ABB 1SBL136560R2200 Block Contactor - 690V IEC/UL

Part Number: 1SBL136560R2200
Manufacturer
ABB
Part number
1SBL136560R2200

Quick Summary

ABB 1SBL136560R2200 Block Contactor is a four-pole motor control device designed for reliable start-stop of medium-power motors in industrial applications. In practice, engineers often contend with voltage fluctuation and wasted panel energy; this contactor’s wide 48–130 V control voltage range helps stabilize operation across unstable networks. It complies with key standards such as IEC/EN 60947-1, IEC 60947-4-1, and UL 60947-4-1, with additional CSA and EN 50155 applicability depending on configuration. Beyond compliance, its compact AF technology and modular accessory options enable easy integration, reduced wiring complexity, and long-term cost savings for equipment fleets in automation and process industries.

Product Information

Extended Description

1SBL136560R2200 ABB: The AF09ZB-22-00RT-22 is a 4 pole - 690 V IEC or 600 UL contactor with Ring-Tongue Terminals, controlling motors up to 4 kW / 400 V AC (AC-3) and switching power circuits up to 25 A (AC-1) or 25 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (48-130 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
Motor control and protection for Rolling stock application_PDF
Instructions and Manuals
Installation instructions AF09...38(Z)B-..RT Contactors, NF(Z)B..ERT Contactor relays and CA4..RT, CAL4..RT, CAT4..RT, LDC4RT Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
45 mm
Product Net Depth / Length
77 mm
Product Net Height
86 mm
Product Net Weight
0.32 kg
Number of Main Contacts NO
2
Number of Main Contacts NC
2
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Number of Poles
4P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives.
Rated Operational Voltage
Main Circuit 690 V
Rated Frequency (f)
Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 35 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 25 A | (690 V) 60 °C 25 A | (690 V) 70 °C 22 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 9 A | (440 V) 60 °C 9 A | (500 V) 60 °C 9.5 A | (690 V) 60 °C 7 A | (380 / 400 V) 60 °C 9 A | (220 / 230 / 240 V) 60 °C 9 A
Rated Operational Power AC-3 (Pe)
(400 V) 4 kW | (415 V) 4 kW | (440 V) 4 kW | (500 V) 5.5 kW | (690 V) 5.5 kW | (380 / 400 V) 4 kW | (220 / 230 / 240 V) 2.2 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 48 ... 130 V | 60 Hz 48 ... 130 V | DC Operation 48 ... 130 V
Power Loss
at Rated Operating Conditions AC-1 per Pole 0.8 W | at Rated Operating Conditions AC-3 per Pole 0.1 W
Operate Time
Between Coil De-energization and NC Contact Closing 13 ... 98 ms | Between Coil De-energization and NO Contact Opening 11 ... 95 ms | Between Coil Energization and NC Contact Opening 38 ... 90 ms | Between Coil Energization and NO Contact Closing 40 ... 95 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 screws placed diagonally
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP10 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Tightening Torque
Control Circuit 1.2 N·m | Main Circuit 1.5 N·m
Terminal Type
Ring-Tongue Terminals
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 25 A
Tightening Torque UL/CSA
Control Circuit 11 in·lb | Main Circuit 13 in·lb
Ambient Air Temperature
Close to Contactor for Storage -60 ... +80 °C | Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Shock and Vibration Withstand acc. to IEC 61373
Category 1, Class B
Pollution Degree
3
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
d54811ad-a3ba-4056-855d-b4e71142d4e7 China (CN)
Simplified SCIP
9600ab80-61ed-4d38-b13d-ba0c7e82d0b3 Hungary (HU) | e7f1d739-aaee-4f14-86df-ea7126cc0b3d Belgium (BE) | e2ada1af-836a-41e5-a108-5963d9e8e7ca Germany (DE) | 97259e8b-ed5d-4d54-b467-5cbb55b3483c Sweden (SE) | 6a663755-ae20-4834-a7b1-db32eeaf63df Germany (DE) | 467830db-d644-4457-a9e5-9320ea0e9b05 Bulgaria (BG) | c71f7500-771b-4c80-a0a5-af22ca991292 Portugal (PT) | f1d67681-10c4-450d-a7a6-a2e10f6f2d79 Sweden (SE) | b4e06d93-ef44-408c-84a4-2170377e7209 Poland (PL) | 921ff4f3-c351-4ce0-9ebf-c6efe9699c22 France (FR) | d4f4b085-2f60-49fc-af6c-c7e48a02bf40 Hungary (HU) | 4e51fda9-6d32-4392-a8b9-8599d1509aaa Poland (PL) | 3b636f86-59c8-4813-a83a-c7a0c36dc0bd Netherlands (NL) | 3161fe5a-eacd-4d18-adbf-de44a719b2a8 Greece (GR) | cd3dafa2-16ed-42eb-9fe2-f10348c5ae31 Estonia (EE) | 65e6d641-6f42-4400-b3a2-b84fe766dc3e Norway (NO) | 6d634f37-2d8f-4389-885d-fae138daf065 Finland (FI) | 6fd80042-e9c0-4940-b0d7-00f3e4d74fc8 Belgium (BE) | 4f8fc184-4c74-4de2-9375-d7e0708fe0dd Germany (DE) | 8e9b7d6c-5720-4329-a35a-f768b3c3700f Czech Republic (CZ) | 35846601-e1b7-4e08-9b32-73e2423ea95e France (FR) | 5e0d24db-7968-4388-b815-b2eb841b8aa9 Poland (PL) | f87ecf75-8275-4ee8-8393-9f0a5dc36779 Spain (ES) | 54132fb9-3870-4ba2-861d-c08fbe992044 Croatia (HR) | 4edb9e90-686c-4bf3-9c94-57314badea2b Denmark (DK) | 1652774b-e28d-4314-abef-398ecfc47f35 Germany (DE) | 2031f5e4-3e16-45e6-9b0d-048c141ef5ac Germany (DE)
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
End Of Life Disassembling Instructions
End of life instruction AF(S)09/12/16/26/30/38(Z)(B)(K)(RT) Contactors & NF(Z)(B)(K)(RT) Contactors relays
Environmental Product Declaration - EPD
Environmental Product Declaration - AF09/12/16(Z)(B) Contactors and NF(Z) Contactor relaysAF(S)09/12/16(Z)(B) Contactors and NF(Z)(B) Contactors Relays (FR) | Environmental Product Declaration - AF09/12/16(Z)(B) Contactors and NF(Z) Contactor relays
Sustainable Material Content in Packaging (wt. %)
Recycled Cardboard - 86 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 28 %
CB Certificate
CB Certificate AF09, AF12, AF16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
CCC Certificate
CCC Certificate AF09, AF12, AF16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
CQC Certificate
CQC Certificate AF(C)09, AF(C)12, AF(C)16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
Declaration of Conformity - CCC
CCC Declaration of Conformity, Contactor, AF*09, AF*12, AF*16, Made in France
Declaration of Conformity - CE
EU Declaration of Conformity AF09 to AF38(Z)B..RT 3 and 4-pole contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09 to AF38(Z)B..RT 3 and 4-pole contactors
UL Listing Card
UL_E319322
UR Certificate
UR Certificate of Compliance AF09...AF38(Z)B-..RT 4-pole contactors with ring tongue terminals
Package Level 1 Units
box 1 piece
Package Level 1 Width
87 mm
Package Level 1 Depth / Length
79 mm
Package Level 1 Height
47 mm
Package Level 1 Gross Weight
0.32 kg
Package Level 1 EAN
3471523129726
Package Level 2 Units
box 27 piece
Package Level 2 Width
250 mm
Package Level 2 Depth / Length
300 mm
Package Level 2 Height
315 mm
Package Level 2 Gross Weight
17.28 kg
Package Level 3 Units
1296 piece
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
Feature: AF technology with a wide control voltage range 48–130 V AC/DC. Business Impact: Enables reliable control across voltage variations, reducing nuisance tripping and energy waste in representative panels. Application: Suitable for machines powered by variable networks in conveyors and processing lines. Feature: 4-pole block contactor with 2 NO and 2 NC main contacts. Business Impact: Delivers robust motor starting for up to 4 kW at 400–690 V, improving line throughput and reducing downtime. Application: Drives small to mid-size motors in manufacturing and packaging lines. Feature: Built-in surge protection. Business Impact: Protects contacts from transient overvoltages, lowering maintenance costs and extending service life. Application: Critical in areas with unstable power quality or long cable runs. Feature: Ring-Tongue terminals and IP10 terminations. Business Impact: Simplifies wiring, improves reliability, and accelerates installation while easing field maintenance. Application: Direct-wielding and modular wiring in control cabinets. Feature: Compact footprint (45 mm width, 77 mm depth, 86 mm height) and 0.32 kg weight. Business Impact: Space-saving DIN rail or panel mounting enables denser control architectures and easier retrofits. Application: Panels with tight cross-sections and retrofits in existing machines. Feature: Modularity with add-on auxiliary contact blocks and accessories. Business Impact: Scales from basic to multifunction control without replacing hardware, reducing spare-part inventories. Application: Customized control schemes for different line configurations and future upgrades. Feature: Compliance with IEC/EN, UL/CSA, and RoHS/REACH. Business Impact: Ensures compatibility with global procurement and reduces risk when sourcing for multinational facilities. Application: Global manufacturing operations and equipment modernization programs.

Get a Quick Quote for a ABB 1SBL136560R2200

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SBL136560R2200? Enquire Now

FAQs

Yes. The 1SBL136560R2200 supports DIN-rail mounting on TH35-15 or TH35-7.5 rails, and it can also be mounted using two diagonal M4 screws for panel integration. The design includes Ring-Tongue terminals and IP10 protection for coil connections, simplifying installation and future servicing.
For AC-1 at 690 V, Ie is 25 A at 40 °C, 25 A at 60 °C, and 22 A at 70 °C. For AC-3, Ie is 9 A across common voltages (e.g., 380–440 and up to 690 V) at 60 °C. This makes the device suitable for motor start/stop tasks up to about 4 kW depending on the voltage and temperature rating.
It's ideal for motor control in conveyors, processing lines, and rolling stock-related drives, where reliable switching of motors up to 4 kW is required. The wide control voltage range and built-in surge protection help tolerate network fluctuations, while modular accessories support scalable control schemes for future upgrades.
The device complies with IEC/EN 60947-1 and 60947-4-1, UL 60947-4-1, CSA C22.2, EN 50155 (where applicable), and RoHS/REACH requirements. Certifications include UL Listing Card (UL_E319322) and CE/UKCA declarations, supporting global procurement and regulatory compliance.
Low coil power loss (0.8 W per pole for AC-1, 0.1 W per pole for AC-3) reduces energy consumption in standby and operation. Built-in surge protection minimizes contact wear, while modular accessories enable easy upgrades without new hardware. Together, these factors lower total cost of ownership and shorten payback periods in automation projects.