ABB AF16ZB-40-00RT-23 Contactor - IEC/UL 60947-4-1

Part Number: 1SBL176260R2300
Manufacturer
ABB
Part number
1SBL176260R2300

Quick Summary

ABB AF16ZB-40-00RT-23 Contactor is a four-pole device designed to control motors up to 9 kW at 690 V in industrial automation. In panel builds, variable control voltages and fluctuating networks can cause unreliable operations; this contactor’s AF technology supports a wide control voltage range of 100–250 V AC/60 Hz and DC, reducing wiring complexity and energy waste. It meets key standards such as IEC/EN 60947-1, IEC 60947-4-1, UL 60947-4-1, and CSA C22.2, with EN 50155 applicability for rolling stock where required. For OEMs and service teams, the block design invites easy expansion with auxiliary contact blocks while maintaining a compact footprint for lean panels and lower total installed cost. The result is dependable performance with predictable coil power loss across varying operating conditions.

Product Information

Extended Description

1SBL176260R2300 ABB: The AF16ZB-40-00RT-23 is a 4 pole - 690 V IEC or 600 UL contactor with Ring-Tongue Terminals, controlling motors up to 7.5 kW / 400 V AC (AC-3) and switching power circuits up to 30 A (AC-1) or 30 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
Motor control and protection for Rolling stock application_PDF
Instructions and Manuals
Installation instructions AF09...38(Z)B-..RT Contactors, NF(Z)B..ERT Contactor relays and CA4..RT, CAL4..RT, CAT4..RT, LDC4RT Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
45 mm
Product Net Depth / Length
77 mm
Product Net Height
86 mm
Product Net Weight
0.32 kg
Number of Main Contacts NO
4
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Number of Poles
4P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives.
Rated Operational Voltage
Main Circuit 690 V
Rated Frequency (f)
Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 35 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 30 A | (690 V) 60 °C 30 A | (690 V) 70 °C 26 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 18 A | (440 V) 60 °C 18 A | (500 V) 60 °C 15 A | (690 V) 60 °C 10.5 A | (380 / 400 V) 60 °C 18 A | (220 / 230 / 240 V) 60 °C 18 A
Rated Operational Current DC-1 (Ie)
(110 V) 1-Pole, 40 °C 20 A | (110 V) 1-Pole, 60 °C 20 A | (110 V) 1-Pole, 70 °C 20 A | (110 V) 2 Poles in Series, 40 °C 30 A | (110 V) 2 Poles in Series, 60 °C 30 A | (110 V) 2 Poles in Series, 70 °C 26 A | (110 V) 3 Poles in Series, 40 °C 30 A | (110 V) 3 Poles in Series, 60 °C 30 A | (110 V) 3 Poles in Series, 70 °C 26 A | (110 V) 4 Poles in Series, 40 °C 30 A | (110 V) 4 Poles in Series, 60 °C 30 A | (110 V) 4 Poles in Series, 70 °C 26 A | (220 V) 2 Poles in Series, 40 °C 20 A | (220 V) 2 Poles in Series, 60 °C 20 A | (220 V) 2 Poles in Series, 70 °C 20 A | (220 V) 3 Poles in Series, 40 °C 30 A | (220 V) 3 Poles in Series, 60 °C 30 A | (220 V) 3 Poles in Series, 70 °C 26 A | (220 V) 4 Poles in Series, 40 °C 30 A | (220 V) 4 Poles in Series, 60 °C 30 A | (220 V) 4 Poles in Series, 70 °C 26 A | (440 V) 4 Poles in Series, 40 °C 20 A | (440 V) 4 Poles in Series, 60 °C 20 A | (440 V) 4 Poles in Series, 70 °C 20 A | (72 V) 1-Pole, 40 °C 30 A | (72 V) 1-Pole, 60 °C 30 A | (72 V) 1-Pole, 70 °C 26 A | (72 V) 2 Poles in Series, 40 °C 30 A | (72 V) 2 Poles in Series, 60 °C 30 A | (72 V) 2 Poles in Series, 70 °C 26 A | (72 V) 3 Poles in Series, 40 °C 30 A | (72 V) 3 Poles in Series, 60 °C 30 A | (72 V) 3 Poles in Series, 70 °C 26 A | (72 V) 4 Poles in Series, 40 °C 30 A | (72 V) 4 Poles in Series, 60 °C 30 A | (72 V) 4 Poles in Series, 70 °C 26 A
Rated Operational Current DC-3 (Ie)
(110 V) 1-Pole, 40 °C 8 A | (110 V) 1-Pole, 60 °C 8 A | (110 V) 1-Pole, 70 °C 8 A | (110 V) 2 Poles in Series, 40 °C 30 A | (110 V) 2 Poles in Series, 60 °C 30 A | (110 V) 2 Poles in Series, 70 °C 26 A | (110 V) 3 Poles in Series, 40 °C 30 A | (110 V) 3 Poles in Series, 60 °C 30 A | (110 V) 3 Poles in Series, 70 °C 26 A | (110 V) 4 Poles in Series, 40 °C 30 A | (110 V) 4 Poles in Series, 60 °C 30 A | (110 V) 4 Poles in Series, 70 °C 26 A | (220 V) 2 Poles in Series, 40 °C 8 A | (220 V) 2 Poles in Series, 60 °C 8 A | (220 V) 2 Poles in Series, 70 °C 8 A | (220 V) 3 Poles in Series, 40 °C 30 A | (220 V) 3 Poles in Series, 60 °C 30 A | (220 V) 3 Poles in Series, 70 °C 26 A | (220 V) 4 Poles in Series, 40 °C 30 A | (220 V) 4 Poles in Series, 60 °C 30 A | (220 V) 4 Poles in Series, 70 °C 26 A | (440 V) 4 Poles in Series, 40 °C 8 A | (440 V) 4 Poles in Series, 60 °C 8 A | (440 V) 4 Poles in Series, 70 °C 8 A | (72 V) 1-Pole, 40 °C 30 A | (72 V) 1-Pole, 60 °C 30 A | (72 V) 1-Pole, 70 °C 26 A | (72 V) 2 Poles in Series, 40 °C 30 A | (72 V) 2 Poles in Series, 60 °C 30 A | (72 V) 2 Poles in Series, 70 °C 26 A | (72 V) 3 Poles in Series, 40 °C 30 A | (72 V) 3 Poles in Series, 60 °C 30 A | (72 V) 3 Poles in Series, 70 °C 26 A | (72 V) 4 Poles in Series, 40 °C 30 A | (72 V) 4 Poles in Series, 60 °C 30 A | (72 V) 4 Poles in Series, 70 °C 26 A
Rated Operational Current DC-5 (Ie)
(110 V) 1-Pole, 40 °C 4 A | (110 V) 1-Pole, 60 °C 4 A | (110 V) 1-Pole, 70 °C 4 A | (110 V) 2 Poles in Series, 40 °C 20 A | (110 V) 2 Poles in Series, 60 °C 20 A | (110 V) 2 Poles in Series, 70 °C 20 A | (110 V) 3 Poles in Series, 40 °C 30 A | (110 V) 3 Poles in Series, 60 °C 30 A | (110 V) 3 Poles in Series, 70 °C 26 A | (110 V) 4 Poles in Series, 40 °C 30 A | (110 V) 4 Poles in Series, 60 °C 30 A | (110 V) 4 Poles in Series, 70 °C 26 A | (220 V) 2 Poles in Series, 40 °C 4 A | (220 V) 2 Poles in Series, 60 °C 4 A | (220 V) 2 Poles in Series, 70 °C 4 A | (220 V) 3 Poles in Series, 40 °C 16 A | (220 V) 3 Poles in Series, 60 °C 16 A | (220 V) 3 Poles in Series, 70 °C 16 A | (220 V) 4 Poles in Series, 40 °C 20 A | (220 V) 4 Poles in Series, 60 °C 20 A | (220 V) 4 Poles in Series, 70 °C 20 A | (440 V) 4 Poles in Series, 40 °C 4 A | (440 V) 4 Poles in Series, 60 °C 4 A | (440 V) 4 Poles in Series, 70 °C 4 A | (72 V) 1-Pole, 40 °C 16 A | (72 V) 1-Pole, 60 °C 16 A | (72 V) 1-Pole, 70 °C 16 A | (72 V) 2 Poles in Series, 40 °C 30 A | (72 V) 2 Poles in Series, 60 °C 30 A | (72 V) 2 Poles in Series, 70 °C 26 A | (72 V) 3 Poles in Series, 40 °C 30 A | (72 V) 3 Poles in Series, 60 °C 30 A | (72 V) 3 Poles in Series, 70 °C 26 A | (72 V) 4 Poles in Series, 40 °C 30 A | (72 V) 4 Poles in Series, 60 °C 30 A | (72 V) 4 Poles in Series, 70 °C 26 A
Rated Operational Power AC-3 (Pe)
(400 V) 7.5 kW | (415 V) 9 kW | (440 V) 9 kW | (500 V) 9 kW | (690 V) 9 kW | (380 / 400 V) 7.5 kW | (220 / 230 / 240 V) 4 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 100 ... 250 V | 60 Hz 100 ... 250 V | DC Operation 100 ... 250 V
Power Loss
at Rated Operating Conditions AC-1 per Pole 1.2 W | at Rated Operating Conditions AC-3 per Pole 0.35 W
Operate Time
Between Coil De-energization and NC Contact Closing 13 ... 98 ms | Between Coil De-energization and NO Contact Opening 11 ... 95 ms | Between Coil Energization and NC Contact Opening 38 ... 90 ms | Between Coil Energization and NO Contact Closing 40 ... 95 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 screws placed diagonally
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP10 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Tightening Torque
Control Circuit 1.2 N·m | Main Circuit 1.5 N·m
Terminal Type
Ring-Tongue Terminals
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 30 A
Tightening Torque UL/CSA
Control Circuit 11 in·lb | Main Circuit 13 in·lb
Ambient Air Temperature
Close to Contactor for Storage -60 ... +80 °C | Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Shock and Vibration Withstand acc. to IEC 61373
Category 1, Class B
Pollution Degree
3
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
End Of Life Disassembling Instructions
End of life instruction AF(S)09/12/16/26/30/38(Z)(B)(K)(RT) Contactors & NF(Z)(B)(K)(RT) Contactors relays
Environmental Product Declaration - EPD
Environmental Product Declaration - AF09/12/16(Z)(B) Contactors and NF(Z) Contactor relaysAF(S)09/12/16(Z)(B) Contactors and NF(Z)(B) Contactors Relays (FR) | Environmental Product Declaration - AF09/12/16(Z)(B) Contactors and NF(Z) Contactor relays
Sustainable Material Content in Packaging (wt. %)
Recycled Cardboard - 86 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 28 %
CB Certificate
CB Certificate AF09, AF12, AF16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
CCC Certificate
CCC Certificate AF09, AF12, AF16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
CQC Certificate
CQC Certificate AF(C)09, AF(C)12, AF(C)16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
Declaration of Conformity - CCC
CCC Declaration of Conformity, Contactor, AF*09, AF*12, AF*16, Made in France
Declaration of Conformity - CE
EU Declaration of Conformity AF09 to AF38(Z)B..RT 3 and 4-pole contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09 to AF38(Z)B..RT 3 and 4-pole contactors
UL Listing Card
UL_E319322
UR Certificate
UR Certificate of Compliance AF09...AF38(Z)B-..RT 4-pole contactors with ring tongue terminals
Package Level 1 Units
box 1 piece
Package Level 1 Width
87 mm
Package Level 1 Depth / Length
79 mm
Package Level 1 Height
47 mm
Package Level 1 Gross Weight
0.32 kg
Package Level 1 EAN
3471523129535
Package Level 2 Units
box 27 piece
Package Level 2 Width
250 mm
Package Level 2 Depth / Length
300 mm
Package Level 2 Height
315 mm
Package Level 2 Gross Weight
17.28 kg
Package Level 3 Units
1296 piece
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
Feature AF technology with a wide control voltage range of 100–250 V AC/60 Hz or DC provides consistent operation across fluctuating networks, reducing panel energy consumption and wiring variance. Business Impact Reduced energy waste and simplified control wiring translate to lower operating costs and faster commissioning in new builds. Application Suitable for motor control tasks in conveyors, pumps, and fans where stable actuation is critical. Feature Built-in surge protection protects contacts and downstream electronics from voltage spikes, reducing maintenance intervals and unplanned downtime. Business Impact Extended component life and lower service costs. Application Particularly beneficial in industrial environments with inconsistent input voltages or noisy electrical infrastructure. Feature 4-pole main circuit rated to 690 V with 7.5 kW (AC-3) / 9 kW (peak) capability across listed voltages, rated AC-1 current up to 30 A and AC-3 up to 18 A in many conditions. Business Impact Enables reliable motor starting and switching of common loads while supporting safety margins and predictable thermal performance. Application Suitable for general purpose industrial drives and rolling stock where applicable. Feature Ring-Tongue terminals and compact 45 mm width enable quick, secure wiring and easy diagnostics. Business Impact Reduces installation time and improves field reliability. Application Ideal for panel builders requiring clean, repeatable terminations in tight spaces. Feature Block-type design supports add-on auxiliary contact blocks for scalable control architectures. Business Impact Facilitates modular upgrades and extended control options without replacing the entire device. Application Useful in systems where future expansion or redundancy is planned. Feature DIN rail mounting options TH35-15 or TH35-7.5 and 2 x M4 mounting screws simplify installation and compatibility with standard enclosures. Business Impact Streamlines OEM assembly and field retrofits, lowering installation risk and time. Application Common in control panels and machine interfaces. Feature Low power loss: 1.2 W per pole at AC-1 and 0.35 W per pole at AC-3, contributing to lower heat generation and energy use. Business Impact Improves panel efficiency and supports higher reliability with cooler operation. Application Beneficial in densely populated control cabinets and energy-conscious designs. Feature Compliance with RoHS, REACH, TSCA and multiple international certificates ensures broad market compatibility and regulatory readiness. Business Impact Reduces compliance risk and accelerates global deployment. Application Essential for multinational machinery and supply chains that require standard conformity. Feature IP10-rated coil and main terminals with robust environmental specs, supporting operation in typical industrial environments. Business Impact Ensures durability and reliability in harsh conditions. Application Relevant for manufacturing floors and outdoor or semi-outdoor installations.

Get a Quick Quote for a ABB 1SBL176260R2300

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SBL176260R2300? Enquire Now

FAQs

Install on TH35-15 or TH35-7.5 DIN rails; secure with two M4 screws diagonally; wire using Ring-Tongue terminals for main and control circuits; tighten coils to the specified torque: 1.2 N·m for control, 1.5 N·m for main; ensure IP10 protection is maintained for terminals.
For AC-1 operation at 690 V, the device supports up to 30 A (40 °C), with lower values at higher temperatures. For AC-3 operation, it handles up to 18 A at 690 V (60 °C) and related ratings across listed voltages, enabling reliable motor starting and switching for typical industrial motors.
Yes, it complies with IEC and UL standards and includes EN 50155 applicability for rolling stock where required. It’s also compatible with conveyors, pumps, and fans in industrial environments, offering robust performance with wide control voltage compatibility and surge protection.
The device carries CE/UKCA, UL/CSA certifications, CCC and CQC certificates, CB and UR declarations, and RoHS, REACH, TSCA compliance, along with WEEE classification for B2B use. These certifications support global deployment and regulatory conformity in diverse markets.
AF technology provides a wide control voltage range, reducing panel rewiring and energy waste. Built-in surge protection lowers downstream failure risk, while modular add-on contacts support future expansion, improving long-term ROI through easier upgrades and lower maintenance costs.