ABB AF16ZB-22-00RT-22 Block Contactor - 690V
Part Number: 1SBL176560R2200
Quick Summary
AF16ZB-22-00RT-22 Block Contactor is a four-pole, 690 V motor control device designed for AC-3 switching of industrial motors up to 7.5 kW. This compact, robust unit supports large control voltage variations with a wide 48–130 V AC/60 Hz or DC input, helping reduce panel energy consumption and avoid coil misoperation in unstable networks. Built-in surge protection enhances reliability and safety, while the block design enables quick expansion with add-on auxiliary contact blocks. The product uses Ring-Tongue terminals and offers mounting on DIN rails TH35-15 or TH35-7.5 for flexible panel integration. Compliance spans IEC/EN 60947-4-1, UL 60947-4-1, and EN 50155, ensuring suitability for rolling stock and industrial applications. In practice, it supports cost-effective motor control with simplified maintenance.
Product Information
Extended Description
1SBL176560R2200 ABB: The AF16ZB-22-00RT-22 is a 4 pole - 690 V IEC or 600 UL contactor with Ring-Tongue Terminals, controlling motors up to 7.5 kW / 400 V AC (AC-3) and switching power circuits up to 30 A (AC-1) or 30 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (48-130 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
Motor control and protection for Rolling stock application_PDF
Instructions and Manuals
Installation instructions AF09...38(Z)B-..RT Contactors, NF(Z)B..ERT Contactor relays and CA4..RT, CAL4..RT, CAT4..RT, LDC4RT Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
45 mm
Product Net Depth / Length
77 mm
Product Net Height
86 mm
Product Net Weight
0.32 kg
Number of Main Contacts NO
2
Number of Main Contacts NC
2
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Number of Poles
4P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives.
Rated Operational Voltage
Main Circuit 690 V
Rated Frequency (f)
Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 35 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 30 A | (690 V) 60 °C 30 A | (690 V) 70 °C 26 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 18 A | (440 V) 60 °C 18 A | (500 V) 60 °C 15 A | (690 V) 60 °C 10.5 A | (380 / 400 V) 60 °C 18 A | (220 / 230 / 240 V) 60 °C 18 A
Rated Operational Power AC-3 (Pe)
(400 V) 7.5 kW | (415 V) 9 kW | (440 V) 9 kW | (500 V) 9 kW | (690 V) 9 kW | (380 / 400 V) 7.5 kW | (220 / 230 / 240 V) 4 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 48 ... 130 V | 60 Hz 48 ... 130 V | DC Operation 48 ... 130 V
Power Loss
at Rated Operating Conditions AC-1 per Pole 1.2 W | at Rated Operating Conditions AC-3 per Pole 0.35 W
Operate Time
Between Coil De-energization and NC Contact Closing 13 ... 98 ms | Between Coil De-energization and NO Contact Opening 11 ... 95 ms | Between Coil Energization and NC Contact Opening 38 ... 90 ms | Between Coil Energization and NO Contact Closing 40 ... 95 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 screws placed diagonally
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP10 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Tightening Torque
Control Circuit 1.2 N·m | Main Circuit 1.5 N·m
Terminal Type
Ring-Tongue Terminals
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 30 A
Tightening Torque UL/CSA
Control Circuit 11 in·lb | Main Circuit 13 in·lb
Ambient Air Temperature
Close to Contactor for Storage -60 ... +80 °C | Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Shock and Vibration Withstand acc. to IEC 61373
Category 1, Class B
Pollution Degree
3
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
25a807d6-0ff7-4793-9534-7a4d622b92c5 China (CN)
Simplified SCIP
e3a69b5b-6c75-41c3-bc19-4593d3830ef2 Poland (PL) | 1dcf073d-6d51-4413-a939-8ef0073dd2b7 France (FR) | c65c62b2-ffaf-4ec7-801e-1166527219a2 Sweden (SE) | 30ad78d2-4833-425a-acdb-3bfad0bc29cc Germany (DE) | b8832860-c83a-45b6-bf34-eabd72b7e39b Poland (PL) | ab048500-d8ea-4fa8-bd23-8e9ae99a7877 Sweden (SE) | f306acc2-fb05-4a6c-bc89-3743c10e90bb Bulgaria (BG) | 7b7304fb-8f2e-4819-871c-4ebadd6cf7a9 Portugal (PT) | e3f4f013-0702-48ca-b778-e7cddb9501b7 Germany (DE) | 0f5e2527-9a43-4dd3-8b53-5a0108289da7 France (FR) | 5f51afda-e632-4770-b7df-b808a5b4b00e Hungary (HU) | 3c707446-6cb9-4a7e-b9e3-7cc36c62417a Belgium (BE) | cca86f26-db97-494d-a20d-3df47f65ffa7 Netherlands (NL) | 08c78596-0f60-47d4-88a6-6832d0a14f86 Spain (ES) | 7b3cfaf1-b1c8-42f7-a756-f73bf778efc0 Germany (DE) | 6a8482af-7041-40b1-b20f-207b0a315eb9 Estonia (EE) | 37498a31-c89d-4c3d-bbd8-7ff4d0950f30 Greece (GR) | e2d5934a-2499-4758-9b6e-0de79d0f115a Belgium (BE) | be37af0e-af29-4732-8fe0-21cf171e4e3d Hungary (HU) | 2a7d14f2-9248-4a1a-b023-acc810846b94 Denmark (DK) | 41b38183-335a-41f8-9420-934a0993bf2d Germany (DE) | 2d070046-60f5-4960-832b-ad2cda5272a5 Germany (DE) | 0bbd7c5c-1df0-457d-8963-b11074fb1be0 Croatia (HR) | 66a047a7-a454-46c5-b0b4-304b4241fa6c Finland (FI) | 9c9f0fd5-eb34-46b4-90dd-83f8b0e117fd Norway (NO) | 86d0e0ba-907c-42f6-b653-67dd3c7a58c5 Poland (PL) | 618afc7c-5366-447c-aad8-d82ecae218c9 Czech Republic (CZ)
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
End Of Life Disassembling Instructions
End of life instruction AF(S)09/12/16/26/30/38(Z)(B)(K)(RT) Contactors & NF(Z)(B)(K)(RT) Contactors relays
Environmental Product Declaration - EPD
Environmental Product Declaration - AF09/12/16(Z)(B) Contactors and NF(Z) Contactor relaysAF(S)09/12/16(Z)(B) Contactors and NF(Z)(B) Contactors Relays (FR) | Environmental Product Declaration - AF09/12/16(Z)(B) Contactors and NF(Z) Contactor relays
Sustainable Material Content in Packaging (wt. %)
Recycled Cardboard - 86 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 28 %
CB Certificate
CB Certificate AF09, AF12, AF16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
CCC Certificate
CCC Certificate AF09, AF12, AF16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
CQC Certificate
CQC Certificate AF(C)09, AF(C)12, AF(C)16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
Declaration of Conformity - CCC
CCC Declaration of Conformity, Contactor, AF*09, AF*12, AF*16, Made in France
Declaration of Conformity - CE
EU Declaration of Conformity AF09 to AF38(Z)B..RT 3 and 4-pole contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09 to AF38(Z)B..RT 3 and 4-pole contactors
UL Listing Card
UL_E319322
UR Certificate
UR Certificate of Compliance AF09...AF38(Z)B-..RT 4-pole contactors with ring tongue terminals
Package Level 1 Units
box 1 piece
Package Level 1 Width
87 mm
Package Level 1 Depth / Length
79 mm
Package Level 1 Height
47 mm
Package Level 1 Gross Weight
0.32 kg
Package Level 1 EAN
3471523129825
Package Level 2 Units
box 27 piece
Package Level 2 Width
250 mm
Package Level 2 Depth / Length
300 mm
Package Level 2 Height
315 mm
Package Level 2 Gross Weight
17.28 kg
Package Level 3 Units
1296 piece
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
Feature four-pole block design → Business Impact compact footprint and easier expansion with add-on auxiliary contact blocks to scale control circuits as the system grows → Application panel builders and OEMs requiring scalable motor control. Feature 690 V main circuit rating and 30 A AC-1 / 18 A AC-3 ratings → Business Impact supports reliable motor switching for up to 7.5 kW and higher efficiency in standard drives → Application conveyors, pumps, and fans in industrial environments. Feature wide coil voltage range 48–130 V AC/60 Hz or DC → Business Impact reduces inventory and stabilizes operation in networks with voltage fluctuations → Application rolling stock and manufacturing lines with variable supply. Feature built-in surge protection → Business Impact enhanced protection from transients, lower EMI, and longer coil and contact life → Application sites with high switching transients. Feature Ring-Tongue terminals and IP10 protection → Business Impact safer, faster wiring and maintenance in clean control cabinets → Application new installations and upgrades needing robust electrical connections. Feature DIN rail mounting TH35-15 / TH35-7.5 → Business Impact streamlined installation and retrofits in standard control panels → Application OEM panel assemblies and retrofit projects. Feature compatibility with add-on auxiliary contact blocks → Business Impact flexible control logic expansion without replacing the base contactor → Application scalable automation systems with minimal downtime.
Get a Quick Quote for a ABB 1SBL176560R2200
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SBL176560R2200?
Enquire Now
FAQs
The AF16ZB-22-00RT-22 is designed for DIN rail mounting on TH35-15 or TH35-7.5 rails. It also supports mounting with two M4 screws placed diagonally. For a clean, secure installation, use the ring-tongue terminals and follow standard panel wiring practices to ensure compliance with IP10 protection and proper wiring torque.
For AC-1 operation at 690 V, the device provides 30 A current handling (at 40–70 °C depending on ambient). For AC-3 operation, ratings vary by voltage: at 415 V, 60 °C it is 18 A; at 690 V, 60 °C it is 10.5 A. This translates to roughly 7.5 kW at 400 V (AC-3) and higher efficiency in suitable configurations.
Yes. The contactor is designed for rolling stock applications and meets relevant standards including EN 50155 for railway environments. It also adheres to IEC/EN 60947-1 and 60947-4-1, UL 60947-4-1, and CSA equivalents, with environmental specs suitable for variable temperatures, vibrations, and altitude up to 3000 meters.
ABB provides declarations and certificates such as CE, UKCA, CCC, CQC, UL listing (UL_E319322), UR, and CB certification for AF09–AF38 family. The AF16ZB-22-00RT-22 includes RoHS compliance, WEEE categorization, and supports EN 50155 rolling stock requirements, ensuring broad regulatory acceptance across global markets.
The built-in surge protection reduces transient damage and downtime, while the wide coil voltage range lowers inventory complexity and improves reliability in networks with voltage variation. The compact block design and DIN-rail mounting simplify installation and future upgrades, delivering lower maintenance costs and faster commissioning for OEMs and maintenance teams.