ABB AF16B-40-00RT-14 Block Contactor - IEC/UL 4P

Part Number: 1SBL177260R1400
Manufacturer
ABB
Part number
1SBL177260R1400

Quick Summary

The ABB AF16B-40-00RT-14 Block Contactor is a 4-pole, 690 V AC motor switch designed to reliably drive pumps, fans, conveyors and other heavy-duty loads. It operates across a wide control voltage range, reducing panel wiring and energy variation issues in unstable networks. The device features built-in surge protection and a compact block design that can be extended with auxiliary contact blocks and accessories. Compliance with IEC/EN 60947-4-1, UL 60947-4-1, and CE declarations helps validate system safety and regulatory readiness. For engineers and procurement teams, this means easier stocking, faster installation, and predictable performance in demanding industrial environments. Its 7.5 kW to 9 kW ratings at common voltages ensure scalable automation for growing plants.

Product Information

Extended Description

1SBL177260R1400 ABB: The AF16B-40-00RT-14 is a 4 pole - 690 V IEC or 600 UL contactor with Ring-Tongue Terminals, controlling motors up to 7.5 kW / 400 V AC (AC-3) and switching power circuits up to 30 A (AC-1) or 30 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (250-500 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
Motor control and protection for Rolling stock application_PDF
Instructions and Manuals
Installation instructions AF09...38(Z)B-..RT Contactors, NF(Z)B..ERT Contactor relays and CA4..RT, CAL4..RT, CAT4..RT, LDC4RT Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
45 mm
Product Net Depth / Length
77 mm
Product Net Height
86 mm
Product Net Weight
0.32 kg
Number of Main Contacts NO
4
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Number of Poles
4P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives.
Rated Operational Voltage
Main Circuit 690 V
Rated Frequency (f)
Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 35 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 30 A | (690 V) 60 °C 30 A | (690 V) 70 °C 26 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 18 A | (440 V) 60 °C 18 A | (500 V) 60 °C 15 A | (690 V) 60 °C 10.5 A | (380 / 400 V) 60 °C 18 A | (220 / 230 / 240 V) 60 °C 18 A
Rated Operational Current DC-1 (Ie)
(110 V) 1-Pole, 40 °C 20 A | (110 V) 1-Pole, 60 °C 20 A | (110 V) 1-Pole, 70 °C 20 A | (110 V) 2 Poles in Series, 40 °C 30 A | (110 V) 2 Poles in Series, 60 °C 30 A | (110 V) 2 Poles in Series, 70 °C 26 A | (110 V) 3 Poles in Series, 40 °C 30 A | (110 V) 3 Poles in Series, 60 °C 30 A | (110 V) 3 Poles in Series, 70 °C 26 A | (110 V) 4 Poles in Series, 40 °C 30 A | (110 V) 4 Poles in Series, 60 °C 30 A | (110 V) 4 Poles in Series, 70 °C 26 A | (220 V) 2 Poles in Series, 40 °C 20 A | (220 V) 2 Poles in Series, 60 °C 20 A | (220 V) 2 Poles in Series, 70 °C 20 A | (220 V) 3 Poles in Series, 40 °C 30 A | (220 V) 3 Poles in Series, 60 °C 30 A | (220 V) 3 Poles in Series, 70 °C 26 A | (220 V) 4 Poles in Series, 40 °C 30 A | (220 V) 4 Poles in Series, 60 °C 30 A | (220 V) 4 Poles in Series, 70 °C 26 A | (440 V) 4 Poles in Series, 40 °C 20 A | (440 V) 4 Poles in Series, 60 °C 20 A | (440 V) 4 Poles in Series, 70 °C 20 A | (72 V) 1-Pole, 40 °C 30 A | (72 V) 1-Pole, 60 °C 30 A | (72 V) 1-Pole, 70 °C 26 A | (72 V) 2 Poles in Series, 40 °C 30 A | (72 V) 2 Poles in Series, 60 °C 30 A | (72 V) 2 Poles in Series, 70 °C 26 A | (72 V) 3 Poles in Series, 40 °C 30 A | (72 V) 3 Poles in Series, 60 °C 30 A | (72 V) 3 Poles in Series, 70 °C 26 A | (72 V) 4 Poles in Series, 40 °C 30 A | (72 V) 4 Poles in Series, 60 °C 30 A | (72 V) 4 Poles in Series, 70 °C 26 A
Rated Operational Current DC-3 (Ie)
(110 V) 1-Pole, 40 °C 8 A | (110 V) 1-Pole, 60 °C 8 A | (110 V) 1-Pole, 70 °C 8 A | (110 V) 2 Poles in Series, 40 °C 30 A | (110 V) 2 Poles in Series, 60 °C 30 A | (110 V) 2 Poles in Series, 70 °C 26 A | (110 V) 3 Poles in Series, 40 °C 30 A | (110 V) 3 Poles in Series, 60 °C 30 A | (110 V) 3 Poles in Series, 70 °C 26 A | (110 V) 4 Poles in Series, 40 °C 30 A | (110 V) 4 Poles in Series, 60 °C 30 A | (110 V) 4 Poles in Series, 70 °C 26 A | (220 V) 2 Poles in Series, 40 °C 8 A | (220 V) 2 Poles in Series, 60 °C 8 A | (220 V) 2 Poles in Series, 70 °C 8 A | (220 V) 3 Poles in Series, 40 °C 30 A | (220 V) 3 Poles in Series, 60 °C 30 A | (220 V) 3 Poles in Series, 70 °C 26 A | (220 V) 4 Poles in Series, 40 °C 30 A | (220 V) 4 Poles in Series, 60 °C 30 A | (220 V) 4 Poles in Series, 70 °C 26 A | (440 V) 4 Poles in Series, 40 °C 8 A | (440 V) 4 Poles in Series, 60 °C 8 A | (440 V) 4 Poles in Series, 70 °C 8 A | (72 V) 1-Pole, 40 °C 30 A | (72 V) 1-Pole, 60 °C 30 A | (72 V) 1-Pole, 70 °C 26 A | (72 V) 2 Poles in Series, 40 °C 30 A | (72 V) 2 Poles in Series, 60 °C 30 A | (72 V) 2 Poles in Series, 70 °C 26 A | (72 V) 3 Poles in Series, 40 °C 30 A | (72 V) 3 Poles in Series, 60 °C 30 A | (72 V) 3 Poles in Series, 70 °C 26 A | (72 V) 4 Poles in Series, 40 °C 30 A | (72 V) 4 Poles in Series, 60 °C 30 A | (72 V) 4 Poles in Series, 70 °C 26 A
Rated Operational Current DC-5 (Ie)
(110 V) 1-Pole, 40 °C 4 A | (110 V) 1-Pole, 60 °C 4 A | (110 V) 1-Pole, 70 °C 4 A | (110 V) 2 Poles in Series, 40 °C 20 A | (110 V) 2 Poles in Series, 60 °C 20 A | (110 V) 2 Poles in Series, 70 °C 20 A | (110 V) 3 Poles in Series, 40 °C 30 A | (110 V) 3 Poles in Series, 60 °C 30 A | (110 V) 3 Poles in Series, 70 °C 26 A | (110 V) 4 Poles in Series, 40 °C 30 A | (110 V) 4 Poles in Series, 60 °C 30 A | (110 V) 4 Poles in Series, 70 °C 26 A | (220 V) 2 Poles in Series, 40 °C 4 A | (220 V) 2 Poles in Series, 60 °C 4 A | (220 V) 2 Poles in Series, 70 °C 4 A | (220 V) 3 Poles in Series, 40 °C 16 A | (220 V) 3 Poles in Series, 60 °C 16 A | (220 V) 3 Poles in Series, 70 °C 16 A | (220 V) 4 Poles in Series, 40 °C 20 A | (220 V) 4 Poles in Series, 60 °C 20 A | (220 V) 4 Poles in Series, 70 °C 20 A | (440 V) 4 Poles in Series, 40 °C 4 A | (440 V) 4 Poles in Series, 60 °C 4 A | (440 V) 4 Poles in Series, 70 °C 4 A | (72 V) 1-Pole, 40 °C 16 A | (72 V) 1-Pole, 60 °C 16 A | (72 V) 1-Pole, 70 °C 16 A | (72 V) 2 Poles in Series, 40 °C 30 A | (72 V) 2 Poles in Series, 60 °C 30 A | (72 V) 2 Poles in Series, 70 °C 26 A | (72 V) 3 Poles in Series, 40 °C 30 A | (72 V) 3 Poles in Series, 60 °C 30 A | (72 V) 3 Poles in Series, 70 °C 26 A | (72 V) 4 Poles in Series, 40 °C 30 A | (72 V) 4 Poles in Series, 60 °C 30 A | (72 V) 4 Poles in Series, 70 °C 26 A
Rated Operational Power AC-3 (Pe)
(400 V) 7.5 kW | (415 V) 9 kW | (440 V) 9 kW | (500 V) 9 kW | (690 V) 9 kW | (380 / 400 V) 7.5 kW | (220 / 230 / 240 V) 4 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 250 ... 500 V | 60 Hz 250 ... 500 V | DC Operation 250 ... 500 V
Power Loss
at Rated Operating Conditions AC-1 per Pole 1.2 W | at Rated Operating Conditions AC-3 per Pole 0.35 W
Operate Time
Between Coil De-energization and NC Contact Closing 13 ... 98 ms | Between Coil De-energization and NO Contact Opening 11 ... 95 ms | Between Coil Energization and NC Contact Opening 38 ... 90 ms | Between Coil Energization and NO Contact Closing 40 ... 95 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 screws placed diagonally
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP10 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Tightening Torque
Control Circuit 1.2 N·m | Main Circuit 1.5 N·m
Terminal Type
Ring-Tongue Terminals
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 30 A
Tightening Torque UL/CSA
Control Circuit 11 in·lb | Main Circuit 13 in·lb
Ambient Air Temperature
Close to Contactor for Storage -60 ... +80 °C | Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Shock and Vibration Withstand acc. to IEC 61373
Category 1, Class B
Pollution Degree
3
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
End Of Life Disassembling Instructions
End of life instruction AF(S)09/12/16/26/30/38(Z)(B)(K)(RT) Contactors & NF(Z)(B)(K)(RT) Contactors relays
Environmental Product Declaration - EPD
Environmental Product Declaration - AF09/12/16(Z)(B) Contactors and NF(Z) Contactor relaysAF(S)09/12/16(Z)(B) Contactors and NF(Z)(B) Contactors Relays (FR)
Sustainable Material Content in Packaging (wt. %)
Recycled Cardboard - 86 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 28 %
CB Certificate
CB Certificate AF09, AF12, AF16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
CCC Certificate
CCC Certificate AF09, AF12, AF16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
CQC Certificate
CQC Certificate AF(C)09, AF(C)12, AF(C)16, AF09(Z)B, AF12(Z)B, AF16(Z)B 3 and 4-pole contactors, AFS09, AFS12, AFS16 safety contactors
Declaration of Conformity - CCC
CCC Declaration of Conformity, Contactor, AF*09, AF*12, AF*16, Made in France
Declaration of Conformity - CE
EU Declaration of Conformity AF09 to AF38(Z)B..RT 3 and 4-pole contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09 to AF38(Z)B..RT 3 and 4-pole contactors
UL Listing Card
UL_E319322
UR Certificate
UR Certificate of Compliance AF09...AF38(Z)B-..RT 4-pole contactors with ring tongue terminals
Package Level 1 Units
box 1 piece
Package Level 1 Width
87 mm
Package Level 1 Depth / Length
79 mm
Package Level 1 Height
47 mm
Package Level 1 Gross Weight
0.32 kg
Package Level 1 EAN
3471523127142
Package Level 2 Units
box 27 piece
Package Level 2 Width
250 mm
Package Level 2 Depth / Length
300 mm
Package Level 2 Height
315 mm
Package Level 2 Gross Weight
17.28 kg
Package Level 3 Units
1296 piece
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
Feature: AF technology delivers a wide control voltage range of 250 to 500 V AC, including DC operation. Business impact: it tolerates large control voltage variations, reducing panel energy consumption and avoiding misoperation in unstable networks. Application: ideal for machine feeders, conveyors, and pumps where supply quality varies.Feature: Built-in surge protection and a compact 4P design. Business impact: extends life of the contactor and reduces external surge protection parts. Application: rolling stock motor control and heavy-duty loads.Feature: Ring-Tongue terminals and DIN rail mounting TH35-15 or TH35-7.5 provide robust, easy-to-wire installations. Business impact: speeds up commissioning and simplifies field maintenance. Application: panel builders and retrofit projects.Feature: Wide operating voltage and power ratings with AC-3 up to 18 A and AC-1 up to 30 A. Business impact: supports scalable drive configurations, lowering part variety and stockkeeping. Application: conveyors, pumps, fans and other motor-driven lines.Feature: Compatibility with auxiliary contact blocks and accessories; block design enables compact layouts. Business impact: enables future expansion without hardware changes; Application: automation cells and modular machinery.Feature: Compliance and reliability—IP10 terminals, RoHS/REACH, and UL/CE/UKCA declarations. Business impact: reduces compliance risk and simplifies vendor qualification. Application: industrial equipment in global plants.

Get a Quick Quote for a ABB 1SBL177260R1400

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SBL177260R1400? Enquire Now

FAQs

This contactor supports DIN Rail mounting TH35-15 (35x15 mm) or TH35-7.5 (35x7.5 mm). For non-DIN installations, two M4 screws are placed diagonally. This simplifies panel integration and retrofits.
AC-3 rated current at 690 V is 10.5 A (60°C). At 415–440 V it can reach 18 A (60°C), with variation for higher ambient temperatures. This supports up to 9 kW in typical motor control applications.
The device accepts a control circuit voltage of 250 to 500 V for AC or DC operation, enabling reliable switching despite voltage fluctuations in industrial power networks.
It aligns with IEC/EN 60947-1, IEC/EN 60947-4-1, and UL 60947-4-1, with CE, UKCA declarations and UL listing. RoHS, REACH and CMRT support global compliance.
Built-in surge protection reduces external components; low coil power loss (about 0.35 W per pole under AC-3) lowers operating costs, while modular add-ons simplify ongoing maintenance and future upgrades.