Quick Summary
The 1SBL236260R2300 Block Contactor provides reliable motor control for industrial machines and rolling stock systems. Users often face voltage fluctuations and energy waste in control panels, which can compromise startup reliability and uptime. This device meets IEC/EN 60947-4-1, UL 60947-4-1, and CSA 60947-4-1 standards, with CE and UKCA declarations supporting global deployments. With AF technology, a wide control voltage range of 100–250 V and built-in surge protection, it reduces panel energy consumption while stabilizing operation even in unstable networks. In addition to its 4P configuration, its compact form factor and modular add-on options support scalable control architecture and easy maintenance across diverse industrial environments.
Product Information
Extended Description
1SBL236260R2300 ABB: The AF26ZB-40-00RT-23 is a 4 pole - 690 V IEC or 600 UL contactor with Ring-Tongue Terminals, controlling motors up to 11 kW / 400 V AC (AC-3) and switching power circuits up to 45 A (AC-1) or 45 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
Motor control and protection for Rolling stock application_PDF
Instructions and Manuals
Installation instructions AF09...38(Z)B-..RT Contactors, NF(Z)B..ERT Contactor relays and CA4..RT, CAL4..RT, CAT4..RT, LDC4RT Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
45 mm
Product Net Depth / Length
101 mm
Product Net Height
86 mm
Product Net Weight
0.39 kg
Number of Main Contacts NO
4
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Number of Poles
4P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives.
Rated Operational Voltage
Main Circuit 690 V
Rated Frequency (f)
Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 55 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 45 A | (690 V) 60 °C 40 A | (690 V) 70 °C 32 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 21.2 A | (440 V) 60 °C 20 A | (500 V) 60 °C 17.6 A | (690 V) 60 °C 10.5 A | (380 / 400 V) 60 °C 22 A | (220 / 230 / 240 V) 60 °C 23.2 A
Rated Operational Current DC-1 (Ie)
(110 V) 2 Poles in Series, 40 °C 45 A | (110 V) 2 Poles in Series, 60 °C 40 A | (110 V) 2 Poles in Series, 70 °C 32 A | (110 V) 3 Poles in Series, 40 °C 45 A | (110 V) 3 Poles in Series, 60 °C 40 A | (110 V) 3 Poles in Series, 70 °C 32 A | (110 V) 4 Poles in Series, 40 °C 45 A | (110 V) 4 Poles in Series, 60 °C 40 A | (110 V) 4 Poles in Series, 70 °C 32 A | (220 V) 3 Poles in Series, 40 °C 45 A | (220 V) 3 Poles in Series, 60 °C 40 A | (220 V) 3 Poles in Series, 70 °C 32 A | (220 V) 4 Poles in Series, 40 °C 45 A | (220 V) 4 Poles in Series, 60 °C 40 A | (220 V) 4 Poles in Series, 70 °C 32 A | (72 V) 1-Pole, 40 °C 45 A | (72 V) 1-Pole, 60 °C 40 A | (72 V) 1-Pole, 70 °C 32 A | (72 V) 2 Poles in Series, 40 °C 45 A | (72 V) 2 Poles in Series, 60 °C 40 A | (72 V) 2 Poles in Series, 70 °C 32 A | (72 V) 3 Poles in Series, 40 °C 45 A | (72 V) 3 Poles in Series, 60 °C 40 A | (72 V) 3 Poles in Series, 70 °C 32 A | (72 V) 4 Poles in Series, 40 °C 45 A | (72 V) 4 Poles in Series, 60 °C 40 A | (72 V) 4 Poles in Series, 70 °C 32 A
Rated Operational Power AC-3 (Pe)
(400 V) 11 kW | (415 V) 11 kW | (440 V) 11 kW | (500 V) 11 kW | (690 V) 9 kW | (220 / 230 / 240 V) 5.5 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 300 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 55 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 150 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 450 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 225 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 100 ... 250 V | 60 Hz 100 ... 250 V | DC Operation 100 ... 250 V
Power Loss
at Rated Operating Conditions AC-1 per Pole 1.6 W | at Rated Operating Conditions AC-3 per Pole 0.42 W
Operate Time
Between Coil De-energization and NC Contact Closing 13 ... 98 ms | Between Coil De-energization and NO Contact Opening 11 ... 95 ms | Between Coil Energization and NC Contact Opening 38 ... 90 ms | Between Coil Energization and NO Contact Closing 40 ... 95 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 screws placed diagonally
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP10 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Tightening Torque
Control Circuit 1.2 N·m | Main Circuit 2.5 N·m
Terminal Type
Ring-Tongue Terminals
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 45 A
Tightening Torque UL/CSA
Control Circuit 11 in·lb | Main Circuit 22 in·lb
Ambient Air Temperature
Close to Contactor for Storage -60 ... +80 °C | Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Shock and Vibration Withstand acc. to IEC 61373
Category 1, Class B
Pollution Degree
3
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
End Of Life Disassembling Instructions
End of life instruction AF(S)09/12/16/26/30/38(Z)(B)(K)(RT) Contactors & NF(Z)(B)(K)(RT) Contactors relays
Environmental Product Declaration - EPD
Environmental Product Declaration AF(S)26/30/38(Z)(B) Contactors (FR)
Sustainable Material Content in Packaging (wt. %)
Recycled Cardboard - 86 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 28 %
CB Certificate
CB Certificate AF26, AF38, AF26(Z)B, AF38(Z)B 4-pole contactors
CCC Certificate
CCC Certificate AF26, AF30, AF38, AF26(Z)B, AF30(Z)B, AF38(Z)B 3 and 4-pole contactors, AFS26, AFS30, AFS38 safety contactors
CQC Certificate
CQC Certificate, Contactor, AF*26, AF*30, AF*38, Made in France
Declaration of Conformity - CCC
CCC Declaration of Conformity, Contactor, AF26, AF30, AF38, AFS26, AFS30, AFS38 Made in France
Declaration of Conformity - CE
EU Declaration of Conformity AF09 to AF38(Z)B..RT 3 and 4-pole contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09 to AF38(Z)B..RT 3 and 4-pole contactors
UL Listing Card
UL_E319322
UR Certificate
UR Certificate of Compliance AF09...AF38(Z)B-..RT 4-pole contactors with ring tongue terminals
Package Level 1 Units
box 1 piece
Package Level 1 Width
87 mm
Package Level 1 Depth / Length
103 mm
Package Level 1 Height
47 mm
Package Level 1 Gross Weight
0.39 kg
Package Level 1 EAN
3471523129634
Package Level 2 Units
box 18 piece
Package Level 2 Width
250 mm
Package Level 2 Depth / Length
300 mm
Package Level 2 Height
315 mm
Package Level 2 Gross Weight
14.04 kg
Package Level 3 Units
864 piece
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
Feature: The device provides a 4-pole, 690 V main circuit with AC-3 rating up to 11 kW. Business Impact: This enables reliable switching of energy‑intensive motors with limited voltage sag and short-circuit tolerance, improving uptime. Application: Ideal for conveyors, pumps, and machine tools in harsh industrial environments. Feature: AF technology delivers a wide control voltage range of 100–250 V and built-in surge protection. Business Impact: Reduces nuisance trips and energy waste in panels with fluctuating supply, stabilizing operation. Application: Works across mixed voltage installations and remote control schemes. Feature: Four normally open main contacts (NO) in a 4P arrangement. Business Impact: Ensures predictable current path and straightforward wiring for standard motor starter configurations. Application: Suitable for motor control in OEM machinery and line equipment. Feature: Compact footprint of 45 mm width, 101 mm depth, and 86 mm height, weight 0.39 kg, with DIN rail mounting TH35‑15 or TH35‑7.5. Business Impact: Saves cabinet space and simplifies panel design, reducing installation time and enclosure costs. Application: Perfect for compact control panels and modular automation rooms. Feature: Block-type design supports add-on auxiliary contact blocks and a broad range of accessories. Business Impact: Enables scalable control logic without replacing the base device, lowering lifecycle costs. Application: Fast expansion in growing automation lines and adaptable machine controllers. Feature: Built-in safety and compliance features including IP10 coil and main terminals, plus CE/UKCA, UL/CSA listings. Business Impact: Lowers risk of regulatory non-compliance and simplifies global procurement. Application: Global deployments across automotive, rail, and process industries.
Get a Quick Quote for a ABB 1SBL236260R2300
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SBL236260R2300?
Enquire Now
FAQs
The 1SBL236260R2300 is designed for DIN rail mounting on TH35‑15 or TH35‑7.5 rails. Use 2 x M4 screws (not supplied) to secure the device, and ensure proper alignment for coil terminals. Verify the coil voltage (100–250 V AC/DC) matches your control circuit and torque the terminals per the data sheet to maintain secure connections and long-term reliability.
Key ratings include 4-pole, main circuit rated up to 690 V with AC-3 current ratings up to 21.2–23.2 A depending on voltage, 11 kW maximum operating power at 400–690 V, and control circuit voltage of 100–250 V (AC, 50/60 Hz or DC). It also features a rated short-time withstand current and a 6 kV impulse withstand voltage for robust protection.
Yes. The AF technology supports a wide control voltage range of 100–250 V (AC/DC) for stable operation under supply variation, and the unit includes built‑in surge protection. This combination reduces nuisance trips, improves reliability, and simplifies panel design in variable networks and rolling stock applications.
The device complies with IEC/EN 60947‑1 and IEC/EN 60947‑4‑1, UL 60947‑4‑1, and CSA C22.2 No. 60947‑4‑1. It also carries CE/UKCA declarations, and related ABB declarations for RoHS, REACH, and environmental considerations to support global deployments.
ROI benefits stem from energy efficiency via AF control, reduced energy consumption in control panels, and easier maintenance due to modular add‑ons and a compact footprint. Space savings, streamlining of spare parts, and quicker expansion with accessories all contribute to lower total cost of ownership in automation projects.