ABB 1SBL176060R2201 Block Contactor - IEC/UL 60947-4-1

Part Number: 1SBL176060R2201
Manufacturer
ABB
Part number
1SBL176060R2201

Quick Summary

Block Contactor 1SBL176060R2201 provides reliable motor control for industrial conveyors and packaging lines. In demanding panels, voltage variation and nuisance tripping can waste energy and reduce uptime; this device aims to minimize those issues with a wide control voltage range and built-in protections. It is designed to meet IEC/EN 60947-4-1, UL 60947-4-1, and CSA C22.2 standards, with CE/UKCA declarations for global compliance. The combination of compact DIN-rail mounting, optional add-on auxiliary contacts, and Ring-Tongue terminations supports scalable, cost-efficient installations while delivering robust performance for modern automation environments.

Product Information

Extended Description

1SBL176060R2201 ABB: The AF16ZB-30-01RT-22 is a 3 pole - 690 V IEC or 600 UL contactor with 1 built-in auxiliary contact and Ring-Tongue Terminals, controlling motors up to 7.5 kW / 400 V AC (AC-3) or 10 hp / 480 V UL and switching power circuits up to 30 A (AC-1) or 30 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (48-130 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
Motor control and protection for Rolling stock application_PDF
Instructions and Manuals
Installation instructions AF09...38(Z)B-..RT Contactors, NF(Z)B..ERT Contactor relays and CA4..RT, CAL4..RT, CAT4..RT, LDC4RT Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
45 mm
Product Net Depth / Length
77 mm
Product Net Height
86 mm
Product Net Weight
0.32 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
1
Number of Poles
3P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives.
Rated Operational Voltage
Auxiliary Circuit 690 V | Main Circuit 690 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 Hz | Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 35 A | acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 30 A | (690 V) 60 °C 30 A | (690 V) 70 °C 26 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 18 A | (440 V) 60 °C 18 A | (500 V) 60 °C 15 A | (690 V) 60 °C 10.5 A | (380 / 400 V) 60 °C 18 A | (220 / 230 / 240 V) 60 °C 18 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 18 A | (440 V) 60 °C 18 A | (500 V) 60 °C 15 A | (690 V) 60 °C 10.5 A | (380 / 400 V) 60 °C 18 A | (220 / 230 / 240 V) 60 °C 18 A
Rated Operational Current AC-15 (Ie)
(500 V) 2 A | (690 V) 2 A | (24 / 127 V) 6 A | (220 / 240 V) 4 A | (400 / 440 V) 3 A
Rated Operational Current DC-1 (Ie)
(110 V) 1-Pole, 40 °C 20 A | (110 V) 1-Pole, 60 °C 20 A | (110 V) 1-Pole, 70 °C 20 A | (110 V) 2 Poles in Series, 40 °C 30 A | (110 V) 2 Poles in Series, 60 °C 30 A | (110 V) 2 Poles in Series, 70 °C 26 A | (110 V) 3 Poles in Series, 40 °C 30 A | (110 V) 3 Poles in Series, 60 °C 30 A | (110 V) 3 Poles in Series, 70 °C 26 A | (220 V) 2 Poles in Series, 40 °C 20 A | (220 V) 2 Poles in Series, 60 °C 20 A | (220 V) 2 Poles in Series, 70 °C 20 A | (220 V) 3 Poles in Series, 40 °C 30 A | (220 V) 3 Poles in Series, 60 °C 30 A | (220 V) 3 Poles in Series, 70 °C 26 A | (72 V) 1-Pole, 40 °C 30 A | (72 V) 1-Pole, 60 °C 30 A | (72 V) 1-Pole, 70 °C 26 A | (72 V) 2 Poles in Series, 40 °C 30 A | (72 V) 2 Poles in Series, 60 °C 30 A | (72 V) 2 Poles in Series, 70 °C 26 A | (72 V) 3 Poles in Series, 40 °C 30 A | (72 V) 3 Poles in Series, 60 °C 30 A | (72 V) 3 Poles in Series, 70 °C 26 A
Rated Operational Current DC-3 (Ie)
(110 V) 1-Pole, 40 °C 8 A | (110 V) 1-Pole, 60 °C 8 A | (110 V) 1-Pole, 70 °C 8 A | (110 V) 2 Poles in Series, 40 °C 30 A | (110 V) 2 Poles in Series, 60 °C 30 A | (110 V) 2 Poles in Series, 70 °C 26 A | (110 V) 3 Poles in Series, 40 °C 30 A | (110 V) 3 Poles in Series, 60 °C 30 A | (110 V) 3 Poles in Series, 70 °C 26 A | (220 V) 2 Poles in Series, 40 °C 8 A | (220 V) 2 Poles in Series, 60 °C 8 A | (220 V) 2 Poles in Series, 70 °C 8 A | (220 V) 3 Poles in Series, 40 °C 30 A | (220 V) 3 Poles in Series, 60 °C 30 A | (220 V) 3 Poles in Series, 70 °C 26 A | (72 V) 1-Pole, 40 °C 30 A | (72 V) 1-Pole, 60 °C 30 A | (72 V) 1-Pole, 70 °C 26 A | (72 V) 2 Poles in Series, 40 °C 30 A | (72 V) 2 Poles in Series, 60 °C 30 A | (72 V) 2 Poles in Series, 70 °C 26 A | (72 V) 3 Poles in Series, 40 °C 30 A | (72 V) 3 Poles in Series, 60 °C 30 A | (72 V) 3 Poles in Series, 70 °C 26 A
Rated Operational Current DC-5 (Ie)
(110 V) 1-Pole, 40 °C 4 A | (110 V) 1-Pole, 60 °C 4 A | (110 V) 1-Pole, 70 °C 4 A | (110 V) 2 Poles in Series, 40 °C 20 A | (110 V) 2 Poles in Series, 60 °C 20 A | (110 V) 2 Poles in Series, 70 °C 20 A | (110 V) 3 Poles in Series, 40 °C 30 A | (110 V) 3 Poles in Series, 60 °C 30 A | (110 V) 3 Poles in Series, 70 °C 26 A | (220 V) 2 Poles in Series, 40 °C 4 A | (220 V) 2 Poles in Series, 60 °C 4 A | (220 V) 2 Poles in Series, 70 °C 4 A | (220 V) 3 Poles in Series, 40 °C 16 A | (220 V) 3 Poles in Series, 60 °C 16 A | (220 V) 3 Poles in Series, 70 °C 16 A | (72 V) 1-Pole, 40 °C 16 A | (72 V) 1-Pole, 60 °C 16 A | (72 V) 1-Pole, 70 °C 16 A | (72 V) 2 Poles in Series, 40 °C 30 A | (72 V) 2 Poles in Series, 60 °C 30 A | (72 V) 2 Poles in Series, 70 °C 26 A | (72 V) 3 Poles in Series, 40 °C 30 A | (72 V) 3 Poles in Series, 60 °C 30 A | (72 V) 3 Poles in Series, 70 °C 26 A
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W | (48 V) 2.8 A / 134 W | (72 V) 1 A / 72 W | (110 V) 0.55 A / 60 W | (125 V) 0.55 A / 69 W | (220 V) 0.27 A / 60 W | (250 V) 0.27 A / 68 W | (400 V) 0.15 A / 60 W | (500 V) 0.13 A / 65 W | (600 V) 0.1 A / 60 W
Rated Operational Power AC-3 (Pe)
(415 V) 9 kW | (440 V) 9 kW | (500 V) 9 kW | (690 V) 9 kW | (380 / 400 V) 7.5 kW | (220 / 230 / 240 V) 4 kW
Rated Operational Power AC-3e (Pe)
(415 V) 9 kW | (440 V) 9 kW | (500 V) 9 kW | (690 V) 9 kW | (380 / 400 V) 7.5 kW | (220 / 230 / 240 V) 4 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A | for 0.1 s 140 A | for 1 s 100 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 V | acc. to IEC 60947-5-1 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-15) 1200 cycles per hour | (AC-2 / AC-4) 300 cycles per hour | (AC-3) 1200 cycles per hour | (DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 48 ... 130 V | 60 Hz 48 ... 130 V | DC Operation 48 ... 130 V
Power Loss
at 6 A per Pole 0.1 W | at Rated Operating Conditions AC-1 per Pole 1.2 W | at Rated Operating Conditions AC-3 per Pole 0.35 W
Operate Time
Between Coil De-energization and NC Contact Closing 13 ... 98 ms | Between Coil De-energization and NO Contact Opening 11 ... 95 ms | Between Coil Energization and NC Contact Opening 38 ... 90 ms | Between Coil Energization and NO Contact Closing 40 ... 95 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 screws placed diagonally
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP10 | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP10 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Tightening Torque
Auxiliary Circuit 1.2 N·m | Control Circuit 1.2 N·m | Main Circuit 1.5 N·m
Terminal Type
Ring-Tongue Terminals
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 30 A
Horsepower Rating UL/CSA
(120 V AC) Single Phase 1-1/2 hp | (200 ... 208 V AC) Three Phase 5 hp | (220 ... 240 V AC) Three Phase 5 hp | (240 V AC) Single Phase 3 hp | (440 ... 480 V AC) Three Phase 10 hp | (550 ... 600 V AC) Three Phase 15 hp
Tightening Torque UL/CSA
Auxiliary Circuit 11 in·lb | Control Circuit 11 in·lb | Main Circuit 13 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 20 A | (200 ... 208 V AC) Three Phase 17.5 A | (220 ... 240 V AC) Three Phase 15.2 A | (240 V AC) Single Phase 17 A | (440 ... 480 V AC) Three Phase 14 A | (550 ... 600 V AC) Three Phase 17 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -25 ... 60 °C | Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Shock and Vibration Withstand acc. to IEC 61373
Category 1, Class B
Pollution Degree
3
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
92411333-dba7-49ef-96c7-fa2a04772928 China (CN)
Simplified SCIP
e9f3871c-f32d-4baf-86b8-1489dd1049d9 Bulgaria (BG) | 2b5132a1-cad5-40ec-8974-2212f3d0a50c Sweden (SE) | e8fbf37f-1595-438c-be3a-557912d7a845 France (FR) | 3cc983bc-b202-4d13-87ca-9db3106a0f6f Germany (DE) | 488d78f8-9b88-4d82-9e0a-6b8e775a8193 Belgium (BE) | 2a8aa221-51c1-4934-beeb-558c17183893 Hungary (HU) | 7f735427-9af6-4a21-88ee-6d72072b6c0f Poland (PL) | 7f514536-d8ad-4388-80ca-37f3fb83f1fa Portugal (PT) | 6db9ba84-c305-413a-98f4-1ca587b86de8 Germany (DE) | 5e142dcc-da0a-421d-bb02-7056f5799ebc Poland (PL) | 0bb9dc4f-7fed-4f9f-bcf8-86cbe221c88e Spain (ES) | edab220f-75cb-4508-8c5a-c5cb38c2b3c8 Czech Republic (CZ) | f313a989-7296-406d-95d5-5285c0f9e596 Norway (NO) | 7005ccb5-7c5e-42d9-815a-d32b70bd16b3 Belgium (BE) | e39ebf6c-c56f-4acf-86a0-4baafb55cc6c Finland (FI) | f09ce63b-63c4-45cd-b5eb-cc27b0e1ebd2 Hungary (HU) | 56f85509-0f7b-43f4-8a9e-b930ef6f1387 Croatia (HR) | 2055ffbb-e341-4d24-9e1e-ef72d64effaf Germany (DE) | 192f477f-1c4f-44ae-8ce1-569d51784d3f Germany (DE) | 932a38c2-d09d-4e56-97a5-3993966128df Denmark (DK) | 30f62348-1be5-481f-af78-7829f52f8455 Poland (PL) | e47f5e98-ad8d-4cdf-9982-ac963d05c809 Estonia (EE) | 697953f9-6b28-480d-83ca-6b5254ca4532 Greece (GR) | 70de6926-7cb7-4ee3-835a-e68698aa6de7 Netherlands (NL) | 47926135-f5b0-4e42-b4f0-6e361316b28b Germany (DE) | da1978ab-011a-4cf5-b124-237a69f8b002 Sweden (SE) | 2dc22fca-5725-49a0-8085-397dd6893671 France (FR)
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
End Of Life Disassembling Instructions
End of life instruction AF(S)09/12/16/26/30/38(Z)(B)(K)(RT) Contactors & NF(Z)(B)(K)(RT) Contactors relays
Environmental Product Declaration - EPD
Environmental Product Declaration - AF09/12/16(Z)(B) Contactors and NF(Z) Contactor relaysAF(S)09/12/16(Z)(B) Contactors and NF(Z)(B) Contactors Relays (FR) | Environmental Product Declaration - AF09/12/16(Z)(B) Contactors and NF(Z) Contactor relays
Sustainable Material Content in Packaging (wt. %)
Recycled Cardboard - 86 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 28 %
CB Certificate
CB Certificate AF09, AF12, AF16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
CCC Certificate
CCC Certificate AF09, AF12, AF16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
CQC Certificate
CQC Certificate AF(C)09, AF(C)12, AF(C)16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
Declaration of Conformity - CCC
CCC Declaration of Conformity, Contactor, AF*09, AF*12, AF*16, Made in France
Declaration of Conformity - CE
EU Declaration of Conformity AF09 to AF38(Z)B..RT 3 and 4-pole contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09 to AF38(Z)B..RT 3 and 4-pole contactors
UL Listing Card
UL_E312527
UR Certificate
UR Certificate of Compliance AF09...AF38(Z)B..RT 3-pole contactors with ring tongue terminals
Package Level 1 Units
box 1 piece
Package Level 1 Width
87 mm
Package Level 1 Depth / Length
79 mm
Package Level 1 Height
47 mm
Package Level 1 Gross Weight
0.32 kg
Package Level 1 EAN
3471523128323
Package Level 2 Units
box 27 piece
Package Level 2 Width
250 mm
Package Level 2 Depth / Length
300 mm
Package Level 2 Height
315 mm
Package Level 2 Gross Weight
17.28 kg
Package Level 3 Units
1296 piece
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
Feature: AF technology provides a wide control voltage range (48-130 VAC/60 Hz and DC), reducing panel energy consumption and ensuring stable operation in networks with voltage fluctuations. Business Impact: Lower energy use and fewer false trips translate to reduced operating costs and improved line availability. Application: Main and auxiliary control in machine tools and material handling systems. Feature: Built-in surge protection protects the coil and related control circuitry, extending device life and reducing maintenance requirements. Business Impact: Fewer coil failures and less downtime for repair work. Application: Harsh factory environments with transient power events. Feature: Three main contacts plus one auxiliary NC contact (3P, 1 NC auxiliary) simplifies wiring and status signaling. Business Impact: Streamlined installation and clearer motor-control diagnostics, enabling faster maintenance. Application: Starter circuits for pumps and fans. Feature: Compact block design with DIN rail mounting (TH35) and compatibility with add-on auxiliary contact blocks. Business Impact: Saves panel space and enables scalable control architectures without redesigns. Application: OEM panels and retrofits in automation lines. Feature: Rated for 690 V main circuit and 415–690 V AC-3 power applications with 30 A AC-1 / electrical ratings; supports CE/UL/CSA compliance. Business Impact: Broad compatibility across regional standards reduces sourcing complexity and procurement risk. Application: Rolling stock motor controls and general-purpose industrial drives.

Get a Quick Quote for a ABB 1SBL176060R2201

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SBL176060R2201? Enquire Now

FAQs

Yes. The unit is designed for DIN rail mounting on TH35-15 or TH35-7.5 rails, and it supports easy expansion with add-on auxiliary contact blocks, enabling flexible control schemes without reconfiguring the panel wiring.
The contactor handles AC-3 applications up to 690 V with rated currents around 10.5 A (AC-3) at higher voltages, and AC-1 ratings of 30 A at 690 V (varies by temperature). This makes it suitable for motor start/stop and general purpose switching in industrial drives.
The control coil accepts 48–130 V AC or DC, accommodating voltage variations in unstable networks, which reduces nuisance trips, improves reliability, and lowers energy waste in panel power supplies and control circuits.
Yes. Built-in surge protection helps shield the coil and control circuitry from voltage spikes, reducing maintenance needs and increasing uptime in industrial applications with fluctuating power.
The product aligns with IEC/EN 60947-4-1, UL 60947-4-1, CSA standards, and CE/UKCA declarations, with RoHS, REACH, and other environmental compliance statements for global deployment in regulated markets.