)
(500 V) 2 A | (690 V) 2 A | (24 / 127 V) 6 A | (220 / 240 V) 4 A | (400 / 440 V) 3 A
Rated Operational Current DC-1 (Ie)
(110 V) 1-Pole, 40 °C 10 A | (110 V) 1-Pole, 60 °C 10 A | (110 V) 1-Pole, 70 °C 10 A | (110 V) 2 Poles in Series, 40 °C 25 A | (110 V) 2 Poles in Series, 60 °C 25 A | (110 V) 2 Poles in Series, 70 °C 22 A | (110 V) 3 Poles in Series, 40 °C 25 A | (110 V) 3 Poles in Series, 60 °C 25 A | (110 V) 3 Poles in Series, 70 °C 22 A | (220 V) 2 Poles in Series, 40 °C 10 A | (220 V) 2 Poles in Series, 60 °C 10 A | (220 V) 2 Poles in Series, 70 °C 10 A | (220 V) 3 Poles in Series, 40 °C 25 A | (220 V) 3 Poles in Series, 60 °C 25 A | (220 V) 3 Poles in Series, 70 °C 22 A | (72 V) 1-Pole, 40 °C 25 A | (72 V) 1-Pole, 60 °C 25 A | (72 V) 1-Pole, 70 °C 22 A | (72 V) 2 Poles in Series, 40 °C 25 A | (72 V) 2 Poles in Series, 60 °C 25 A | (72 V) 2 Poles in Series, 70 °C 22 A | (72 V) 3 Poles in Series, 40 °C 25 A | (72 V) 3 Poles in Series, 60 °C 25 A | (72 V) 3 Poles in Series, 70 °C 22 A
Rated Operational Current DC-3 (Ie)
(110 V) 1-Pole, 40 °C 6 A | (110 V) 1-Pole, 60 °C 6 A | (110 V) 1-Pole, 70 °C 6 A | (110 V) 2 Poles in Series, 40 °C 25 A | (110 V) 2 Poles in Series, 60 °C 25 A | (110 V) 2 Poles in Series, 70 °C 22 A | (110 V) 3 Poles in Series, 40 °C 25 A | (110 V) 3 Poles in Series, 60 °C 25 A | (110 V) 3 Poles in Series, 70 °C 22 A | (220 V) 2 Poles in Series, 40 °C 6 A | (220 V) 2 Poles in Series, 60 °C 6 A | (220 V) 2 Poles in Series, 70 °C 6 A | (220 V) 3 Poles in Series, 40 °C 25 A | (220 V) 3 Poles in Series, 60 °C 25 A | (220 V) 3 Poles in Series, 70 °C 22 A | (72 V) 1-Pole, 40 °C 25 A | (72 V) 1-Pole, 60 °C 25 A | (72 V) 1-Pole, 70 °C 22 A | (72 V) 2 Poles in Series, 40 °C 25 A | (72 V) 2 Poles in Series, 60 °C 25 A | (72 V) 2 Poles in Series, 70 °C 22 A | (72 V) 3 Poles in Series, 40 °C 25 A | (72 V) 3 Poles in Series, 60 °C 25 A | (72 V) 3 Poles in Series, 70 °C 22 A
Rated Operational Current DC-5 (Ie)
(110 V) 1-Pole, 40 °C 4 A | (110 V) 1-Pole, 60 °C 4 A | (110 V) 1-Pole, 70 °C 4 A | (110 V) 2 Poles in Series, 40 °C 10 A | (110 V) 2 Poles in Series, 60 °C 10 A | (110 V) 2 Poles in Series, 70 °C 10 A | (110 V) 3 Poles in Series, 40 °C 25 A | (110 V) 3 Poles in Series, 60 °C 25 A | (110 V) 3 Poles in Series, 70 °C 22 A | (220 V) 2 Poles in Series, 40 °C 4 A | (220 V) 2 Poles in Series, 60 °C 4 A | (220 V) 2 Poles in Series, 70 °C 4 A | (220 V) 3 Poles in Series, 40 °C 9 A | (220 V) 3 Poles in Series, 60 °C 9 A | (220 V) 3 Poles in Series, 70 °C 9 A | (72 V) 1-Pole, 40 °C 9 A | (72 V) 1-Pole, 60 °C 9 A | (72 V) 1-Pole, 70 °C 9 A | (72 V) 2 Poles in Series, 40 °C 25 A | (72 V) 2 Poles in Series, 60 °C 25 A | (72 V) 2 Poles in Series, 70 °C 22 A | (72 V) 3 Poles in Series, 40 °C 25 A | (72 V) 3 Poles in Series, 60 °C 25 A | (72 V) 3 Poles in Series, 70 °C 22 A
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W | (48 V) 2.8 A / 134 W | (72 V) 1 A / 72 W | (110 V) 0.55 A / 60 W | (125 V) 0.55 A / 69 W | (220 V) 0.27 A / 60 W | (250 V) 0.27 A / 68 W | (400 V) 0.15 A / 60 W | (500 V) 0.13 A / 65 W | (600 V) 0.1 A / 60 W
Rated Operational Power AC-3 (Pe)
(415 V) 4 kW | (440 V) 4 kW | (500 V) 5.5 kW | (690 V) 5.5 kW | (380 / 400 V) 4 kW | (220 / 230 / 240 V) 2.2 kW
Rated Operational Power AC-3e (Pe)
(415 V) 4 kW | (440 V) 4 kW | (500 V) 5.5 kW | (690 V) 5.5 kW | (380 / 400 V) 4 kW | (220 / 230 / 240 V) 2.2 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A | for 0.1 s 140 A | for 1 s 100 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 V | acc. to IEC 60947-5-1 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-15) 1200 cycles per hour | (AC-2 / AC-4) 300 cycles per hour | (AC-3) 1200 cycles per hour | (DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 48 ... 130 V | 60 Hz 48 ... 130 V | DC Operation 48 ... 130 V
Power Loss
at 6 A per Pole 0.1 W | at Rated Operating Conditions AC-1 per Pole 0.8 W | at Rated Operating Conditions AC-3 per Pole 0.1 W
Operate Time
Between Coil De-energization and NC Contact Closing 13 ... 98 ms | Between Coil De-energization and NO Contact Opening 11 ... 95 ms | Between Coil Energization and NC Contact Opening 38 ... 90 ms | Between Coil Energization and NO Contact Closing 40 ... 95 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 0.75 ... 6 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 4 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² | Rigid Solid 1/2x 1 ... 4 mm² | Rigid Stranded 1/2x 1 ... 6 mm²
Connecting Capacity Auxiliary Circuit
Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Auxiliary Circuit 10 mm | Control Circuit 10 mm | Main Circuit 10 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Tightening Torque
Auxiliary Circuit 1.2 N·m | Control Circuit 1.2 N·m | Main Circuit 1.5 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
NEMA Size
00
Continuous Current Rating NEMA
9 A
Horsepower Rating NEMA
(115 V AC) Single Phase 1/3 Hp | (200 V AC) Three Phase 1-1/2 Hp | (230 V AC) Single Phase 1 Hp | (230 V AC) Three Phase 1-1/2 Hp | (460 V AC) Three Phase 2 Hp | (575 V AC) Three Phase 2 Hp
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 25 A
Horsepower Rating UL/CSA
(120 V AC) Single Phase 3/4 hp | (200 ... 208 V AC) Three Phase 2 hp | (220 ... 240 V AC) Three Phase 2 hp | (240 V AC) Single Phase 1-1/2 hp | (440 ... 480 V AC) Three Phase 5 hp | (550 ... 600 V AC) Three Phase 7-1/2 hp
Connecting Capacity Main Circuit UL/CSA
Rigid Solid 1/2x 16-10 AWG | Rigid Stranded 1/2x 16-10 AWG
Connecting Capacity Auxiliary Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG | Rigid Stranded 1/2x 18-14 AWG
Connecting Capacity Control Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG | Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSA
Auxiliary Circuit 11 in·lb | Control Circuit 11 in·lb | Main Circuit 13 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 13.8 A | (200 ... 208 V AC) Three Phase 7.8 A | (220 ... 240 V AC) Three Phase 6.8 A | (240 V AC) Single Phase 10 A | (440 ... 480 V AC) Three Phase 7.6 A | (550 ... 600 V AC) Three Phase 9 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -25 ... 60 °C | Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Shock and Vibration Withstand acc. to IEC 61373
Category 1, Class B
Pollution Degree
3
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
4585ee85-29f0-47cb-8fd8-e4c16d8955c3 China (CN)
Simplified SCIP
184baf4f-fa5e-42bd-9925-a7c62fc46d76 France (FR) | e9fc4533-3af1-465a-a064-b4e4d7e4ce17 Belgium (BE) | 57c8ea6a-d23c-4325-b51f-424bed509bb9 Germany (DE) | a659f29b-6403-439b-b7a1-4f3233b0df7a Spain (ES) | b742ee53-027a-462b-9210-dbd960acabbb Hungary (HU) | dc129631-8047-4aea-a0ff-1c7a06417843 Bulgaria (BG) | 15a3d92a-e1d9-4124-b252-c118459086cf Portugal (PT) | 3b1e4395-6761-44b8-93aa-a6bef31ac63e Poland (PL) | cadd3728-97d9-4f34-866f-c7c2a3cea7a4 Sweden (SE) | 3ad984f8-8b86-41aa-954c-e9ae1b8ce67d Germany (DE) | 00f25552-9dfa-49d0-8727-ee228442b6dc Greece (GR) | 553fb667-65a1-4580-8f46-f471ce1d3339 Estonia (EE) | 9d578ccd-c48d-4da6-b760-bbd597abc5e4 Netherlands (NL) | 71f0575f-fd94-4c04-9a2c-8a202ffdd05b Hungary (HU) | cc4e24a4-797b-4d2f-b0f9-d14c7e75e076 Poland (PL) | 67fd8486-1808-487c-b5fe-578a50036055 France (FR) | 2a65f274-6d2d-46a9-8e0e-90d0b5d0237d Croatia (HR) | 1c357c41-2cf2-49a2-b2b2-4f94fd0a028b Denmark (DK) | 450dfa0e-c457-4631-86b4-0600a103042c Germany (DE) | 992811c8-7224-4835-9d83-d79b203a73dd Germany (DE) | 5de92c2e-2503-4614-8de7-0e06c72aa4e1 Finland (FI) | 987a27ad-c122-4f4d-94ce-02ed4c99e12f Belgium (BE) | 4d7e4061-9f0f-4b07-80e6-e506332b4005 Norway (NO) | 06009efa-771a-4e59-85bf-fb0d61bcea1b Poland (PL) | 9dc2258d-6d24-4cf2-9daa-81846943709e Germany (DE) | f2d84252-1d88-4605-b918-7a1ab80937e5 Czech Republic (CZ) | 20e3d09d-3559-4835-b62b-27e2fb93f634 Sweden (SE)
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
End Of Life Disassembling Instructions
End of life instruction AF(S)09/12/16/26/30/38(Z)(B)(K)(RT) Contactors & NF(Z)(B)(K)(RT) Contactors relays
Environmental Product Declaration - EPD
Environmental Product Declaration - AF09/12/16(Z)(B) Contactors and NF(Z) Contactor relaysAF(S)09/12/16(Z)(B) Contactors and NF(Z)(B) Contactors Relays (FR) | Environmental Product Declaration - AF09/12/16(Z)(B) Contactors and NF(Z) Contactor relays
Sustainable Material Content in Packaging (wt. %)
Recycled Cardboard - 86 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 28 %
A2L Certificate – UL
UL-US A2L LZGH2 Certificate of Compliance AF09 ... AF38 3-pole contactors with screw terminals - UL 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers | UL-CA A2L LZGH2 Certificate of Compliance AF09 ... AF38 3-pole contactors with screw terminals - CSA C22.2 No. 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers
CB Certificate
CB Certificate AF09, AF12, AF16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
CCC Certificate
CCC Certificate AF09, AF12, AF16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
CQC Certificate
CQC Certificate AF(C)09, AF(C)12, AF(C)16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
Declaration of Conformity - CCC
CCC Declaration of Conformity, Contactor, AF*09, AF*12, AF*16, Made in France
Declaration of Conformity - CE
EU Declaration of Conformity AF09 ... AF38(Z)B..(K), AF40B ... AF96B 3 and 4-pole contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09 ... AF38(Z)B..(K), AF40B ... AF96B 3 and 4-pole contactors
GOST Certificate
GOST_POCCFR.ME77.B07175.pdf
KC Certificate
KC Certificate AF09 3-pole contactors
UL Certificate
UL-US Certificate of Compliance AF(C)(S)09(R/M/N)-..(L)(S)(K)...AF(C)(S)38(R/M/N)..(K) 3-pole contactors screw, spring and push-in spring terminals; LDC4 additional coil terminal block; LF16-4, LG16-4, LF38-4 and LH38-4 connecting strips, LD38-4 additional terminal block | UL-CA Certificate of Compliance AF(C)(S)09(R/M/N)-..(L)(S)(K)...AF(C)(S)38(R/M/N)..(K) 3-pole contactors screw, spring and push-in spring terminals; LDC4 additional coil terminal block; LF16-4, LG16-4, LF38-4 and LH38-4 connecting strips, LD38-4 additional terminal block
UL Listing Card
E312527
Package Level 1 Units
box 1 piece
Package Level 1 Width
87 mm
Package Level 1 Depth / Length
79 mm
Package Level 1 Height
47 mm
Package Level 1 Gross Weight
0.31 kg
Package Level 1 EAN
3471523123625
Package Level 2 Units
box 27 piece
Package Level 2 Width
250 mm
Package Level 2 Depth / Length
300 mm
Package Level 2 Height
315 mm
Package Level 2 Gross Weight
16.74 kg
Package Level 3 Units
1296 piece
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
Feature: Wide control voltage range (48-130 V AC/DC) → Business Impact: Stable coil operation despite supply variations, reducing mis-operations and energy waste; Application: Industrial panels with fluctuating control signals. Feature: 3-pole, 690 V main circuit with 25 A AC-1 and 7 A AC-3 ratings → Business Impact: Enables motors up to 4 kW and multiple spacing options without oversizing; Application: High-power conveyor drives and fans. Feature: Built-in surge protection → Business Impact: Lower external protection costs and simpler panel design; Application: Environments with voltage transients and grid fluctuations. Feature: AF technology with wide voltage tolerance → Business Impact: Improved reliability in unstable networks; Application: Rolling stock and heavy-duty machinery. Feature: Block design with add-on auxiliary blocks → Business Impact: Scalable solutions that grow with control system needs; Application: Modular control panels requiring future expansion. Feature: Compact footprint (45 mm width, 86 mm height, 0.31 kg) and screw terminals → Business Impact: Easy DIN-rail mounting and reduced panel space; Application: Modern control cabinets with limited space. Feature: DIN rail mounting TH35-15/TH35-7.5 → Business Impact: Fast, secure installation and interchangeability across ABB AF family; Application: Standard electrical enclosures. Feature: Integrated coil and auxiliary contact (1 NC) → Business Impact: Simplified interlocking and status feedback; Application: Sequential control and monitoring circuits. Feature: IP20 protection and safe torque values → Business Impact: Safe operation and reliable terminal integrity; Application: Indoor panel assemblies with routine maintenance.

Get a Quick Quote for a ABB 1SBL136061R2201

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SBL136061R2201? Enquire Now

FAQs

The unit supports DIN rail mounting on TH35-15 or TH35-7.5 rails and can be screw-mounted with two M4 screws if needed, enabling quick, secure installation and easy service access.
Rated Operational Current AC-3 at 690 V is 7 A; AC-1 at 690 V is 25 A (60 °C). This makes it suitable for smaller motor starts and general power switching within residential to light-industrial ranges.
The control circuit accepts 48–130 V AC, 50/60 Hz, or DC operation. This wide range tolerates voltage fluctuations, reducing nuisance trips and improving reliability in unstable networks.
Yes, it features built-in surge protection, which reduces external protection requirements and enhances reliability in environments with transients or grid disturbances.
It complies with IEC 60947-1, IEC 60947-4-1, UL 60335-2-40 (LZGH2 A2L), CSA C22.2 No. 60335-2-40, and related CE/UKCA declarations, ensuring global applicability in safety-critical motor control.