ABB 1SBL136063R2210 Block Contactor - 690V AC

Part Number: 1SBL136063R2210
Manufacturer
ABB
Part number
1SBL136063R2210

Quick Summary

ABB 1SBL136063R2210 Block Contactor is a 3-pole, 690 V AC motor controller designed for robust, reliable start/stop in demanding industrial environments. In networks with voltage fluctuations, control coils can misoperate, leading to nuisance trips and downtime. This device mitigates that risk with AF technology featuring a wide control voltage range and built-in surge protection, while meeting IEC/EN and UL standards for global installations. It includes one built-in auxiliary contact and Push-in spring terminals for fast, secure wiring. Ideal for motor protection on conveyors, pumps, fans, and packaging lines, it also supports easy DIN rail mounting and straightforward expansion with add-on auxiliary blocks to scale alongside your evolving control architecture.

Product Information

Extended Description

1SBL136063R2210 ABB: The AF09ZB-30-10K-22 is a 3 pole - 690 V IEC or 600 UL contactor with 1 built-in auxiliary contact and Push-in spring terminals, controlling motors up to 4 kW / 400 V AC (AC-3) or 5 hp / 480 V UL and switching power circuits up to 25 A (AC-1) or 25 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (48-130 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
Motor control and protection for Rolling stock application_PDF
Instructions and Manuals
Installation instructions AF(C)09...38(Z)(B)..K Contactors, NF(C)(Z)(B)..K Contactor relays and CA4..K, CAL4..K, LDC4K Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
45 mm
Product Net Depth / Length
77 mm
Product Net Height
92.3 mm
Product Net Weight
0.315 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
0
Number of Poles
3P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives.
Rated Operational Voltage
Auxiliary Circuit 690 V | Main Circuit 690 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 Hz | Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 35 A | acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 25 A | (690 V) 60 °C 25 A | (690 V) 70 °C 22 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 9 A | (440 V) 60 °C 9 A | (500 V) 60 °C 9.5 A | (690 V) 60 °C 7 A | (380 / 400 V) 60 °C 9 A | (220 / 230 / 240 V) 60 °C 9 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 9 A | (440 V) 60 °C 9 A | (500 V) 60 °C 9.5 A | (690 V) 60 °C 7 A | (380 / 400 V) 60 °C 9 A | (220 / 230 / 240 V) 60 °C 9 A
Rated Operational Current AC-15 (Ie)
(500 V) 2 A | (690 V) 2 A | (24 / 127 V) 6 A | (220 / 240 V) 4 A | (400 / 440 V) 3 A
Rated Operational Current DC-1 (Ie)
(110 V) 1-Pole, 40 °C 10 A | (110 V) 1-Pole, 60 °C 10 A | (110 V) 1-Pole, 70 °C 10 A | (110 V) 2 Poles in Series, 40 °C 25 A | (110 V) 2 Poles in Series, 60 °C 25 A | (110 V) 2 Poles in Series, 70 °C 22 A | (110 V) 3 Poles in Series, 40 °C 25 A | (110 V) 3 Poles in Series, 60 °C 25 A | (110 V) 3 Poles in Series, 70 °C 22 A | (220 V) 2 Poles in Series, 40 °C 10 A | (220 V) 2 Poles in Series, 60 °C 10 A | (220 V) 2 Poles in Series, 70 °C 10 A | (220 V) 3 Poles in Series, 40 °C 25 A | (220 V) 3 Poles in Series, 60 °C 25 A | (220 V) 3 Poles in Series, 70 °C 22 A | (72 V) 1-Pole, 40 °C 25 A | (72 V) 1-Pole, 60 °C 25 A | (72 V) 1-Pole, 70 °C 22 A | (72 V) 2 Poles in Series, 40 °C 25 A | (72 V) 2 Poles in Series, 60 °C 25 A | (72 V) 2 Poles in Series, 70 °C 22 A | (72 V) 3 Poles in Series, 40 °C 25 A | (72 V) 3 Poles in Series, 60 °C 25 A | (72 V) 3 Poles in Series, 70 °C 22 A
Rated Operational Current DC-3 (Ie)
(110 V) 1-Pole, 40 °C 6 A | (110 V) 1-Pole, 60 °C 6 A | (110 V) 1-Pole, 70 °C 6 A | (110 V) 2 Poles in Series, 40 °C 25 A | (110 V) 2 Poles in Series, 60 °C 25 A | (110 V) 2 Poles in Series, 70 °C 22 A | (110 V) 3 Poles in Series, 40 °C 25 A | (110 V) 3 Poles in Series, 60 °C 25 A | (110 V) 3 Poles in Series, 70 °C 22 A | (220 V) 2 Poles in Series, 40 °C 6 A | (220 V) 2 Poles in Series, 60 °C 6 A | (220 V) 2 Poles in Series, 70 °C 6 A | (220 V) 3 Poles in Series, 40 °C 25 A | (220 V) 3 Poles in Series, 60 °C 25 A | (220 V) 3 Poles in Series, 70 °C 22 A | (72 V) 1-Pole, 40 °C 25 A | (72 V) 1-Pole, 60 °C 25 A | (72 V) 1-Pole, 70 °C 22 A | (72 V) 2 Poles in Series, 40 °C 25 A | (72 V) 2 Poles in Series, 60 °C 25 A | (72 V) 2 Poles in Series, 70 °C 22 A | (72 V) 3 Poles in Series, 40 °C 25 A | (72 V) 3 Poles in Series, 60 °C 25 A | (72 V) 3 Poles in Series, 70 °C 22 A
Rated Operational Current DC-5 (Ie)
(110 V) 1-Pole, 40 °C 4 A | (110 V) 1-Pole, 60 °C 4 A | (110 V) 1-Pole, 70 °C 4 A | (110 V) 2 Poles in Series, 40 °C 10 A | (110 V) 2 Poles in Series, 60 °C 10 A | (110 V) 2 Poles in Series, 70 °C 10 A | (110 V) 3 Poles in Series, 40 °C 25 A | (110 V) 3 Poles in Series, 60 °C 25 A | (110 V) 3 Poles in Series, 70 °C 22 A | (220 V) 2 Poles in Series, 40 °C 4 A | (220 V) 2 Poles in Series, 60 °C 4 A | (220 V) 2 Poles in Series, 70 °C 4 A | (220 V) 3 Poles in Series, 40 °C 9 A | (220 V) 3 Poles in Series, 60 °C 9 A | (220 V) 3 Poles in Series, 70 °C 9 A | (72 V) 1-Pole, 40 °C 9 A | (72 V) 1-Pole, 60 °C 9 A | (72 V) 1-Pole, 70 °C 9 A | (72 V) 2 Poles in Series, 40 °C 25 A | (72 V) 2 Poles in Series, 60 °C 25 A | (72 V) 2 Poles in Series, 70 °C 22 A | (72 V) 3 Poles in Series, 40 °C 25 A | (72 V) 3 Poles in Series, 60 °C 25 A | (72 V) 3 Poles in Series, 70 °C 22 A
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W | (48 V) 2.8 A / 134 W | (72 V) 1 A / 72 W | (110 V) 0.55 A / 60 W | (125 V) 0.55 A / 69 W | (220 V) 0.27 A / 60 W | (250 V) 0.27 A / 68 W | (400 V) 0.15 A / 60 W | (500 V) 0.13 A / 65 W | (600 V) 0.1 A / 60 W
Rated Operational Power AC-3 (Pe)
(415 V) 4 kW | (440 V) 4 kW | (500 V) 5.5 kW | (690 V) 5.5 kW | (380 / 400 V) 4 kW | (220 / 230 / 240 V) 2.2 kW
Rated Operational Power AC-3e (Pe)
(415 V) 4 kW | (440 V) 4 kW | (500 V) 5.5 kW | (690 V) 5.5 kW | (380 / 400 V) 4 kW | (220 / 230 / 240 V) 2.2 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A | for 0.1 s 140 A | for 1 s 100 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 V | acc. to IEC 60947-5-1 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-15) 1200 cycles per hour | (AC-2 / AC-4) 300 cycles per hour | (AC-3) 1200 cycles per hour | (DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 48 ... 130 V | 60 Hz 48 ... 130 V | DC Operation 48 ... 130 V
Power Loss
at 6 A per Pole 0.1 W | at Rated Operating Conditions AC-1 per Pole 1.14 W | at Rated Operating Conditions AC-3 per Pole 0.15 W
Operate Time
Between Coil De-energization and NC Contact Closing 13 ... 98 ms | Between Coil De-energization and NO Contact Opening 11 ... 95 ms | Between Coil Energization and NC Contact Opening 38 ... 90 ms | Between Coil Energization and NO Contact Closing 40 ... 95 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 0.5 ... 4 mm² | Flexible with Insulated Ferrule 1x 0.5 ... 4 mm² | Flexible with Insulated Ferrule 2x 0.5 ... 2.5 mm² | Flexible 1/2x 0.5 ... 4 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 4 ... 6 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 1/2x 0.5 ... 2.5 mm² | Flexible with Insulated Ferrule 1/2x 0.5 ... 1.5 mm² | Flexible 1/2x 0.5 ... 2.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.5 ... 2.5 mm² | Flexible with Insulated Ferrule 1/2x 0.5 ... 1.5 mm² | Flexible 1/2x 0.5 ... 2.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Auxiliary Circuit 10 mm | Control Circuit 10 mm | Main Circuit 10 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Terminal Type
Push-in Spring Terminals
Product Name
Block Contactor
NEMA Size
00
Continuous Current Rating NEMA
9 A
Horsepower Rating NEMA
(115 V AC) Single Phase 1/3 Hp | (200 V AC) Three Phase 1-1/2 Hp | (230 V AC) Single Phase 1 Hp | (230 V AC) Three Phase 1-1/2 Hp | (460 V AC) Three Phase 2 Hp | (575 V AC) Three Phase 2 Hp
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 25 A
Horsepower Rating UL/CSA
(120 V AC) Single Phase 3/4 hp | (200 ... 208 V AC) Three Phase 2 hp | (220 ... 240 V AC) Three Phase 2 hp | (240 V AC) Single Phase 1-1/2 hp | (440 ... 480 V AC) Three Phase 5 hp | (550 ... 600 V AC) Three Phase 7-1/2 hp
Connecting Capacity Main Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG | Rigid Stranded 1/2x 18-10 AWG
Connecting Capacity Auxiliary Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG
Connecting Capacity Control Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG
Full Load Amps Motor Use
(120 V AC) Single Phase 13.8 A | (200 ... 208 V AC) Three Phase 7.8 A | (220 ... 240 V AC) Three Phase 6.8 A | (240 V AC) Single Phase 10 A | (440 ... 480 V AC) Three Phase 7.6 A | (550 ... 600 V AC) Three Phase 9 A
Ambient Air Temperature
Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Resistance to Vibrations
4g Closed Position & 2g Open position 5 ... 300 Hz
Shock and Vibration Withstand acc. to IEC 61373
Category 1, Class B
Pollution Degree
3
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
End Of Life Disassembling Instructions
End of life instruction AF(S)09/12/16/26/30/38(Z)(B)(K)(RT) Contactors & NF(Z)(B)(K)(RT) Contactors relays
Environmental Product Declaration - EPD
Environmental Product Declaration - AF09/12/16(Z)(B) Contactors and NF(Z) Contactor relaysAF(S)09/12/16(Z)(B) Contactors and NF(Z)(B) Contactors Relays (FR)
Sustainable Material Content in Packaging (wt. %)
Recycled Cardboard - 86 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 28 %
CB Certificate
CB Certificate AF09, AF12, AF16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
CCC Certificate
CCC Certificate AF09, AF12, AF16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
CQC Certificate
CQC Certificate AF(C)09, AF(C)12, AF(C)16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
Declaration of Conformity - CCC
CCC Declaration of Conformity, Contactor, AF*09, AF*12, AF*16, Made in France
Declaration of Conformity - CE
EU Declaration of Conformity AF09 ... AF38(Z)B..(K), AF40B ... AF96B 3 and 4-pole contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09 ... AF38(Z)B..(K), AF40B ... AF96B 3 and 4-pole contactors
UL Certificate
UL-US Certificate of Compliance AF(C)(S)09(R/M/N)-..(L)(S)(K)...AF(C)(S)38(R/M/N)..(K) 3-pole contactors screw, spring and push-in spring terminals; LDC4 additional coil terminal block; LF16-4, LG16-4, LF38-4 and LH38-4 connecting strips, LD38-4 additional terminal block | UL-CA Certificate of Compliance AF(C)(S)09(R/M/N)-..(L)(S)(K)...AF(C)(S)38(R/M/N)..(K) 3-pole contactors screw, spring and push-in spring terminals; LDC4 additional coil terminal block; LF16-4, LG16-4, LF38-4 and LH38-4 connecting strips, LD38-4 additional terminal block
Package Level 1 Units
box 1 piece
Package Level 1 Width
93 mm
Package Level 1 Depth / Length
86 mm
Package Level 1 Height
45 mm
Package Level 1 Gross Weight
0.33 kg
Package Level 1 EAN
3471523008656
Package Level 3 Units
1080 piece
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
Feature AF technology with wide control voltage range → Business Impact Ensures reliable operation despite large control-voltage variations and reduces panel energy consumption; Application Suitable for motors driven from fluctuating networks in conveyors, pumps, and packaging lines. The result is fewer false trips and improved process stability. Feature Built-in surge protection → Business Impact Minimizes electrical noise and protects downstream electronics; Application Great for systems with frequent switching and inductive loads, like conveyors and HVAC drives. The outcome is extended component life and lower maintenance costs. Feature Push-in spring terminals → Business Impact Speeds wiring and improves terminations under vibration; Application Ideal for compact control panels and retrofit projects where space is at a premium. Feature 3 main NO contacts with 1 auxiliary NO → Business Impact Simplifies control logic and diagnostics; Application Enables straightforward control of motors with a single device and reduces panel wiring complexity. Feature Mounting on DIN rail TH35-15/TH35-7.5 + 2x M4 mounting screws → Business Impact Facilitates quick installation and easy field servicing; Application Works with standard EN 60715 DIN rails, minimizing integration effort. Feature Rated AC-3 and AC-1 capabilities, IP20 protection, and certified standards (IEC/EN 60947-1, 60947-4-1; UL/CSA) → Business Impact Delivers predictable performance across multiple voltages and jurisdictions; Application Suitable for global machine builders requiring compliant and traceable motor control solutions.

Get a Quick Quote for a ABB 1SBL136063R2210

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SBL136063R2210? Enquire Now

FAQs

The 1SBL136063R2210 coil supports 48 to 130 V, and operation is available for both AC and DC control within the 50/60 Hz range. This wide range helps tolerate supply variations and simplifies control-signal sourcing from different equipment.
For AC-3 operation, it handles up to 7 A at 690 V (60 °C) and up to 4 kW at 415–440 V, with up to 5.5 kW at higher voltages depending on the exact supply. This makes it suitable for controlling small to medium motors in typical process and packaging lines.
Yes, the contactor mounts on DIN rails TH35-15 or TH35-7.5. It uses Push-in Spring Terminals for main, auxiliary, and control circuits, enabling fast, secure wiring with reliable vibration resistance.
It complies with IEC/EN 60947-1 and 60947-4-1, UL 60947-4-1, CSA, EN 50155, TR CU 001/2011, and related CE/UKCA documentation, providing broad regulatory acceptance for industrial automation projects.
Built-in auxiliary contact simplifies wiring and diagnostics, surge protection reduces EMI and wear, AF technology lowers energy consumption, and the compact design frees panel space. Together, these factors reduce installation time, downtime, and maintenance costs while improving overall equipment effectiveness.