ABB Block Contactor 1SBL231001R8100 - IEC 60947-4-1
Part Number: 1SBL231001R8100
Quick Summary
ABB Block Contactor 1SBL231001R8100 is a 3-pole coil-operated switch for motor control and power circuits. When projects scale, engineers often struggle with reliability, mounting flexibility, and cross-border compliance. This device meets IEC/EN 60947-1, IEC/EN 60947-4-1, and UL/CSA safety standards, with CE declarations for global use. Designed for DIN rail mounting on TH35 profiles and screw-terminal wiring, it supports compact installations while reducing energy use and downtime.
Product Information
Extended Description
1SBL231001R8100 ABB: The AFC26-30-00-81 is a 3-pole - 690 V IEC or 600 V UL contactor withScrew terminals, mainly controlling power circuits up to 11 kW / 400 V AC (AC-3) or 15 hp / 480 V AC UL and 45 A (AC-1) or 45 A UL general use. Within the AF platform, AFC contactors offer an optimized operating time for AC controlled applications with electromagnetic coil (control voltage : 24 V AC 50 Hz / 24 V AC 60 Hz). AFC contactors have a block type design and can be easily extended with add-on auxiliary contact blocks and a wide range of additionnal accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
1SBC100219C0201 AFC contactors for AC control applications_Catalog PDF
Instructions and Manuals
Installation instructions AF(C)09...38(Z)(B) Contactors, NF(C)(Z)(B)22...80E Contactor relays and CA4, CAL4, CAT4, CC4, LDC4 Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
45 mm
Product Net Depth / Length
86 mm
Product Net Height
86 mm
Product Net Weight
0.36 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Number of Poles
3P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, UL 60335-2-40 LZGH2 A2L
Rated Operational Voltage
Main Circuit 690 V
Rated Frequency (f)
Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 50 A | acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 45 A | (690 V) 60 °C 40 A | (690 V) 70 °C 32 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 26 A | (440 V) 60 °C 26 A | (500 V) 60 °C 23 A | (690 V) 60 °C 17 A | (380 / 400 V) 60 °C 26 A | (220 / 230 / 240 V) 60 °C 26 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 26 A | (440 V) 60 °C 26 A | (500 V) 60 °C 23 A | (690 V) 60 °C 17 A | (380 / 400 V) 60 °C 26 A | (220 / 230 / 240 V) 60 °C 26 A
Rated Operational Current DC-1 (Ie)
(110 V) 2 Poles in Series, 40 °C 45 A | (110 V) 2 Poles in Series, 60 °C 40 A | (110 V) 2 Poles in Series, 70 °C 32 A | (110 V) 3 Poles in Series, 40 °C 45 A | (110 V) 3 Poles in Series, 60 °C 40 A | (110 V) 3 Poles in Series, 70 °C 32 A | (220 V) 3 Poles in Series, 40 °C 45 A | (220 V) 3 Poles in Series, 60 °C 40 A | (220 V) 3 Poles in Series, 70 °C 32 A | (72 V) 1-Pole, 40 °C 45 A | (72 V) 1-Pole, 60 °C 40 A | (72 V) 1-Pole, 70 °C 32 A | (72 V) 2 Poles in Series, 40 °C 45 A | (72 V) 2 Poles in Series, 60 °C 40 A | (72 V) 2 Poles in Series, 70 °C 32 A | (72 V) 3 Poles in Series, 40 °C 45 A | (72 V) 3 Poles in Series, 60 °C 40 A | (72 V) 3 Poles in Series, 70 °C 32 A
Rated Operational Current DC-3 (Ie)
(110 V) 2 Poles in Series, 40 °C 45 A | (110 V) 2 Poles in Series, 60 °C 40 A | (110 V) 2 Poles in Series, 70 °C 32 A | (110 V) 3 Poles in Series, 40 °C 45 A | (110 V) 3 Poles in Series, 60 °C 40 A | (110 V) 3 Poles in Series, 70 °C 32 A | (220 V) 3 Poles in Series, 40 °C 45 A | (220 V) 3 Poles in Series, 60 °C 40 A | (220 V) 3 Poles in Series, 70 °C 32 A | (72 V) 1-Pole, 40 °C 45 A | (72 V) 1-Pole, 60 °C 40 A | (72 V) 1-Pole, 70 °C 32 A | (72 V) 2 Poles in Series, 40 °C 45 A | (72 V) 2 Poles in Series, 60 °C 40 A | (72 V) 2 Poles in Series, 70 °C 32 A | (72 V) 3 Poles in Series, 40 °C 45 A | (72 V) 3 Poles in Series, 60 °C 40 A | (72 V) 3 Poles in Series, 70 °C 32 A
Rated Operational Current DC-5 (Ie)
(110 V) 2 Poles in Series, 40 °C 45 A | (110 V) 2 Poles in Series, 60 °C 40 A | (110 V) 2 Poles in Series, 70 °C 32 A | (110 V) 3 Poles in Series, 40 °C 45 A | (110 V) 3 Poles in Series, 60 °C 40 A | (110 V) 3 Poles in Series, 70 °C 32 A | (220 V) 3 Poles in Series, 40 °C 20 A | (220 V) 3 Poles in Series, 60 °C 20 A | (220 V) 3 Poles in Series, 70 °C 20 A | (72 V) 1-Pole, 40 °C 20 A | (72 V) 1-Pole, 60 °C 20 A | (72 V) 1-Pole, 70 °C 20 A | (72 V) 2 Poles in Series, 40 °C 45 A | (72 V) 2 Poles in Series, 60 °C 40 A | (72 V) 2 Poles in Series, 70 °C 32 A | (72 V) 3 Poles in Series, 40 °C 45 A | (72 V) 3 Poles in Series, 60 °C 40 A | (72 V) 3 Poles in Series, 70 °C 32 A
Rated Operational Power AC-3 (Pe)
(415 V) 11 kW | (440 V) 15 kW | (500 V) 15 kW | (690 V) 15 kW | (380 / 400 V) 11 kW | (220 / 230 / 240 V) 6.5 kW
Rated Operational Power AC-3e (Pe)
(415 V) 11 kW | (440 V) 15 kW | (500 V) 15 kW | (690 V) 15 kW | (380 / 400 V) 11 kW | (220 / 230 / 240 V) 6.5 kW
Rated Operational Power AC-6b (Pe)
(400 / 415 V) 40 °C, 50 / 60 Hz 19 kvar | (400 / 415 V) 70 °C, 50 / 60 Hz 15 kvar | (400 / 415 V) 55 °C, 50 / 60 Hz 19 kvar | (500 / 550 V), 40 °C, 50 / 60 Hz 23 kvar | (500 / 550 V) 55 °C, 50 / 60 Hz 23 kvar | (500 / 550 V) 70 °C, 50 / 60 Hz 19 kvar | (690 V) 40 °C, 50 / 60 Hz 32 kvar | (690 V) 55 °C, 50 / 60 Hz 32 kvar | (690 V) 70 °C, 50 / 60 Hz 26 kvar
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 350 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 50 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 150 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 700 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 225 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 500 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 200 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-15) 0 cycles per hour | (AC-2 / AC-4) 150 cycles per hour | (AC-3) 1200 cycles per hour | (DC-13) 0 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 24 V | 60 Hz 24 V
Coil Consumption
Average Holding Value 50 / 60 Hz 8 V·A | Average Pull-in Value 50 Hz 70 V·A | Average Pull-in Value 60 Hz 66 V·A
Power Loss
at Rated Operating Conditions AC-1 per Pole 1.8 W | at Rated Operating Conditions AC-3 per Pole 0.6 W
Operate Time
Between Coil De-energization and NC Contact Closing 9 ... 20 ms | Between Coil De-energization and NO Contact Opening 4 ... 18 ms | Between Coil Energization and NC Contact Opening 7 ... 21 ms | Between Coil Energization and NO Contact Closing 10 ... 26 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 1.5 ... 10 mm² | Flexible with Insulated Ferrule 1x 1.5 ... 10 mm² | Flexible with Insulated Ferrule 2x 1.5 ... 4 mm² | Rigid Solid 1/2x 2.5 ... 4 mm² | Rigid Stranded 1/2x 2.5 ... 10 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Control Circuit 10 mm | Main Circuit 14 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Tightening Torque
Control Circuit 1.2 N·m | Main Circuit 2.5 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
NEMA Size
1
Continuous Current Rating NEMA
27 A
Horsepower Rating NEMA
(115 V AC) Single Phase 2 Hp | (200 V AC) Three Phase 7-1/2 Hp | (230 V AC) Single Phase 3 Hp | (230 V AC) Three Phase 7-1/2 Hp | (460 V AC) Three Phase 10 Hp | (575 V AC) Three Phase 10 Hp
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 45 A
Horsepower Rating UL/CSA
(120 V AC) Single Phase 2 hp | (200 ... 208 V AC) Three Phase 7-1/2 hp | (220 ... 240 V AC) Three Phase 7-1/2 hp | (240 V AC) Single Phase 3 hp | (440 ... 480 V AC) Three Phase 15 hp | (550 ... 600 V AC) Three Phase 20 hp
Connecting Capacity Main Circuit UL/CSA
Rigid Solid 1/2x 14-10 AWG | Rigid Stranded 1/2x 14-8 AWG
Connecting Capacity Control Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG | Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSA
Control Circuit 11 in·lb | Main Circuit 22 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 24 A | (200 ... 208 V AC) Three Phase 25.3 A | (220 ... 240 V AC) Three Phase 22 A | (240 V AC) Single Phase 17 A | (440 ... 480 V AC) Three Phase 21 A | (550 ... 600 V AC) Three Phase 22 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -25 ... 60 °C | Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 60 °C | Close to Contactor without Thermal O/L Relay (Uc) -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27
Closed, Shock Direction: B1 25 g | Open, Shock Direction: B1 5 g | Shock Direction: A 30 g | Shock Direction: B2 15 g | Shock Direction: C1 25 g | Shock Direction: C2 25 g
Resistance to Vibrations
4g Closed Position & 2g Open position 5 ... 300 Hz
Pollution Degree
3
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
A2L Certificate – UL
UL-US A2L LZGH2 Certificate of Compliance AFC09 ... AFC38 3-pole contactors with screw terminals - UL 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers | UL-CA A2L LZGH2 Certificate of Compliance AFC09 ... AFC38 3-pole contactors with screw terminals - CSA C22.2 No. 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers
BV Certificate
BV Certificate AF(C)09...AF(C)38 3-pole and 4-pole contactors with screw and Push-in Spring terminals
CB Certificate
CB Certificate AFC26, AFC30, AFC38 3-pole contactors
CQC Certificate
CQC Certificate, Contactor, AF*26, AF*30, AF*38, Made in France
Declaration of Conformity - CCC
CCC Declaration of Conformity, Contactor, AF26, AF30, AF38, AFS26, AFS30, AFS38 Made in France
Declaration of Conformity - CE
EU Declaration of Conformity AFC09..(K) ... AFC96 3-pole Contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AFC09..(K) ... AFC96 3-pole Contactors
DNV Certificate
DNV Certificate AFC09...96 3-pole & AFC09...80 4-pole contactors with screw, push-in terminals
RINA Certificate
Rina Certificate for AFC09...AFC96 3 pole and 4 pole contactors, NFC relays ,screw and spring terminals
UL Certificate
UL-Certificate of Compliance AFC09 ... AFC38 3-pole contactors
Package Level 1 Units
box 1 piece
Package Level 1 Width
87 mm
Package Level 1 Depth / Length
87 mm
Package Level 1 Height
47 mm
Package Level 1 Gross Weight
0.383 kg
Package Level 1 EAN
3471523014657
Package Level 3 Units
1008 piece
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4755 >> Contactors
The 1SBL231001R8100 expands motor control capabilities with a compact, modular design suitable for panel builders and machine integrators. Feature → Business Impact → Application: 24 V coil control minimizes control side power draw and simplifies integration with existing PLCs, reducing energy waste and heat in control cabinets; this translates to lower operating costs and improved panel reliability in high-cycle environments. The 3P main contacts (NO) with 690 V rated insulation supports AC-3 power switching for motors up to 11 kW at 400 V or 15 kW at higher voltages, enabling straightforward modernization of legacy drives. Mounting on TH35-15 DIN rails and screw-terminal connections streamline installation and field servicing, reducing commissioning time and field wiring errors. With IP20 protection, incremental accessory options (auxiliary contact blocks and CA4, CAL4, CAT4, CC4, LDC4 etc.) broaden compatibility for complex automation schemes. Coil consumption and mechanical life are optimized for reliable, repeatable operation across typical industrial temperature ranges (-25 to 60 C with suitable ambient conditions).
Get a Quick Quote for a ABB 1SBL231001R8100
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SBL231001R8100?
Enquire Now
FAQs
Mounting uses TH35-15 rails for a secure 35x15 mm profile, or TH35-7.5 where space is constrained. The unit uses screw terminals for main and control circuits, and wire stripping length is 14 mm for main and 10 mm for the control circuit, simplifying termination and reducing wiring errors during installation.
Rated Operational Current AC-3 varies by voltage: 26 A at 380/400/440 V, and 17 A at 690 V (all at 60 °C). This enables reliable motor switching up to 15 kW at higher voltages and 11 kW at 415 V, with suitable derating applicable at elevated temperatures.
Yes. With 3P NO contacts, 690 V insulation rating, IP20 protection, and a compact DIN-rail footprint, the 1SBL231001R8100 is well-suited for conveyor drives, pumps, and similar motor control tasks in standard industrial panels, provided ambient conditions stay within specified temperature and altitude limits.
It complies with IEC/EN 60947-1 and 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, and CE declarations. Additional declarations cover RoHS, REACH, CMRT, WEEE B2B, and UL/CSA safety labeling for global product usage.
Absolutely. The AFC/AF platform allows add-on auxiliary contact blocks and a wide range of accessories (CA4, CAL4, CAT4, CC4, LDC4, etc.), enabling scalable automation without replacing the base unit. The low coil power loss and compact footprint reduce energy consumption and cabinet space, delivering a favorable total cost of ownership over typical installation lifecycles.