ABB 1SBL176005T2310 - Block Contactor, 690V IEC/UL
Part Number: 1SBL176005T2310
Quick Summary
Block Contactor AF16Z-30-10K-23T switches 690 V motor circuits in industrial automation. Users seek reliable control under variable voltages and harsh plant conditions. It carries CE, UKCA, and UL/CSA certifications, plus IP20 protection, providing confidence across global installations. Built for compact panels, the device supports a wide control voltage range of 100–250 V AC or DC, and features built-in surge protection to guard against transients. The design also benefits from AF technology, a block-type layout that is easily extended with auxiliary contact blocks. In practice, this means easier maintenance, faster commissioning, and measurable energy savings in complex motor control schemes, with compatibility for DIN-rail mounting and modern accessory ecosystems.
Product Information
Extended Description
1SBL176005T2310 ABB: The AF16Z-30-10K-23T is a 3 pole - 690 V IEC or 600 V UL contactor with 1 built-in auxiliary contact and Push-In, switching power circuits up to 30 A (AC-1) or 30 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Data Sheet, Technical Information
1SBC100214C0202 - Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) - Edition 2024
Instructions and Manuals
Installation instructions AF(C)09...38(Z)(B)..K Contactors, NF(C)(Z)(B)..K Contactor relays and CA4..K, CAL4..K, LDC4K Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
45 mm
Product Net Depth / Length
77 mm
Product Net Height
92.3 mm
Product Net Weight
0.315 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
0
Number of Poles
3P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1
Rated Operational Voltage
Auxiliary Circuit 690 V | Main Circuit 690 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 Hz | Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 35 A | acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 30 A | (690 V) 60 °C 30 A | (690 V) 70 °C 26 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 18 A | (440 V) 60 °C 18 A | (500 V) 60 °C 15 A | (690 V) 60 °C 10.5 A | (380 / 400 V) 60 °C 18 A | (220 / 230 / 240 V) 60 °C 18 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 18 A | (440 V) 60 °C 18 A | (500 V) 60 °C 15 A | (690 V) 60 °C 10.5 A | (380 / 400 V) 60 °C 18 A | (220 / 230 / 240 V) 60 °C 18 A
Rated Operational Current AC-15 (Ie)
(500 V) 2 A | (690 V) 2 A | (24 / 127 V) 6 A | (220 / 240 V) 4 A | (400 / 440 V) 3 A
Rated Operational Current DC-1 (Ie)
(110 V) 1-Pole, 40 °C 20 A | (110 V) 1-Pole, 60 °C 20 A | (110 V) 1-Pole, 70 °C 20 A | (110 V) 2 Poles in Series, 40 °C 30 A | (110 V) 2 Poles in Series, 60 °C 30 A | (110 V) 2 Poles in Series, 70 °C 26 A | (110 V) 3 Poles in Series, 40 °C 30 A | (110 V) 3 Poles in Series, 60 °C 30 A | (110 V) 3 Poles in Series, 70 °C 26 A | (220 V) 2 Poles in Series, 40 °C 20 A | (220 V) 2 Poles in Series, 60 °C 20 A | (220 V) 2 Poles in Series, 70 °C 20 A | (220 V) 3 Poles in Series, 40 °C 30 A | (220 V) 3 Poles in Series, 60 °C 30 A | (220 V) 3 Poles in Series, 70 °C 26 A | (72 V) 1-Pole, 40 °C 30 A | (72 V) 1-Pole, 60 °C 30 A | (72 V) 1-Pole, 70 °C 26 A | (72 V) 2 Poles in Series, 40 °C 30 A | (72 V) 2 Poles in Series, 60 °C 30 A | (72 V) 2 Poles in Series, 70 °C 26 A | (72 V) 3 Poles in Series, 40 °C 30 A | (72 V) 3 Poles in Series, 60 °C 30 A | (72 V) 3 Poles in Series, 70 °C 26 A
Rated Operational Current DC-3 (Ie)
(110 V) 1-Pole, 40 °C 8 A | (110 V) 1-Pole, 60 °C 8 A | (110 V) 1-Pole, 70 °C 8 A | (110 V) 2 Poles in Series, 40 °C 30 A | (110 V) 2 Poles in Series, 60 °C 30 A | (110 V) 2 Poles in Series, 70 °C 26 A | (110 V) 3 Poles in Series, 40 °C 30 A | (110 V) 3 Poles in Series, 60 °C 30 A | (110 V) 3 Poles in Series, 70 °C 26 A | (220 V) 2 Poles in Series, 40 °C 8 A | (220 V) 2 Poles in Series, 60 °C 8 A | (220 V) 2 Poles in Series, 70 °C 8 A | (220 V) 3 Poles in Series, 40 °C 30 A | (220 V) 3 Poles in Series, 60 °C 30 A | (220 V) 3 Poles in Series, 70 °C 26 A | (72 V) 1-Pole, 40 °C 30 A | (72 V) 1-Pole, 60 °C 30 A | (72 V) 1-Pole, 70 °C 26 A | (72 V) 2 Poles in Series, 40 °C 30 A | (72 V) 2 Poles in Series, 60 °C 30 A | (72 V) 2 Poles in Series, 70 °C 26 A | (72 V) 3 Poles in Series, 40 °C 30 A | (72 V) 3 Poles in Series, 60 °C 30 A | (72 V) 3 Poles in Series, 70 °C 26 A
Rated Operational Current DC-5 (Ie)
(110 V) 1-Pole, 40 °C 4 A | (110 V) 1-Pole, 60 °C 4 A | (110 V) 1-Pole, 70 °C 4 A | (110 V) 2 Poles in Series, 40 °C 20 A | (110 V) 2 Poles in Series, 60 °C 20 A | (110 V) 2 Poles in Series, 70 °C 20 A | (110 V) 3 Poles in Series, 40 °C 30 A | (110 V) 3 Poles in Series, 60 °C 30 A | (110 V) 3 Poles in Series, 70 °C 26 A | (220 V) 2 Poles in Series, 40 °C 4 A | (220 V) 2 Poles in Series, 60 °C 4 A | (220 V) 2 Poles in Series, 70 °C 4 A | (220 V) 3 Poles in Series, 40 °C 16 A | (220 V) 3 Poles in Series, 60 °C 16 A | (220 V) 3 Poles in Series, 70 °C 16 A | (72 V) 1-Pole, 40 °C 16 A | (72 V) 1-Pole, 60 °C 16 A | (72 V) 1-Pole, 70 °C 16 A | (72 V) 2 Poles in Series, 40 °C 30 A | (72 V) 2 Poles in Series, 60 °C 30 A | (72 V) 2 Poles in Series, 70 °C 26 A | (72 V) 3 Poles in Series, 40 °C 30 A | (72 V) 3 Poles in Series, 60 °C 30 A | (72 V) 3 Poles in Series, 70 °C 26 A
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W | (48 V) 2.8 A / 134 W | (72 V) 1 A / 72 W | (110 V) 0.55 A / 60 W | (125 V) 0.55 A / 69 W | (220 V) 0.27 A / 60 W | (250 V) 0.27 A / 68 W | (400 V) 0.15 A / 60 W | (500 V) 0.13 A / 65 W | (600 V) 0.1 A / 60 W
Rated Operational Power AC-3 (Pe)
(415 V) 9 kW | (440 V) 9 kW | (500 V) 9 kW | (690 V) 9 kW | (380 / 400 V) 7.5 kW | (220 / 230 / 240 V) 4 kW
Rated Operational Power AC-3e (Pe)
(415 V) 9 kW | (440 V) 9 kW | (500 V) 9 kW | (690 V) 9 kW | (380 / 400 V) 7.5 kW | (220 / 230 / 240 V) 4 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A | for 0.1 s 140 A | for 1 s 100 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 V | acc. to IEC 60947-5-1 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-15) 1200 cycles per hour | (AC-2 / AC-4) 300 cycles per hour | (AC-3) 1200 cycles per hour | (DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 100 ... 250 V | 60 Hz 100 ... 250 V | DC Operation 100 ... 250 V
Power Loss
at 6 A per Pole 0.1 W | at Rated Operating Conditions AC-1 per Pole 1.64 W | at Rated Operating Conditions AC-3 per Pole 0.6 W
Operate Time
Between Coil De-energization and NC Contact Closing 13 ... 98 ms | Between Coil De-energization and NO Contact Opening 11 ... 95 ms | Between Coil Energization and NC Contact Opening 38 ... 90 ms | Between Coil Energization and NO Contact Closing 40 ... 95 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 0.5 ... 4 mm² | Flexible with Insulated Ferrule 1x 0.5 ... 4 mm² | Flexible with Insulated Ferrule 2x 0.5 ... 2.5 mm² | Flexible 1/2x 0.5 ... 4 mm² | Rigid 1/2x 1 ... 6 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 4 ... 6 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 1/2x 0.5 ... 2.5 mm² | Flexible with Insulated Ferrule 1/2x 0.5 ... 1.5 mm² | Flexible 1/2x 0.5 ... 2.5 mm² | Rigid 1/2x 1 ... 2.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.5 ... 2.5 mm² | Flexible with Insulated Ferrule 1/2x 0.5 ... 1.5 mm² | Flexible 1/2x 0.5 ... 2.5 mm² | Rigid 1/2x 1 ... 2.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Auxiliary Circuit 10 mm | Control Circuit 10 mm | Main Circuit 10 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Terminal Type
Push-in Spring Terminals
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 30 A
Horsepower Rating UL/CSA
(120 V AC) Single Phase 1-1/2 hp | (200 ... 208 V AC) Three Phase 5 hp | (220 ... 240 V AC) Three Phase 5 hp | (240 V AC) Single Phase 3 hp | (440 ... 480 V AC) Three Phase 10 hp | (550 ... 600 V AC) Three Phase 15 hp
Connecting Capacity Main Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG | Rigid Stranded 1/2x 18-10 AWG
Connecting Capacity Auxiliary Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG
Connecting Capacity Control Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG
Full Load Amps Motor Use
(120 V AC) Single Phase 20 A | (200 ... 208 V AC) Three Phase 17.5 A | (220 ... 240 V AC) Three Phase 15.2 A | (240 V AC) Single Phase 17 A | (440 ... 480 V AC) Three Phase 14 A | (550 ... 600 V AC) Three Phase 17 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -25 ... 60 °C | Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C | Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Resistance to Vibrations
4g Closed Position & 2g Open position 5 ... 300 Hz
Pollution Degree
3
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
ABS Certificate
ABS Certificate, AF(S)09 to AF(S)96 contactors, NF contactor relays and CA4, CC4, CAL4, CAT4 auxiliary contact blocks, TEF4 electronic timers
CB Certificate
CB Certificate AF09, AF12, AF16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
CCC Certificate
CCC Certificate AF09, AF12, AF16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
CQC Certificate
CQC Certificate AF(C)09, AF(C)12, AF(C)16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors | CQC Certificate, Contactor, AF09,AF12,AF16, Made in China
Declaration of Conformity - CCC
CCC Declaration of Conformity, Contactor, AF*09, AF*12, AF*16, Made in France | CCC Declaration of Conformity, Contactor, AF09,AF12,AF16, Made in China
Declaration of Conformity - CE
EU Declaration of Conformity AF09... AF96-30-.., AF09...38(Z)-30..K 3-pole Contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09... AF96-30-.., AF09...38(Z)-30..K 3-pole Contactors
DNV Certificate
DNV Certificate AF(S)09...96 3-pole & AF09...80 4-pole contactors with screw, spring, push-in terminals
LR Certificate
LRS Certificate AF(S)09..(K) ... AF96 3 and 4-pole contactors and CA(L)4..(K), CAT4, CC4 auxiliary contact blocks
RINA Certificate
Rina Certificate for AF(S)09...AF(S)96 contactors, NF contactor relays and accessories with screw,spring and push-in terminals
RMRS Certificate
RMRS Certificate AF(S)09(S)...AF(S)38 3-pole and 4-pole, AF(S)40..96 3-pole contactors with screw, push-in and spring terminals
UL Certificate
UL-US Certificate of Compliance AF(C)(S)09(R/M/N)-..(L)(S)(K)...AF(C)(S)38(R/M/N)..(K) 3-pole contactors screw, spring and push-in spring terminals; LDC4 additional coil terminal block; LF16-4, LG16-4, LF38-4 and LH38-4 connecting strips, LD38-4 additional terminal block | UL-CA Certificate of Compliance AF(C)(S)09(R/M/N)-..(L)(S)(K)...AF(C)(S)38(R/M/N)..(K) 3-pole contactors screw, spring and push-in spring terminals; LDC4 additional coil terminal block; LF16-4, LG16-4, LF38-4 and LH38-4 connecting strips, LD38-4 additional terminal block
Package Level 1 Units
box 1 piece
Package Level 1 Width
93 mm
Package Level 1 Depth / Length
86 mm
Package Level 1 Height
45 mm
Package Level 1 Gross Weight
0.33 kg
Package Level 1 EAN
3471523018419
Package Level 2 Units
box 120 piece
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
Feature: AF technology delivers wide control voltage range and surge protection. Business Impact: Reduces panel energy consumption and guards against voltage variations, improving reliability in unstable networks. Application: Ideal for large control panels where supply voltage fluctuates and motor protection is critical. Feature: 3 main NO contacts with 1 NO auxiliary contact and 690 V ratings. Business Impact: Enables robust AC-1/AC-3 motor switching up to 30 A, with a compact 3P footprint. Application: Suitable for conveyors, pumps, and fans in automated lines. Feature: Push-In Spring Terminals and DIN-rail mounting options (TH35-15 / TH35-7.5). Business Impact: Speeds installation, simplifies wiring, and streamlines field service. Application: Reliable across panel densities and modular installations. Feature: Built-in surge protection and low I²t power loss. Business Impact: Enhances longevity, lowers maintenance costs, and supports high cycling with predictable performance. Application: Industrial environments demanding repeatable switching with minimal heat. Feature: Comprehensive standards coverage (IEC/EN, UL/CSA). Business Impact: Ensures regulatory compliance and easier cross-border deployment. Application: Global manufacturing and OEM integrations. Feature: Flexible connection capacities (Main, Auxiliary, Control circuits). Business Impact: Reduces termination time, accommodates a range of conductor types and sizes. Application: Panels with mixed wiring schemes and future-proofing for accessory blocks.
Get a Quick Quote for a ABB 1SBL176005T2310
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SBL176005T2310?
Enquire Now
FAQs
The AF16Z-30-10K-23T supports DIN-rail mounting TH35-15 or TH35-7.5 in addition to screw mounting with 2 x M4 screws. This provides flexible integration into existing panel layouts and simplifies retrofits, especially in compact control cabinets where space is at a premium.
For AC-1 operation at 690 V, the device provides 30 A rated current, with variations up to 60 °C. AC-3 ratings reach 18 A at typical voltages such as 380–690 V. The unit also supports AC-3e and DC-1/DC-3 regimes per catalog data, enabling versatile motor switching across multiple load profiles.
The contactor complies with IEC/EN 60947-1 and IEC/EN 60947-4-1, with UL 60947-4-1 and CSA equivalents. UKCA and CE declarations are provided, along with multiple product safety certifications. IP20 protection ensures safe operation within typical control panel environments, supporting global deployment.
The 100–250 V control range (AC or DC) allows the coil to operate reliably despite voltage fluctuations, reducing nuisance tripping and panel energy waste. This is especially beneficial in plants with unstable mains or long cable runs, where consistent coil energization translates to smoother motor starts and fewer control faults.
With built-in surge protection and low power loss per pole (0.1 W; 1.64 W per pole under rated AC-1), the device minimizes heat and extends component life. Push-in terminals simplify wiring and future upgrades, reducing commissioning time and maintenance costs while delivering predictable, repeatable motor control performance.