ABB 1SBL176501R3000 Block Contactor - AF technology

Part Number: 1SBL176501R3000
Manufacturer
ABB
Part number
1SBL176501R3000

Quick Summary

ABB 1SBL176501R3000 Block Contactor with AF technology provides reliable 4-pole motor control for 690 V AC drives. Engineers often battle panel energy waste and complex PLC interfaces, but this device reduces both with a 24 V DC coil and direct PLC drive. It complies with IEC/EN 60947-1, IEC/EN 60947-4-1 and UL 60335-2-40, supporting global safety and performance requirements. The compact block design with screw terminals and DIN rail mounting streamlines installation across machines, conveyors, and pumps. A broad accessory ecosystem and add-on contact blocks enable scalable control architectures for evolving automation needs.

Product Information

Extended Description

1SBL176501R3000 ABB: The AF16Z-22-00-30 is a 4-pole - 690 V IEC or 600 UL contactor with screw terminals, controlling motors up to 7.5 kW / 400 V AC (AC-3) and switching power circuits up to 30 A (AC-1) or 30 A UL general use. Thanks to the AF technology, the contactor has a 24 V DC coil, featuring a reduced holding coil consumption down to 1.7 W and offering the possibility of a direct control by PLC-output ≥ 250 mA 24 V DC, without need of additional interface relay, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Data Sheet, Technical Information
1SBC100214C0202 - Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) - Edition 2024
Instructions and Manuals
Installation instructions AF09...38Z-..-..-30 Contactors, NFZ..E-30 Contactor relays and CA4, CAL4, CC4, LDC4 Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
45 mm
Product Net Depth / Length
97 mm
Product Net Height
86 mm
Product Net Weight
0.43 kg
Number of Main Contacts NO
2
Number of Main Contacts NC
2
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Number of Poles
4P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CAN/CSA C22.2 No.60947-1, CAN/CSA C22.2 No.60947-4-1
Rated Operational Voltage
Main Circuit 690 V
Rated Frequency (f)
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 35 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 30 A | (690 V) 60 °C 30 A | (690 V) 70 °C 26 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 18 A | (440 V) 60 °C 18 A | (500 V) 60 °C 15 A | (690 V) 60 °C 10.5 A | (380 / 400 V) 60 °C 18 A | (220 / 230 / 240 V) 60 °C 18 A
Rated Operational Power AC-3 (Pe)
(415 V) 9 kW | (440 V) 9 kW | (500 V) 9 kW | (690 V) 9 kW | (380 / 400 V) 7.5 kW | (220 / 230 / 240 V) 4 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
DC Operation 24 V
Power Loss
at Rated Operating Conditions AC-1 per Pole 1.2 W | at Rated Operating Conditions AC-3 per Pole 0.35 W
Operate Time
Between Coil De-energization and NC Contact Closing 22 ... 57 ms | Between Coil De-energization and NO Contact Opening 17 ... 29 ms | Between Coil Energization and NC Contact Opening 20 ... 35 ms | Between Coil Energization and NO Contact Closing 27 ... 53 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 0.75 ... 6 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 4 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² | Rigid Solid 1/2x 1 ... 4 mm² | Rigid Stranded 1/2x 1 ... 6 mm²
Connecting Capacity Auxiliary Circuit
Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Control Circuit 10 mm | Main Circuit 10 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Tightening Torque
Control Circuit 1.2 N·m | Main Circuit 1.5 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 30 A
Connecting Capacity Main Circuit UL/CSA
Rigid Solid 1/2x 16-10 AWG | Rigid Stranded 1/2x 16-10 AWG
Connecting Capacity Auxiliary Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG | Rigid Stranded 1/2x 18-14 AWG
Connecting Capacity Control Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG | Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSA
Control Circuit 11 in·lb | Main Circuit 13 in·lb
Ambient Air Temperature
Close to Contactor for Storage -60 ... +80 °C | Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Resistance to Vibrations
4g Closed Position & 2g Open position 5 ... 300 Hz
Pollution Degree
3
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
End Of Life Disassembling Instructions
End of life instruction AF(S)09/12/16/26/30/38(Z)(B)(K)(RT) Contactors & NF(Z)(B)(K)(RT) Contactors relays
Environmental Product Declaration - EPD
Environmental Product Declaration - AF09/12/16(Z)(B) Contactors and NF(Z) Contactor relaysAF(S)09/12/16(Z)(B) Contactors and NF(Z)(B) Contactors Relays (FR)
Sustainable Material Content in Packaging (wt. %)
Recycled Cardboard - 86 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 28 %
A2L Certificate – UL
UL-US A2L LZGH2 Certificate of Compliance AF09 ... AF38 3-pole contactors with screw terminals - UL 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers | UL-CA A2L LZGH2 Certificate of Compliance AF09 ... AF38 3-pole contactors with screw terminals - CSA C22.2 No. 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers
ABS Certificate
ABS Certificate, AF(S)09 to AF(S)96 contactors, NF contactor relays and CA4, CC4, CAL4, CAT4 auxiliary contact blocks, TEF4 electronic timers
CB Certificate
CB Certificate AF09, AF12, AF16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
CCC Certificate
CCC Certificate AF09, AF12, AF16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
CQC Certificate
CQC Certificate AF(C)09, AF(C)12, AF(C)16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors | CQC Certificate, Contactor, AF09,AF12,AF16, Made in China
Declaration of Conformity - CCC
CCC Declaration of Conformity, Contactor, AF*09, AF*12, AF*16, Made in France | CCC Declaration of Conformity, Contactor, AF09,AF12,AF16, Made in China
Declaration of Conformity - CE
EU Declaration of Conformity AF09, AF16, AF26, AF38, AF40, AF52, AF80, 4-pole Contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09, AF16, AF26, AF38, AF40, AF52, AF80, 4-pole Contactors
DNV Certificate
DNV Certificate AF(S)09...96 3-pole & AF09...80 4-pole contactors with screw, spring, push-in terminals
RMRS Certificate
RMRS Certificate AF(S)09(S)...AF(S)38 3-pole and 4-pole, AF(S)40..96 3-pole contactors with screw, push-in and spring terminals
UL Certificate
UL-US Certificate of Compliance AF(C)09..(K) ... AF(C)38 4-pole contactors with screw and push-in spring terminals | UL-CA Certificate of Compliance AF(C)09..(K) ... AF(C)38 4-pole contactors with screw and push-in spring terminals
Package Level 1 Units
box 1 piece
Package Level 1 Width
96 mm
Package Level 1 Depth / Length
112 mm
Package Level 1 Height
50 mm
Package Level 1 Gross Weight
0.475 kg
Package Level 1 EAN
3471523116795
Package Level 2 Units
crate 12 piece
Package Level 2 Width
51 mm
Package Level 2 Depth / Length
98 mm
Package Level 2 Height
114 mm
Package Level 2 Gross Weight
5.7 kg
Package Level 3 Units
576 piece
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
E-Number (Finland)
3709066
Feature AF technology coil delivers a low 1.7 W hold power, reducing panel heat and energy use. Business Impact Lower energy consumption in control panels and fewer cooling requirements, improving overall machine efficiency. Application Ideal for PLC-controlled motor circuits in packaging lines and conveyors. Feature 4P main circuit rated up to 690 V supports motors up to 7.5 kW at 400 V AC (AC-3) and 30 A AC-1 at 690 V. Business Impact Enables compact, robust motor control with high short-term fault tolerance and broad voltage applicability. Application Suitable for mid-range conveyors, machine tools, and pumps in industrial settings. Feature Built-in surge protection reduces external suppression components and simplifies panel design. Business Impact Safer operation in networks susceptible to transients and voltage spikes, lowering maintenance costs. Application Critical in environments with variable power quality. Feature Screw terminals and mounting on TH35 DIN rails simplify installation. Business Impact Faster commissioning and easier retrofits with minimal wiring complexity. Application Common in machine upgrades and new line builds. Feature Compact footprint: 45 mm width, 97 mm depth, 86 mm height with a 0.43 kg weight. Business Impact Saves panel space and reduces installation weight, enabling denser control cabinets. Application Ideal for compact control enclosures in small to mid-size machines. Feature Comprehensive standards coverage (IEC/EN 60947-1, 60947-4-1, UL/CSA). Business Impact Facilitates global compliance and smoother cross-border deployments. Application Supports multi-region production lines. Feature Block-contactor design with add-on auxiliary contact blocks. Business Impact Scalable control architectures with easy expansion. Application Fits evolving automation layouts in manufacturing plants.

Get a Quick Quote for a ABB 1SBL176501R3000

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SBL176501R3000? Enquire Now

FAQs

Install on TH35-15 or TH35-7.5 DIN rails, using 2x M4 screws diagonally for mounting. Connect the main circuit conductors to screw terminals with a torque of 1.5 N·m and the control circuit at 1.2 N·m. Ensure IP20 protection and observe the 10 mm wire stripping length for both main and control circuits. The 24 V DC coil is designed for direct PLC drive.
Rated Operational Current AC-1 at 690 V is 30 A across 40–70 °C. For AC-3, the device supports up to 18 A at 415–690 V and up to 4 kW at 220–240 V. Maximum short-time withstand current and mechanical cycles are designed for demanding industrial duty, while the built-in surge protection supports transients typical in automation environments.
Yes. With 4P configuration and AC-3 ratings, the ABB 1SBL176501R3000 handles motors up to 7.5 kW (380–400 V) and 18 A at higher voltages, making it suitable for conveyors, pumps, and other motor-driven loads in common industrial applications. The 24 V DC coil also enables simple PLC integration for direct control without extra relays.
It aligns with IEC/EN 60947-1 and 60947-4-1, UL 60335-2-40, and support for CSA, UL/CSA certifications, with CE/UKCA DoCs available. RoHS and REACH declarations are included, along with WEEE considerations for B2B deployments. This ensures global compliance for machinery, process equipment, and cross-border installations.
AF technology reduces coil holding power to about 1.7 W, enabling direct PLC control without an interface relay. This lowers panel heat, reduces wiring and component counts, shortens commissioning time, and improves energy efficiency in continuous operation, contributing to a faster payback in automations with multiple contactors or frequent cycling.