ABB AF26ZB-22-00RT-23 Contactor - 4P, 690V, Ring-Tongue Terminals, UL/IEC Listed

Part Number: 1SBL236560R2300
Manufacturer
ABB
Part number
1SBL236560R2300

Quick Summary

AF26ZB-22-00RT-23 Contactor is a 4-pole motor control device for industrial equipment. In demanding environments, voltage fluctuations and panel energy waste threaten uptime, but this unit addresses them with a wide control voltage range and robust design. It carries CE, UKCA, and UL/CSA markings and complies with IEC/EN 60947-4-1, UL 60947-4-1, ensuring global applicability. Coupled with AF technology and compatibility with add-on auxiliary contact blocks, it enables scalable, space-efficient panels and lower total cost of ownership for rolling stock applications and general industrial automation.

Product Information

Extended Description

1SBL236560R2300 ABB: The AF26ZB-22-00RT-23 is a 4 pole - 690 V IEC or 600 UL contactor with Ring-Tongue Terminals, controlling motors up to 11 kW / 400 V AC (AC-3) and switching power circuits up to 45 A (AC-1) or 45 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
Motor control and protection for Rolling stock application_PDF
Instructions and Manuals
Installation instructions AF09...38(Z)B-..RT Contactors, NF(Z)B..ERT Contactor relays and CA4..RT, CAL4..RT, CAT4..RT, LDC4RT Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
45 mm
Product Net Depth / Length
101 mm
Product Net Height
86 mm
Product Net Weight
0.39 kg
Number of Main Contacts NO
2
Number of Main Contacts NC
2
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Number of Poles
4P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives.
Rated Operational Voltage
Main Circuit 690 V
Rated Frequency (f)
Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 55 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 45 A | (690 V) 60 °C 40 A | (690 V) 70 °C 32 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 21.2 A | (440 V) 60 °C 20 A | (500 V) 60 °C 17.6 A | (690 V) 60 °C 10.5 A | (380 / 400 V) 60 °C 22 A | (220 / 230 / 240 V) 60 °C 23.2 A
Rated Operational Power AC-3 (Pe)
(400 V) 11 kW | (415 V) 11 kW | (440 V) 11 kW | (500 V) 11 kW | (690 V) 9 kW | (220 / 230 / 240 V) 5.5 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 300 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 55 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 150 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 450 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 225 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 100 ... 250 V | 60 Hz 100 ... 250 V | DC Operation 100 ... 250 V
Power Loss
at Rated Operating Conditions AC-1 per Pole 1.6 W | at Rated Operating Conditions AC-3 per Pole 0.42 W
Operate Time
Between Coil De-energization and NC Contact Closing 13 ... 98 ms | Between Coil De-energization and NO Contact Opening 11 ... 95 ms | Between Coil Energization and NC Contact Opening 38 ... 90 ms | Between Coil Energization and NO Contact Closing 40 ... 95 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 screws placed diagonally
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP10 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Tightening Torque
Control Circuit 1.2 N·m | Main Circuit 2.5 N·m
Terminal Type
Ring-Tongue Terminals
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 45 A
Tightening Torque UL/CSA
Control Circuit 11 in·lb | Main Circuit 22 in·lb
Ambient Air Temperature
Close to Contactor for Storage -60 ... +80 °C | Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Shock and Vibration Withstand acc. to IEC 61373
Category 1, Class B
Pollution Degree
3
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
End Of Life Disassembling Instructions
End of life instruction AF(S)09/12/16/26/30/38(Z)(B)(K)(RT) Contactors & NF(Z)(B)(K)(RT) Contactors relays
Environmental Product Declaration - EPD
Environmental Product Declaration AF(S)26/30/38(Z)(B) Contactors (FR)
Sustainable Material Content in Packaging (wt. %)
Recycled Cardboard - 86 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 28 %
CB Certificate
CB Certificate AF26, AF38, AF26(Z)B, AF38(Z)B 4-pole contactors
CCC Certificate
CCC Certificate AF26, AF30, AF38, AF26(Z)B, AF30(Z)B, AF38(Z)B 3 and 4-pole contactors, AFS26, AFS30, AFS38 safety contactors
CQC Certificate
CQC Certificate, Contactor, AF*26, AF*30, AF*38, Made in France
Declaration of Conformity - CCC
CCC Declaration of Conformity, Contactor, AF26, AF30, AF38, AFS26, AFS30, AFS38 Made in France
Declaration of Conformity - CE
EU Declaration of Conformity AF09 to AF38(Z)B..RT 3 and 4-pole contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09 to AF38(Z)B..RT 3 and 4-pole contactors
UL Listing Card
UL_E319322
UR Certificate
UR Certificate of Compliance AF09...AF38(Z)B-..RT 4-pole contactors with ring tongue terminals
Package Level 1 Units
box 1 piece
Package Level 1 Width
87 mm
Package Level 1 Depth / Length
103 mm
Package Level 1 Height
47 mm
Package Level 1 Gross Weight
0.39 kg
Package Level 1 EAN
3471523129931
Package Level 2 Units
box 18 piece
Package Level 2 Width
250 mm
Package Level 2 Depth / Length
300 mm
Package Level 2 Height
315 mm
Package Level 2 Gross Weight
14.04 kg
Package Level 3 Units
864 piece
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
Feature: Four-pole block contactor with two normally open and two normally closed main contacts. Business Impact: Delivers reliable start-stop control for motors up to 11 kW and power circuits up to 45 A, reducing wiring complexity and mounting footprint. Application: Ideal for rolling stock motor control and general industrial machinery where compact, robust switching is required. Feature: Wide control circuit voltage range (100-250 V AC, 50/60 Hz, or DC). Business Impact: Tolerates voltage variations without nuisance tripping, improving system uptime and energy efficiency. Application: Great for panels with fluctuating supply or mixed control sources. Feature: Built-in surge protection. Business Impact: Protects contactors and downstream electronics from voltage spikes, lowering maintenance costs and downtime. Application: Beneficial in harsh electrical environments typical of manufacturing floors. Feature: Ring-Tongue terminals for main and control wiring. Business Impact: Ensures secure, repeatable terminations with straightforward field wiring, speeding installation. Application: Useful in retrofit projects and new builds where wiring reliability matters. Feature: DIN rail mounting options TH35-15 or TH35-7.5 and compact footprint. Business Impact: Simplifies panel integration, reduces enclosure space, and speeds installation with standard rails. Application: Suits modern control panels and enclosures. Feature: Compliance and broad accessory ecosystem. Business Impact: Enables compliance across regions (CE, UKCA, UL/CSA) and easy expansion via add-on auxiliary contact blocks and accessories. Application: Supports scalable control architectures in automation and traction systems.

Get a Quick Quote for a ABB 1SBL236560R2300

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SBL236560R2300? Enquire Now

FAQs

Installation is straightforward on TH35-15 or TH35-7.5 DIN rails. The unit uses 2 x M4 screws for panel mounting and must be secured to the DIN rail. The compact 45 mm width, 101 mm depth, and 86 mm height facilitate tight panel layouts. Ensure correct orientation so main terminals and coil terminals are accessible for wiring and maintenance.
Rated Operational Current AC-1 (690 V): 45 A at 40°C, 40 A at 60°C, 32 A at 70°C. Rated Operational Current AC-3 (varying voltages): 21.2 A at 415 V, 20 A at 440 V, 17.6 A at 500 V, 10.5 A at 690 V, 22 A at 380/400 V, 23.2 A at 220/230/240 V. Rated Power AC-3: up to 11 kW at several voltages (e.g., 400–690 V). These figures support reliable motor control in industrial drives.
The contactor accepts 100-250 V control voltage at 50/60 Hz or DC operation. It includes built-in surge protection to guard against voltage transients, reducing coil and circuit wear. This makes it suitable for networks with fluctuating supply and helps maintain consistent operation without external protection components.
The device carries CE and UKCA markings, along with UL/CSA listings, signaling compliance with EU, UK, and North American safety standards. These certifications support regulatory approvals for global deployment, reduce compliance risk in multi-site projects, and simplify supplier qualification for automotive, rail, and general industrial automation programs.
Product net width is 45 mm, depth 101 mm, height 86 mm, and weight 0.39 kg, enabling a compact footprint. It supports Ring-Tongue terminations and screw terminals (not supplied). The device is designed to be compatible with add-on auxiliary contact blocks for extended signaling and control, and with standard DIN rail accessories for streamlined retrofits and future expansions.