ABB 1SBL211001R5110 Contactor - IEC 60947-4-1
Part Number: 1SBL211001R5110
Quick Summary
ABB 1SBL211001R5110 Contactor is a compact 3-pole switch designed for reliable motor control in industrial automation. Engineers often face challenges aligning coil voltages, terminal layouts, and accessory options within limited cabinets. This device addresses those pains with a 400–415 V AC (50 Hz) or 480 V AC (60 Hz) coil, a built-in NO auxiliary contact, and screw terminals in a 45 mm-wide block that fits tight control panels. It complies with IEC/EN 60947-4-1 and UL 60947-4-1, and offers an optional add-on contact blocks to extend functionality. For procurement and maintenance teams, the standardized ratings—AC-3 up to 32 A at 690 V, IP20 protection—simplify stocking, improve serviceability, and ensure consistent performance across AF platform applications.
Product Information
Extended Description
1SBL211001R5110 ABB: The AFC25-30-10-51 is a 3-pole - 690 V IEC or 600 V UL contactor with 1 N.O built-in auxiliary contact and Screw terminals, mainly controlling power circuits up to 11 kW / 400 V AC (AC-3) or 15 hp / 480 V AC UL and 32 A (AC-1) or 30 A UL general use. Within the AF platform, AFC contactors offer an optimized operating time for AC controlled applications with electromagnetic coil (control voltage : 400 ... 415 V AC 50 Hz / 480 V AC 60 Hz). AFC contactors have a block type design and can be easily extended with add-on auxiliary contact blocks and a wide range of additionnal accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
1SBC100219C0201 AFC contactors for AC control applications_Catalog PDF
Instructions and Manuals
Installation instructions AF(C)09...38(Z)(B) Contactors, NF(C)(Z)(B)22...80E Contactor relays and CA4, CAL4, CAT4, CC4, LDC4 Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
45 mm
Product Net Depth / Length
77 mm
Product Net Height
86 mm
Product Net Weight
0.298 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
0
Number of Poles
3P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, UL 60335-2-40 LZGH2 A2L
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 35 A | acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 32 A | (690 V) 60 °C 32 A | (690 V) 70 °C 28 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 25 A | (380 / 400 V) 60 °C 25 A | (220 / 230 / 240 V) 60 °C 25 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 25 A | (380 / 400 V) 60 °C 25 A | (220 / 230 / 240 V) 60 °C 25 A
Rated Operational Current AC-15 (Ie)
(24 / 127 V) 6 A | (220 / 240 V) 4 A | (400 / 440 V) 3 A
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W | (48 V) 2.8 A / 134 W | (72 V) 1 A / 72 W | (110 V) 0.55 A / 60 W | (125 V) 0.55 A / 69 W | (220 V) 0.27 A / 60 W | (250 V) 0.27 A / 68 W | (400 V) 0.15 A / 60 W | (500 V) 0.13 A / 65 W | (600 V) 0.1 A / 60 W
Rated Operational Power AC-3 (Pe)
(415 V) 11 kW | (380 / 400 V) 11 kW | (220 / 230 / 240 V) 5.5 kW
Rated Operational Power AC-3e (Pe)
(415 V) 11 kW | (380 / 400 V) 11 kW | (220 / 230 / 240 V) 5.5 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 200 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 85 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 105 A | for 0.1 s 140 A | for 1 s 100 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 V | acc. to IEC 60947-5-1 690 V | acc. to UL/CSA 600 V
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-15) 1200 cycles per hour | (AC-3) 1200 cycles per hour | (DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 400 ... 415 V | 50 Hz 400 ... 415 V | 60 Hz 480 V
Coil Consumption
Average Holding Value 50 / 60 Hz 8 V·A | Average Pull-in Value 50 Hz 70 V·A | Average Pull-in Value 60 Hz 66 V·A
Power Loss
at Rated Operating Conditions AC-1 per Pole 1.4 W | at Rated Operating Conditions AC-3 per Pole 0.7 W
Operate Time
Between Coil De-energization and NC Contact Closing 9 ... 20 ms | Between Coil De-energization and NO Contact Opening 4 ... 18 ms | Between Coil Energization and NC Contact Opening 7 ... 21 ms | Between Coil Energization and NO Contact Closing 10 ... 26 ms
Connecting Capacity Main Circuit
Rigid Solid 1/2x 1 ... 4 mm² | Rigid Stranded 1/2x 1 ... 6 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Auxiliary Circuit 10 mm | Control Circuit 10 mm | Main Circuit 10 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Tightening Torque
Auxiliary Circuit 1.2 N·m | Control Circuit 1.2 N·m | Main Circuit 1.5 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 30 A
Horsepower Rating UL/CSA
(120 V AC) Single Phase 2 hp | (200 ... 208 V AC) Three Phase 7.5 hp | (220 ... 240 V AC) Three Phase 7.5 hp | (240 V AC) Single Phase 3 hp | (440 ... 480 V AC) Three Phase 15 hp | (550 ... 600 V AC) Three Phase 15 hp
Connecting Capacity Main Circuit UL/CSA
Rigid Solid 1/2x 16-10 AWG | Rigid Stranded 1/2x 16-10 AWG
Connecting Capacity Auxiliary Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG | Rigid Stranded 1/2x 18-14 AWG
Connecting Capacity Control Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG | Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSA
Auxiliary Circuit 11 in·lb | Control Circuit 11 in·lb | Main Circuit 13 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 24 A | (200 ... 208 V AC) Three Phase 25.3 A | (220 ... 240 V AC) Three Phase 22 A | (240 V AC) Single Phase 17 A | (440 ... 480 V AC) Three Phase 21 A | (550 ... 600 V AC) Three Phase 17 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -25 ... 60 °C | Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 60 °C | Close to Contactor without Thermal O/L Relay (Uc) -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27
Closed, Shock Direction: B1 25 g | Open, Shock Direction: B1 5 g | Shock Direction: A 30 g | Shock Direction: B2 15 g | Shock Direction: C1 25 g | Shock Direction: C2 25 g
Resistance to Vibrations
4g Closed Position & 2g Open position 5 ... 300 Hz
Pollution Degree
3
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
A2L Certificate – UL
UL-US A2L LZGH2 Certificate of Compliance AFC09 ... AFC38 3-pole contactors with screw terminals - UL 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers | UL-CA A2L LZGH2 Certificate of Compliance AFC09 ... AFC38 3-pole contactors with screw terminals - CSA C22.2 No. 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers
BV Certificate
BV Certificate AF(C)09...AF(C)38 3-pole and 4-pole contactors with screw and Push-in Spring terminals
CB Certificate
CB Certificate AFC09, AFC12, AFC16 3 or 4-pole contactors
CCC Certificate
CCC Certificate, Contactor, AFC25
Declaration of Conformity - CE
EU Declaration of Conformity AFC09..(K) ... AFC96 3-pole Contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AFC09..(K) ... AFC96 3-pole Contactors
DNV Certificate
DNV Certificate AFC09...96 3-pole & AFC09...80 4-pole contactors with screw, push-in terminals
RINA Certificate
Rina Certificate for AFC09...AFC96 3 pole and 4 pole contactors, NFC relays ,screw and spring terminals
UL Certificate
UL-Certificate of Compliance AFC09 ... AFC38 3-pole contactors
Package Level 1 Units
box 1 piece
Package Level 1 Width
87 mm
Package Level 1 Depth / Length
79 mm
Package Level 1 Height
47 mm
Package Level 1 Gross Weight
0.321 kg
Package Level 1 EAN
3471523021426
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4755 >> Contactors
Feature: 3-pole block contactor with coil voltage options 400–415 V AC at 50 Hz or 480 V AC at 60 Hz. Business Impact: Enables reliable AC motor starting with consistent performance across common European and North American control voltages. Application: Ideal for controlling motors up to 11 kW at 400 V AC (AC-3) and 15 hp at 480 V UL ratings, reducing panel complexity and spare part variety. Feature: Built-in 1 NO auxiliary contact. Business Impact: Enables interlock, feedback, and control logic without additional components, lowering wiring effort and improving diagnostics. Application: Suitable for signaling, sequencing, and integration with soft starters or starter relays. Feature: Screw terminals and 45 mm width. Business Impact: Streamlines field wiring, saves cabinet space, and simplifies maintenance with standard terminal technology. Application: Fits into compact control panels with straightforward torque and conductor sizing. Feature: AF platform compatibility with add-on accessories. Business Impact: Scales from basic control to advanced interlocks while preserving familiar ABB interfaces. Application: Facilitates phased upgrades and spare parts consistency across multiple machines. Feature: Compliance and protection. Business Impact: Meeting IEC/EN 60947-1, UL 60947-4-1, and IP20 ratings reduces regulatory risk and enhances operator safety. Application: Deploy in industrial cabinets requiring robust protection and traceable certifications.
Get a Quick Quote for a ABB 1SBL211001R5110
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SBL211001R5110?
Enquire Now
FAQs
The main circuit uses rigid solid or stranded conductors sized 1/2 x 1 to 6 mm² with a tightening torque of 1.5 N·m. The auxiliary circuit accepts flexible with ferrule 0.75–2.5 mm² or rigid solid 1/2 x 1 to 2.5 mm², with a 1.2 N·m torque. Use 10 mm wire stripping length for both circuits to ensure reliable termination and minimize risk of loose connections in vibration-prone environments.
This 3-pole contactor is designed for coil voltages of 400–415 V AC (50 Hz) or 480 V AC (60 Hz). It provides AC-3 operation up to 25 A at 415 V and up to 11 kW at 400 V, with a maximum short-time withstand current suitable for motor starting. The device also supports general purpose use up to specified UL/CSA ratings, enabling compliant integration in both IEC and UL control circuits.
Yes, within its specifications. It features IP20 protection for terminals and is rated for ambient conditions up to 60–70 °C depending on the coil and enclosure. It is listed under IEC/EN 60947-1 and UL 60947-4-1, with a maximum installation altitude of up to 3000 m without derating, making it suitable for most factory floors and machine controls.
The device complies with IEC/EN 60947-1 and IEC/EN 60947-4-1, UL 60947-4-1, and CSA C22.2 standards. It also carries declarations and certificates such as UL, CSA, CB, BV, DNV, RINA, CCC, CE UKCA, and REACH/RoHS compliance, ensuring regulatory fit across global markets and facilitating product registrations and audits.
The compact 45 mm width, screw-terminal design, and 0.298 kg weight simplify cabinet layout and serviceability. The integrated aux contact reduces component counts, while AF platform compatibility allows adding auxiliary blocks as needs grow. Tightening torques, wiring options, and dimensional data are all documented to support quick commissioning, reduced downtime, and predictable maintenance cycles.