ABB 1SBL177001R1201 Block Contactor - IEC/UL 60947-4-1
Part Number: 1SBL177001R1201
Quick Summary
ABB 1SBL177001R1201 is a block contactor designed for reliable motor control in industrial equipment. In networks with wide control voltage swings, users struggle with nuisance trips and inefficient energy use, especially in unstable panel environments. It meets IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40, and CSA standards, delivering safety and compliance. Built-in surge protection and a compact, extendable design simplify installation on DIN rails, while the AF technology supports a wide control voltage range. This combination reduces energy losses, improves uptime, and lowers total cost of ownership, aligning with procurement goals for dependable, standards-compliant motor control.
Product Information
Extended Description
1SBL177001R1201 ABB: The AF16-30-01-12 is a 3 pole - 690 V IEC or 600 UL contactor with 1 built-in auxiliary contact and screw terminals, controlling motors up to 7.5 kW / 400 V AC (AC-3) or 10 hp / 480 V UL and switching power circuits up to 30 A (AC-1) or 30 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (48-130 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Data Sheet, Technical Information
1SBC100214C0202 - Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) - Edition 2024
Instructions and Manuals
Installation instructions AF(C)09...38(Z)(B) Contactors, NF(C)(Z)(B)22...80E Contactor relays and CA4, CAL4, CAT4, CC4, LDC4 Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
45 mm
Product Net Depth / Length
77 mm
Product Net Height
86 mm
Product Net Weight
0.27 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
1
Number of Poles
3P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-4-1
Rated Operational Voltage
Auxiliary Circuit 690 V | Main Circuit 690 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 Hz | Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 35 A | acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 30 A | (690 V) 60 °C 30 A | (690 V) 70 °C 26 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 18 A | (440 V) 60 °C 18 A | (500 V) 60 °C 15 A | (690 V) 60 °C 10.5 A | (380 / 400 V) 60 °C 18 A | (220 / 230 / 240 V) 60 °C 18 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 18 A | (440 V) 60 °C 18 A | (500 V) 60 °C 15 A | (690 V) 60 °C 10.5 A | (380 / 400 V) 60 °C 18 A | (220 / 230 / 240 V) 60 °C 18 A
Rated Operational Current AC-15 (Ie)
(500 V) 2 A | (690 V) 2 A | (24 / 127 V) 6 A | (220 / 240 V) 4 A | (400 / 440 V) 3 A
Rated Operational Current DC-1 (Ie)
(110 V) 1-Pole, 40 °C 20 A | (110 V) 1-Pole, 60 °C 20 A | (110 V) 1-Pole, 70 °C 20 A | (110 V) 2 Poles in Series, 40 °C 30 A | (110 V) 2 Poles in Series, 60 °C 30 A | (110 V) 2 Poles in Series, 70 °C 26 A | (110 V) 3 Poles in Series, 40 °C 30 A | (110 V) 3 Poles in Series, 60 °C 30 A | (110 V) 3 Poles in Series, 70 °C 26 A | (220 V) 2 Poles in Series, 40 °C 20 A | (220 V) 2 Poles in Series, 60 °C 20 A | (220 V) 2 Poles in Series, 70 °C 20 A | (220 V) 3 Poles in Series, 40 °C 30 A | (220 V) 3 Poles in Series, 60 °C 30 A | (220 V) 3 Poles in Series, 70 °C 26 A | (72 V) 1-Pole, 40 °C 30 A | (72 V) 1-Pole, 60 °C 30 A | (72 V) 1-Pole, 70 °C 26 A | (72 V) 2 Poles in Series, 40 °C 30 A | (72 V) 2 Poles in Series, 60 °C 30 A | (72 V) 2 Poles in Series, 70 °C 26 A | (72 V) 3 Poles in Series, 40 °C 30 A | (72 V) 3 Poles in Series, 60 °C 30 A | (72 V) 3 Poles in Series, 70 °C 26 A
Rated Operational Current DC-3 (Ie)
(110 V) 1-Pole, 40 °C 8 A | (110 V) 1-Pole, 60 °C 8 A | (110 V) 1-Pole, 70 °C 8 A | (110 V) 2 Poles in Series, 40 °C 30 A | (110 V) 2 Poles in Series, 60 °C 30 A | (110 V) 2 Poles in Series, 70 °C 26 A | (110 V) 3 Poles in Series, 40 °C 30 A | (110 V) 3 Poles in Series, 60 °C 30 A | (110 V) 3 Poles in Series, 70 °C 26 A | (220 V) 2 Poles in Series, 40 °C 8 A | (220 V) 2 Poles in Series, 60 °C 8 A | (220 V) 2 Poles in Series, 70 °C 8 A | (220 V) 3 Poles in Series, 40 °C 30 A | (220 V) 3 Poles in Series, 60 °C 30 A | (220 V) 3 Poles in Series, 70 °C 26 A | (72 V) 1-Pole, 40 °C 30 A | (72 V) 1-Pole, 60 °C 30 A | (72 V) 1-Pole, 70 °C 26 A | (72 V) 2 Poles in Series, 40 °C 30 A | (72 V) 2 Poles in Series, 60 °C 30 A | (72 V) 2 Poles in Series, 70 °C 26 A | (72 V) 3 Poles in Series, 40 °C 30 A | (72 V) 3 Poles in Series, 60 °C 30 A | (72 V) 3 Poles in Series, 70 °C 26 A
Rated Operational Current DC-5 (Ie)
(110 V) 1-Pole, 40 °C 4 A | (110 V) 1-Pole, 60 °C 4 A | (110 V) 1-Pole, 70 °C 4 A | (110 V) 2 Poles in Series, 40 °C 20 A | (110 V) 2 Poles in Series, 60 °C 20 A | (110 V) 2 Poles in Series, 70 °C 20 A | (110 V) 3 Poles in Series, 40 °C 30 A | (110 V) 3 Poles in Series, 60 °C 30 A | (110 V) 3 Poles in Series, 70 °C 26 A | (220 V) 2 Poles in Series, 40 °C 4 A | (220 V) 2 Poles in Series, 60 °C 4 A | (220 V) 2 Poles in Series, 70 °C 4 A | (220 V) 3 Poles in Series, 40 °C 16 A | (220 V) 3 Poles in Series, 60 °C 16 A | (220 V) 3 Poles in Series, 70 °C 16 A | (72 V) 1-Pole, 40 °C 16 A | (72 V) 1-Pole, 60 °C 16 A | (72 V) 1-Pole, 70 °C 16 A | (72 V) 2 Poles in Series, 40 °C 30 A | (72 V) 2 Poles in Series, 60 °C 30 A | (72 V) 2 Poles in Series, 70 °C 26 A | (72 V) 3 Poles in Series, 40 °C 30 A | (72 V) 3 Poles in Series, 60 °C 30 A | (72 V) 3 Poles in Series, 70 °C 26 A
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W | (48 V) 2.8 A / 134 W | (72 V) 1 A / 72 W | (110 V) 0.55 A / 60 W | (125 V) 0.55 A / 69 W | (220 V) 0.27 A / 60 W | (250 V) 0.27 A / 68 W | (400 V) 0.15 A / 60 W | (500 V) 0.13 A / 65 W | (600 V) 0.1 A / 60 W
Rated Operational Power AC-3 (Pe)
(400 V) 7.5 kW | (415 V) 9 kW | (440 V) 9 kW | (500 V) 9 kW | (690 V) 9 kW | (380 / 400 V) 7.5 kW | (220 / 230 / 240 V) 4 kW
Rated Operational Power AC-3e (Pe)
(415 V) 9 kW | (440 V) 9 kW | (500 V) 9 kW | (690 V) 9 kW | (380 / 400 V) 7.5 kW | (220 / 230 / 240 V) 4 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A | for 0.1 s 140 A | for 1 s 100 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 V | acc. to IEC 60947-5-1 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-15) 1200 cycles per hour | (AC-2 / AC-4) 300 cycles per hour | (AC-3) 1200 cycles per hour | (DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 48 ... 130 V | 60 Hz 48 ... 130 V | DC Operation 48 ... 130 V
Power Loss
at 6 A per Pole 0.1 W | at Rated Operating Conditions AC-1 per Pole 1.2 W | at Rated Operating Conditions AC-3 per Pole 0.35 W
Operate Time
Between Coil De-energization and NC Contact Closing 13 ... 98 ms | Between Coil De-energization and NO Contact Opening 11 ... 95 ms | Between Coil Energization and NC Contact Opening 38 ... 90 ms | Between Coil Energization and NO Contact Closing 40 ... 95 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 0.75 ... 6 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 4 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² | Rigid Solid 1/2x 1 ... 4 mm² | Rigid Stranded 1/2x 1 ... 6 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Auxiliary Circuit 10 mm | Control Circuit 10 mm | Main Circuit 10 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Tightening Torque
Auxiliary Circuit 1.2 N·m | Control Circuit 1.2 N·m | Main Circuit 1.5 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 30 A
Horsepower Rating UL/CSA
(120 V AC) Single Phase 1-1/2 hp | (200 ... 208 V AC) Three Phase 5 hp | (220 ... 240 V AC) Three Phase 5 hp | (240 V AC) Single Phase 3 hp | (440 ... 480 V AC) Three Phase 10 hp | (550 ... 600 V AC) Three Phase 15 hp
Connecting Capacity Main Circuit UL/CSA
Rigid Solid 1/2x 16-10 AWG | Rigid Stranded 1/2x 16-10 AWG
Connecting Capacity Auxiliary Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG | Rigid Stranded 1/2x 18-14 AWG
Connecting Capacity Control Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG | Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSA
Auxiliary Circuit 11 in·lb | Control Circuit 11 in·lb | Main Circuit 13 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 20 A | (200 ... 208 V AC) Three Phase 17.5 A | (220 ... 240 V AC) Three Phase 15.2 A | (240 V AC) Single Phase 17 A | (440 ... 480 V AC) Three Phase 14 A | (550 ... 600 V AC) Three Phase 17 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -25 ... 60 °C | Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27
Closed, Shock Direction: B1 25 g | Open, Shock Direction: B1 5 g | Shock Direction: A 30 g | Shock Direction: B2 15 g | Shock Direction: C1 25 g | Shock Direction: C2 25 g
Resistance to Vibrations
4g Closed Position & 2g Open position 5 ... 300 Hz
Pollution Degree
3
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
28d6e361-832a-4974-9e8e-10684af76ce3 China (CN)
Simplified SCIP
8644f80b-a40e-4cb4-a042-21a1bdcde73e Poland (PL) | 042af014-2bff-42b6-ba7f-d5c957683bc0 Norway (NO) | 050ec330-54ce-494a-bec9-865c3c455f70 Finland (FI) | f247254d-a1bf-469e-9d7b-1f005a760839 Poland (PL) | 0a91e286-6c50-4953-817c-40159f2de0e7 Hungary (HU) | 725b73ca-519d-4a27-a5e5-77c424fa3539 Netherlands (NL) | b920f0d6-7f77-4858-9910-f6d7e81f5d4a Estonia (EE) | 040aeecb-654d-4de5-a188-6cc4324b5775 Greece (GR) | 6b26af71-1e73-4512-8718-d1a6c8336bf6 Croatia (HR) | fb6a8434-129f-4041-80ae-496c0d7453fb Germany (DE) | 3838e36b-f5af-48d7-bdf7-0a003c2a33d8 Germany (DE) | f8b123c6-471a-47ce-a3d6-153f9ff49b4e Denmark (DK) | 0d516c86-08a4-4dc0-82b0-10b11774b3c0 Belgium (BE) | 09aa3e05-3e05-425a-add6-739ea3abe583 Poland (PL) | 3558e635-8f32-4120-910b-9ec70502547f France (FR) | a9ab9edd-d711-4f0b-bb4c-ff2a1a0b288f Germany (DE) | 363cdc98-a030-40cc-a2f4-21beaf9219d7 Bulgaria (BG) | 21b737c9-6cf5-4d3c-9a27-2d3dac1eb9b6 Sweden (SE) | e5028a1c-b82c-4995-87da-d94d13937bbd Portugal (PT) | 2def76ce-3b48-4302-aeeb-049c33afbfa1 Germany (DE) | 3d0e0680-5e29-4c98-8e5b-8fb8ba0fbd29 France (FR) | cae77f80-53f0-4d2d-9193-391943ed6661 Sweden (SE) | 0dcc2afd-0658-4504-ba43-d122fffaff43 Hungary (HU) | 4383ea8c-9263-4a34-bcf3-83a13334b135 Belgium (BE) | 1d685659-1237-428a-b78a-4acdb2bcc2bf Spain (ES) | 0e8c23e4-aac5-4775-97e8-49a4bd43c437 Germany (DE) | b61f6e40-fdf4-42fb-a976-c8bd3a78acdb Czech Republic (CZ)
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
End Of Life Disassembling Instructions
End of life instruction AF(S)09/12/16/26/30/38(Z)(B)(K)(RT) Contactors & NF(Z)(B)(K)(RT) Contactors relays
Environmental Product Declaration - EPD
Environmental Product Declaration - AF09/12/16(Z)(B) Contactors and NF(Z) Contactor relaysAF(S)09/12/16(Z)(B) Contactors and NF(Z)(B) Contactors Relays (FR) | Environmental Product Declaration - AF09/12/16(Z)(B) Contactors and NF(Z) Contactor relays
Sustainable Material Content in Packaging (wt. %)
Recycled Cardboard - 86 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 28 %
A2L Certificate – UL
UL-US A2L LZGH2 Certificate of Compliance AF09 ... AF38 3-pole contactors with screw terminals - UL 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers | UL-CA A2L LZGH2 Certificate of Compliance AF09 ... AF38 3-pole contactors with screw terminals - CSA C22.2 No. 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers
ABS Certificate
ABS Certificate, AF(S)09 to AF(S)96 contactors, NF contactor relays and CA4, CC4, CAL4, CAT4 auxiliary contact blocks, TEF4 electronic timers
BV Certificate
BV Certificate AF(C)09...AF(C)38 3-pole and 4-pole contactors with screw and Push-in Spring terminals
CB Certificate
CB Certificate AF09, AF12, AF16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
CCC Certificate
CCC Certificate AF09, AF12, AF16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
CQC Certificate
CQC Certificate AF(C)09, AF(C)12, AF(C)16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors | CQC Certificate, Contactor, AF09,AF12,AF16, Made in China
Declaration of Conformity - CCC
CCC Declaration of Conformity, Contactor, AF*09, AF*12, AF*16, Made in France | CCC Declaration of Conformity, Contactor, AF09,AF12,AF16, Made in China
Declaration of Conformity - CE
EU Declaration of Conformity AF09... AF96-30-.., AF09...38(Z)-30..K 3-pole Contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09... AF96-30-.., AF09...38(Z)-30..K 3-pole Contactors
DNV Certificate
DNV Certificate AF(S)09...96 3-pole & AF09...80 4-pole contactors with screw, spring, push-in terminals
GOST Certificate
GOST_POCCFR.ME77.B07175.pdf
KC Certificate
KC Certificate AF12, AF16 3-pole contactors
LR Certificate
LRS Certificate AF(S)09..(K) ... AF96 3 and 4-pole contactors and CA(L)4..(K), CAT4, CC4 auxiliary contact blocks
RINA Certificate
Rina Certificate for AF(S)09...AF(S)96 contactors, NF contactor relays and accessories with screw,spring and push-in terminals
RMRS Certificate
RMRS Certificate AF(S)09(S)...AF(S)38 3-pole and 4-pole, AF(S)40..96 3-pole contactors with screw, push-in and spring terminals
UL Certificate
UL-US Certificate of Compliance AF(C)(S)09(R/M/N)-..(L)(S)(K)...AF(C)(S)38(R/M/N)..(K) 3-pole contactors screw, spring and push-in spring terminals; LDC4 additional coil terminal block; LF16-4, LG16-4, LF38-4 and LH38-4 connecting strips, LD38-4 additional terminal block | UL-CA Certificate of Compliance AF(C)(S)09(R/M/N)-..(L)(S)(K)...AF(C)(S)38(R/M/N)..(K) 3-pole contactors screw, spring and push-in spring terminals; LDC4 additional coil terminal block; LF16-4, LG16-4, LF38-4 and LH38-4 connecting strips, LD38-4 additional terminal block
UL Listing Card
E312527
Package Level 1 Units
box 1 piece
Package Level 1 Width
87 mm
Package Level 1 Depth / Length
79 mm
Package Level 1 Height
47 mm
Package Level 1 Gross Weight
0.27 kg
Package Level 1 EAN
3471523110724
Package Level 2 Units
box 27 piece
Package Level 2 Width
250 mm
Package Level 2 Depth / Length
300 mm
Package Level 2 Height
315 mm
Package Level 2 Gross Weight
7.29 kg
Package Level 3 Units
1296 piece
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
E-Number (Finland)
3706245
E-Number (Sweden)
3211371
Feature: Three-pole, 690 V AC-3 contactor with 7.5–9 kW Pe rating and a built-in 1 auxiliary NC contact. Business Impact: Enables high-efficiency motor switching with robust load handling and reduced wiring complexity. Application: Suitable for 3-phase motors in general industrial drives, improving line uptime. Feature: Built-in auxiliary contact and screw terminals. Business Impact: Streamlines control circuit wiring and allows straightforward integration with existing control logic. Application: Ideal for retrofit projects and new installations requiring simple control connections. Feature: AF technology with a wide control voltage range of 48–130 V AC/DC. Business Impact: Minimizes control- voltage variations, reducing panel energy consumption and limiting nuisance trips. Application: Ideal for facilities with voltage fluctuations or diverse control sources. Feature: Surge protection integrated into the device. Business Impact: Protects downstream electronics and relays, extending component life and reducing maintenance costs. Application: Particularly beneficial in harsh electrical environments or long cable runs. Feature: DIN rail mounting option (TH35-15 / TH35-7.5) and compatibility with add-on auxiliary blocks. Business Impact: Speeds up installation, simplifies future expansion, and supports modularity in control panels. Application: Supports standardized panel design and easy spare-part management. Feature: IP20 protection for coil and terminals, with screw-terminal connections and torque specifications. Business Impact: Ensures safe, reliable operation in typical indoor industrial settings while maintaining easy serviceability. Application: Suitable for clean, enclosed control panels with routine maintenance.
Get a Quick Quote for a ABB 1SBL177001R1201
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SBL177001R1201?
Enquire Now
FAQs
Install the unit on TH35-15 or TH35-7.5 DIN rails, securing with the recommended mounting method. Use two M4 screws diagonally if mounting by screws is required, connect the Main Circuit wires to the screw terminals, and ensure the Auxiliary Circuit and Control Circuit are wired per the 48–130 V range. Verify IP20 protection and tighten torque specifications after wiring.
For AC-3 at 690 V, the contactor operates up to 10.5 A (Ie) and 9 kW (Pe). At 415–690 V, AC-3e is also 10.5 A with 9 kW. In AC-1, Ie values vary with voltage and temperature, up to 30 A at 690 V and 70 °C. These ratings support reliable motor control for typical industrial loads.
Yes. The contactor provides AC-3 power handling up to 9 kW at 690 V and 7.5 kW at common 400 V class voltages, making it suitable for motors up to 7.5 kW in many European and international installations. It also supports UL/CSA configurations for broader compatibility.
It conforms to IEC 60947-1 and IEC 60947-4-1, with UL 60335-2-40 and CSA listings. Additional certificates include CE and UKCA declarations, and various third-party verifications (ABS, BV, DNV, UL Listings) depending on regional configurations, ensuring compliance for global deployments.
AF technology provides a wide control voltage tolerance (48–130 V), reducing nuisance trips from voltage fluctuations and limiting panel energy waste. Built-in surge protection minimizes coil and contact wear, lowering maintenance costs and extending lifecycle in demanding environments. The design also supports modular accessories for longer panel life and faster upgrades.