ABB 1SBL136261R2200 Block Contactor - 690V AC-3 4P

Part Number: 1SBL136261R2200
Manufacturer
ABB
Part number
1SBL136261R2200

Quick Summary

ABB 1SBL136261R2200 block contactor provides robust motor switching for industrial drives and packaging lines. It addresses the common pain of control voltage fluctuations and wasted panel energy by combining AF technology with a wide control voltage range. Certified to IEC/EN 60947-1 and IEC/EN 60947-4-1, with UL 60335-2-40 and CSA compatibility, it supports global compliance. The design supports DIN rail mounting and easy extension with auxiliary contact blocks, delivering scalable protection while preserving precious panel space and reducing installation complexity for maintenance teams.

Product Information

Extended Description

1SBL136261R2200 ABB: The AF09ZB-40-00-22 is a 4 pole - 690 V IEC or 600 UL contactor with screw terminals, controlling motors up to 4 kW / 400 V AC (AC-3) and switching power circuits up to 25 A (AC-1) or 25 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (48-130 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
Motor control and protection for Rolling stock application_PDF
Instructions and Manuals
Installation instructions AF(C)09...38(Z)(B) Contactors, NF(C)(Z)(B)22...80E Contactor relays and CA4, CAL4, CAT4, CC4, LDC4 Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
45 mm
Product Net Depth / Length
77 mm
Product Net Height
86 mm
Product Net Weight
0.31 kg
Number of Main Contacts NO
4
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Number of Poles
4P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-1, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives.
Rated Operational Voltage
Main Circuit 690 V
Rated Frequency (f)
Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 35 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 25 A | (690 V) 60 °C 25 A | (690 V) 70 °C 22 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 9 A | (440 V) 60 °C 9 A | (500 V) 60 °C 9.5 A | (690 V) 60 °C 7 A | (380 / 400 V) 60 °C 9 A | (220 / 230 / 240 V) 60 °C 9 A
Rated Operational Current DC-1 (Ie)
(110 V) 1-Pole, 40 °C 10 A | (110 V) 1-Pole, 60 °C 10 A | (110 V) 1-Pole, 70 °C 10 A | (110 V) 2 Poles in Series, 40 °C 25 A | (110 V) 2 Poles in Series, 60 °C 25 A | (110 V) 2 Poles in Series, 70 °C 22 A | (110 V) 3 Poles in Series, 40 °C 25 A | (110 V) 3 Poles in Series, 60 °C 25 A | (110 V) 3 Poles in Series, 70 °C 22 A | (110 V) 4 Poles in Series, 40 °C 25 A | (110 V) 4 Poles in Series, 60 °C 25 A | (110 V) 4 Poles in Series, 70 °C 22 A | (220 V) 2 Poles in Series, 40 °C 10 A | (220 V) 2 Poles in Series, 60 °C 10 A | (220 V) 2 Poles in Series, 70 °C 10 A | (220 V) 3 Poles in Series, 40 °C 25 A | (220 V) 3 Poles in Series, 60 °C 25 A | (220 V) 3 Poles in Series, 70 °C 22 A | (220 V) 4 Poles in Series, 40 °C 25 A | (220 V) 4 Poles in Series, 60 °C 25 A | (220 V) 4 Poles in Series, 70 °C 22 A | (440 V) 4 Poles in Series, 40 °C 10 A | (440 V) 4 Poles in Series, 60 °C 10 A | (440 V) 4 Poles in Series, 70 °C 10 A | (72 V) 1-Pole, 40 °C 25 A | (72 V) 1-Pole, 60 °C 25 A | (72 V) 1-Pole, 70 °C 22 A | (72 V) 2 Poles in Series, 40 °C 25 A | (72 V) 2 Poles in Series, 60 °C 25 A | (72 V) 2 Poles in Series, 70 °C 22 A | (72 V) 3 Poles in Series, 40 °C 25 A | (72 V) 3 Poles in Series, 60 °C 25 A | (72 V) 3 Poles in Series, 70 °C 22 A | (72 V) 4 Poles in Series, 40 °C 25 A | (72 V) 4 Poles in Series, 60 °C 25 A | (72 V) 4 Poles in Series, 70 °C 22 A
Rated Operational Current DC-3 (Ie)
(110 V) 1-Pole, 40 °C 6 A | (110 V) 1-Pole, 60 °C 6 A | (110 V) 1-Pole, 70 °C 6 A | (110 V) 2 Poles in Series, 40 °C 25 A | (110 V) 2 Poles in Series, 60 °C 25 A | (110 V) 2 Poles in Series, 70 °C 22 A | (110 V) 3 Poles in Series, 40 °C 25 A | (110 V) 3 Poles in Series, 60 °C 25 A | (110 V) 3 Poles in Series, 70 °C 22 A | (110 V) 4 Poles in Series, 40 °C 25 A | (110 V) 4 Poles in Series, 60 °C 25 A | (110 V) 4 Poles in Series, 70 °C 22 A | (220 V) 2 Poles in Series, 40 °C 6 A | (220 V) 2 Poles in Series, 60 °C 6 A | (220 V) 2 Poles in Series, 70 °C 6 A | (220 V) 3 Poles in Series, 40 °C 25 A | (220 V) 3 Poles in Series, 60 °C 25 A | (220 V) 3 Poles in Series, 70 °C 22 A | (220 V) 4 Poles in Series, 40 °C 25 A | (220 V) 4 Poles in Series, 60 °C 25 A | (220 V) 4 Poles in Series, 70 °C 22 A | (440 V) 4 Poles in Series, 40 °C 6 A | (440 V) 4 Poles in Series, 60 °C 6 A | (440 V) 4 Poles in Series, 70 °C 6 A | (72 V) 1-Pole, 40 °C 25 A | (72 V) 1-Pole, 60 °C 25 A | (72 V) 1-Pole, 70 °C 22 A | (72 V) 2 Poles in Series, 40 °C 25 A | (72 V) 2 Poles in Series, 60 °C 25 A | (72 V) 2 Poles in Series, 70 °C 22 A | (72 V) 3 Poles in Series, 40 °C 25 A | (72 V) 3 Poles in Series, 60 °C 25 A | (72 V) 3 Poles in Series, 70 °C 22 A | (72 V) 4 Poles in Series, 40 °C 25 A | (72 V) 4 Poles in Series, 60 °C 25 A | (72 V) 4 Poles in Series, 70 °C 22 A
Rated Operational Current DC-5 (Ie)
(110 V) 1-Pole, 40 °C 4 A | (110 V) 1-Pole, 60 °C 4 A | (110 V) 1-Pole, 70 °C 4 A | (110 V) 2 Poles in Series, 40 °C 10 A | (110 V) 2 Poles in Series, 60 °C 10 A | (110 V) 2 Poles in Series, 70 °C 10 A | (110 V) 3 Poles in Series, 40 °C 25 A | (110 V) 3 Poles in Series, 60 °C 25 A | (110 V) 3 Poles in Series, 70 °C 22 A | (110 V) 4 Poles in Series, 40 °C 25 A | (110 V) 4 Poles in Series, 60 °C 25 A | (110 V) 4 Poles in Series, 70 °C 22 A | (220 V) 2 Poles in Series, 40 °C 4 A | (220 V) 2 Poles in Series, 60 °C 4 A | (220 V) 2 Poles in Series, 70 °C 4 A | (220 V) 3 Poles in Series, 40 °C 9 A | (220 V) 3 Poles in Series, 60 °C 9 A | (220 V) 3 Poles in Series, 70 °C 9 A | (220 V) 4 Poles in Series, 40 °C 10 A | (220 V) 4 Poles in Series, 60 °C 10 A | (220 V) 4 Poles in Series, 70 °C 10 A | (440 V) 4 Poles in Series, 40 °C 4 A | (440 V) 4 Poles in Series, 60 °C 4 A | (440 V) 4 Poles in Series, 70 °C 4 A | (72 V) 1-Pole, 40 °C 9 A | (72 V) 1-Pole, 60 °C 9 A | (72 V) 1-Pole, 70 °C 9 A | (72 V) 2 Poles in Series, 40 °C 25 A | (72 V) 2 Poles in Series, 60 °C 25 A | (72 V) 2 Poles in Series, 70 °C 22 A | (72 V) 3 Poles in Series, 40 °C 25 A | (72 V) 3 Poles in Series, 60 °C 25 A | (72 V) 3 Poles in Series, 70 °C 22 A | (72 V) 4 Poles in Series, 40 °C 25 A | (72 V) 4 Poles in Series, 60 °C 25 A | (72 V) 4 Poles in Series, 70 °C 22 A
Rated Operational Power AC-3 (Pe)
(400 V) 4 kW | (415 V) 4 kW | (440 V) 4 kW | (500 V) 5.5 kW | (690 V) 5.5 kW | (380 / 400 V) 4 kW | (220 / 230 / 240 V) 2.2 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 48 ... 130 V | 60 Hz 48 ... 130 V | DC Operation 48 ... 130 V
Power Loss
at Rated Operating Conditions AC-1 per Pole 0.8 W | at Rated Operating Conditions AC-3 per Pole 0.1 W
Operate Time
Between Coil De-energization and NC Contact Closing 13 ... 98 ms | Between Coil De-energization and NO Contact Opening 11 ... 95 ms | Between Coil Energization and NC Contact Opening 38 ... 90 ms | Between Coil Energization and NO Contact Closing 40 ... 95 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 0.75 ... 6 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 4 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² | Rigid Solid 1/2x 1 ... 4 mm² | Rigid Stranded 1/2x 1 ... 6 mm²
Connecting Capacity Auxiliary Circuit
Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Control Circuit 10 mm | Main Circuit 10 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Tightening Torque
Control Circuit 1.2 N·m | Main Circuit 1.5 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 25 A
Connecting Capacity Main Circuit UL/CSA
Rigid Solid 1/2x 16-10 AWG | Rigid Stranded 1/2x 16-10 AWG
Connecting Capacity Auxiliary Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG | Rigid Stranded 1/2x 18-14 AWG
Connecting Capacity Control Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG | Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSA
Control Circuit 11 in·lb | Main Circuit 13 in·lb
Ambient Air Temperature
Close to Contactor for Storage -60 ... +80 °C | Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Shock and Vibration Withstand acc. to IEC 61373
Category 1, Class B
Pollution Degree
3
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
c36e80bb-553c-476f-88e2-a23965abcddc China (CN)
Simplified SCIP
608a0822-53b1-4d49-b5c6-102395629976 Poland (PL) | b8af45fe-5f6d-4684-a5c0-9e1388956f83 Czech Republic (CZ) | 45801744-d7ac-4ac8-90a1-3d86e51b04c8 Sweden (SE) | c65f772b-6b10-4f4f-9d69-094acbf42720 Germany (DE) | f38d6315-4720-4bbe-83ba-ed85320d1b37 Norway (NO) | d8c850d9-618b-4793-89d9-548187bb7496 Belgium (BE) | 5835657a-7656-4813-b514-29a4d41be6f3 Finland (FI) | 0a63e959-4c21-4821-8c50-4b1cd1b6301b Denmark (DK) | 628d6717-69b3-4ef0-8d3d-336baba8341e Germany (DE) | ff8e50db-8ad8-4962-bd9d-d35eb82862a7 Germany (DE) | a80e8b94-f91b-4cba-8756-e5334fcbeaaf Croatia (HR) | cffd360e-0af1-4a18-b3dc-581ed93d5028 Greece (GR) | da762866-25e1-4804-85fa-6ed043e1eaf8 Estonia (EE) | c954e4d1-7403-43b4-a8d6-f4042b224e35 Hungary (HU) | 373b62f1-185e-4c11-88d6-45218b06a919 Netherlands (NL) | 7c93fa55-04b2-4095-97f6-91115a221ca5 Poland (PL) | 06b9e1d3-94b5-419a-bfaf-c24130755c93 Spain (ES) | 5b80ebab-3ca4-4b38-bdbd-1b198984087e Belgium (BE) | 21beabb6-ec81-4922-835b-300691fb3a67 Hungary (HU) | cf0af572-e006-4047-987c-b50d52fb1119 France (FR) | 5be04ab9-70bf-47f2-8a10-00d1ac1c06d9 Germany (DE) | bfabc05c-6223-40e1-b604-39fa5f0b3d7d Poland (PL) | d1758f79-830c-4c03-8365-9eebf9940984 Bulgaria (BG) | dffe877b-ce89-4a0b-9cb6-fd9eb53cc764 Portugal (PT) | 7d7b9a82-a476-41f1-8137-813604b17ef6 France (FR) | 2565b5c8-e1c6-44d1-8540-b3c476032686 Germany (DE) | 11f09a80-dc3c-473a-9edd-b8adf6b78fdf Sweden (SE)
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
End Of Life Disassembling Instructions
End of life instruction AF(S)09/12/16/26/30/38(Z)(B)(K)(RT) Contactors & NF(Z)(B)(K)(RT) Contactors relays
Environmental Product Declaration - EPD
Environmental Product Declaration - AF09/12/16(Z)(B) Contactors and NF(Z) Contactor relaysAF(S)09/12/16(Z)(B) Contactors and NF(Z)(B) Contactors Relays (FR) | Environmental Product Declaration - AF09/12/16(Z)(B) Contactors and NF(Z) Contactor relays
Sustainable Material Content in Packaging (wt. %)
Recycled Cardboard - 86 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 28 %
A2L Certificate – UL
UL-US A2L LZGH2 Certificate of Compliance AF09 ... AF38 3-pole contactors with screw terminals - UL 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers | UL-CA A2L LZGH2 Certificate of Compliance AF09 ... AF38 3-pole contactors with screw terminals - CSA C22.2 No. 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers
CB Certificate
CB Certificate AF09, AF12, AF16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
CCC Certificate
CCC Certificate AF09, AF12, AF16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
CQC Certificate
CQC Certificate AF(C)09, AF(C)12, AF(C)16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
Declaration of Conformity - CCC
CCC Declaration of Conformity, Contactor, AF*09, AF*12, AF*16, Made in France
Declaration of Conformity - CE
EU Declaration of Conformity AF09 ... AF38(Z)B..(K), AF40B ... AF96B 3 and 4-pole contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09 ... AF38(Z)B..(K), AF40B ... AF96B 3 and 4-pole contactors
GOST Certificate
GOST_POCCFR.ME77.B07175.pdf
KC Certificate
KC Certificate AF09 4pole contactors
UL Certificate
UL-US Certificate of Compliance AF(C)09..(K) ... AF(C)38 4-pole contactors with screw and push-in spring terminals | UL-CA Certificate of Compliance AF(C)09..(K) ... AF(C)38 4-pole contactors with screw and push-in spring terminals
UL Listing Card
UL_E319322
Package Level 1 Units
box 1 piece
Package Level 1 Width
87 mm
Package Level 1 Depth / Length
79 mm
Package Level 1 Height
47 mm
Package Level 1 Gross Weight
0.31 kg
Package Level 1 EAN
3471523124424
Package Level 2 Units
box 27 piece
Package Level 2 Width
250 mm
Package Level 2 Depth / Length
300 mm
Package Level 2 Height
315 mm
Package Level 2 Gross Weight
16.74 kg
Package Level 3 Units
1296 piece
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
Feature AF technology delivers a wide control voltage range of 48–130 V and DC operation, reducing control voltage sensitivity and panel energy waste. Business Impact Reliable operation in networks with voltage fluctuations; application in diverse control loops. Application Motor control in manufacturing lines and packaging equipment. Feature Four main contacts in a 4P configuration with 690 V rated main circuit, AC-1 up to 25 A and AC-3 up to 9 A, enabling efficient motor start/stop sequences. Business Impact Higher load handling with lower heat dissipation; application in small to mid-size industrial drives. Application Light to medium industrial drive applications. Feature Built-in surge protection provides compact protection against voltage transients. Business Impact Simplified panel design and fewer separate protective devices; application in space-constrained control panels. Feature Compact block design with screw terminals and DIN rail mounting TH35-15/TH35-7.5 enables quick installation. Business Impact Faster commissioning and neater wiring; application in new builds and upgrades. Feature Add-on auxiliary contact blocks extend functionality without replacing the base unit. Business Impact Flexible monitoring and interlocking for process safety; application in conveyors and sorter systems. Feature Low power loss of 0.8 W per pole under AC-1 and 0.1 W per pole under AC-3, improving energy efficiency. Business Impact Reduced energy consumption in control circuits; application in energy-conscious panel design. Feature Comprehensive compliance and environmental data including RoHS, REACH, EPD documentation, and multiple national certifications. Business Impact Assurance for global deployments and supplier sustainability; application in regulated industries. Feature DIN rail mounting and screw-terminal connections support versatile installation and future-proofing. Business Impact Easier retrofits and scalable control architectures; application in equipment upgrades and lifecycle planning.

Get a Quick Quote for a ABB 1SBL136261R2200

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SBL136261R2200? Enquire Now

FAQs

The device mounts on TH35-15 or TH35-7.5 DIN rails, with screw terminals for main and control circuits. Main circuit terminals accept flexible ferrule 0.75–6 mm² and rigid/Solid 0.5–4 mm², while control circuit terminals accommodate ferrule 0.75–2.5 mm². Use the 2 x M4 screws for chassis mounting and tighten to 1.5 N·m on main circuit connections, 1.2 N·m on control circuit.
Rated Operational Current AC-1: 25 A at 690 V (60 °C 25 A; 70 °C 22 A). Rated Operational Current AC-3: 9 A at 415–690 V (various voltages listed up to 440–500 V). Maximum breaking capacity and short-time withstand values support reliable motor starting and protection in standard industrial drives.
Yes, it meets multiple standards including IEC/EN 60947-1 and IEC/EN 60947-4-1, with UL and CSA alignments for general use. It also conforms to EN 50155 and other environmental specs, enabling reliable operation in rolling stock and transport-related applications, provided installation follows the specified mounting and protection guidelines.
Certifications include IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40, CSA equivalents, and CE/UKCA declarations. Environmental data covers RoHS compliance, REACH declarations, and an EPD for AF contactors, underscoring responsible material use and lifecycle considerations.
The wide control voltage range reduces panel wiring complexity and energy waste in unstable networks, while built-in surge protection lowers auxiliary protection costs. Combined with DIN rail simplicity and scalable auxiliary blocks, this supports faster commissioning, reduced maintenance, and a lower total cost of ownership over the line’s lifecycle.