ABB AF30ZB-30-00RT-22 Contactor - AF tech with surge

Part Number: 1SBL276060R2200
Manufacturer
ABB
Part number
1SBL276060R2200

Quick Summary

ABB AF30ZB-30-00RT-22 Contactor controls 690 V motors in industrial automation. In real-world lines, voltage fluctuations trigger trips and wasted energy. It supports a wide control voltage from 48 to 130 V, AC/DC, with built-in surge protection. Certified under IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 and EN 50155, it's ready for rolling stock and general use. This combination reduces panel energy, enables modular expansion, and streamlines maintenance for your plant. Its DIN rail mounting and accessory ecosystem minimize installation time. Three NO main contacts and built‑in surge protection simplify design and improve reliability. Compact size fits 45 mm width and 86 mm depth, enabling scalable panel architectures and straightforward retrofits.

Product Information

Extended Description

1SBL276060R2200 ABB: The AF30ZB-30-00RT-22 is a 3 pole - 690 V IEC or 600 UL contactor with Ring-Tongue Terminals, controlling motors up to 15 kW / 400 V AC (AC-3) or 20 hp / 480 V UL and switching power circuits up to 50 A (AC-1) or 50 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (48-130 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
Motor control and protection for Rolling stock application_PDF
Instructions and Manuals
Installation instructions AF09...38(Z)B-..RT Contactors, NF(Z)B..ERT Contactor relays and CA4..RT, CAL4..RT, CAT4..RT, LDC4RT Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
45 mm
Product Net Depth / Length
86 mm
Product Net Height
86 mm
Product Net Weight
0.36 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Number of Poles
3P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives.
Rated Operational Voltage
Main Circuit 690 V
Rated Frequency (f)
Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 50 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 50 A | (690 V) 60 °C 42 A | (690 V) 70 °C 37 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 32 A | (440 V) 60 °C 32 A | (500 V) 60 °C 28 A | (690 V) 60 °C 21 A | (380 / 400 V) 60 °C 32 A | (220 / 230 / 240 V) 60 °C 33 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 32 A | (440 V) 60 °C 32 A | (500 V) 60 °C 28 A | (690 V) 60 °C 21 A | (380 / 400 V) 60 °C 32 A | (220 / 230 / 240 V) 60 °C 33 A
Rated Operational Current DC-1 (Ie)
(110 V) 2 Poles in Series, 40 °C 50 A | (110 V) 2 Poles in Series, 60 °C 42 A | (110 V) 2 Poles in Series, 70 °C 37 A | (110 V) 3 Poles in Series, 40 °C 50 A | (110 V) 3 Poles in Series, 60 °C 42 A | (110 V) 3 Poles in Series, 70 °C 37 A | (220 V) 3 Poles in Series, 40 °C 50 A | (220 V) 3 Poles in Series, 60 °C 42 A | (220 V) 3 Poles in Series, 70 °C 37 A | (72 V) 1-Pole, 40 °C 50 A | (72 V) 1-Pole, 60 °C 42 A | (72 V) 1-Pole, 70 °C 37 A | (72 V) 2 Poles in Series, 40 °C 50 A | (72 V) 2 Poles in Series, 60 °C 42 A | (72 V) 2 Poles in Series, 70 °C 37 A | (72 V) 3 Poles in Series, 40 °C 50 A | (72 V) 3 Poles in Series, 60 °C 42 A | (72 V) 3 Poles in Series, 70 °C 37 A
Rated Operational Current DC-3 (Ie)
(110 V) 2 Poles in Series, 40 °C 50 A | (110 V) 2 Poles in Series, 60 °C 42 A | (110 V) 2 Poles in Series, 70 °C 37 A | (110 V) 3 Poles in Series, 40 °C 50 A | (110 V) 3 Poles in Series, 60 °C 42 A | (110 V) 3 Poles in Series, 70 °C 37 A | (220 V) 3 Poles in Series, 40 °C 50 A | (220 V) 3 Poles in Series, 60 °C 42 A | (220 V) 3 Poles in Series, 70 °C 37 A | (72 V) 1-Pole, 40 °C 50 A | (72 V) 1-Pole, 60 °C 42 A | (72 V) 1-Pole, 70 °C 37 A | (72 V) 2 Poles in Series, 40 °C 50 A | (72 V) 2 Poles in Series, 60 °C 42 A | (72 V) 2 Poles in Series, 70 °C 37 A | (72 V) 3 Poles in Series, 40 °C 50 A | (72 V) 3 Poles in Series, 60 °C 42 A | (72 V) 3 Poles in Series, 70 °C 37 A
Rated Operational Current DC-5 (Ie)
(110 V) 2 Poles in Series, 40 °C 50 A | (110 V) 2 Poles in Series, 60 °C 42 A | (110 V) 2 Poles in Series, 70 °C 37 A | (110 V) 3 Poles in Series, 40 °C 50 A | (110 V) 3 Poles in Series, 60 °C 42 A | (110 V) 3 Poles in Series, 70 °C 37 A | (220 V) 3 Poles in Series, 40 °C 25 A | (220 V) 3 Poles in Series, 60 °C 25 A | (220 V) 3 Poles in Series, 70 °C 25 A | (72 V) 1-Pole, 40 °C 25 A | (72 V) 1-Pole, 60 °C 25 A | (72 V) 1-Pole, 70 °C 25 A | (72 V) 2 Poles in Series, 40 °C 50 A | (72 V) 2 Poles in Series, 60 °C 42 A | (72 V) 2 Poles in Series, 70 °C 37 A | (72 V) 3 Poles in Series, 40 °C 50 A | (72 V) 3 Poles in Series, 60 °C 42 A | (72 V) 3 Poles in Series, 70 °C 37 A
Rated Operational Power AC-3 (Pe)
(415 V) 15 kW | (440 V) 18.5 kW | (500 V) 18.5 kW | (690 V) 18.5 kW | (380 / 400 V) 15 kW | (220 / 230 / 240 V) 9 kW
Rated Operational Power AC-3e (Pe)
(415 V) 15 kW | (440 V) 18.5 kW | (500 V) 18.5 kW | (690 V) 18.5 kW | (380 / 400 V) 15 kW | (220 / 230 / 240 V) 9 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 350 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 50 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 150 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 700 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 225 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 500 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 200 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-2 / AC-4) 150 cycles per hour | (AC-3) 1200 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 48 ... 130 V | 60 Hz 48 ... 130 V | DC Operation 48 ... 130 V
Power Loss
at Rated Operating Conditions AC-1 per Pole 2.4 W | at Rated Operating Conditions AC-3 per Pole 0.9 W
Operate Time
Between Coil De-energization and NC Contact Closing 13 ... 98 ms | Between Coil De-energization and NO Contact Opening 11 ... 95 ms | Between Coil Energization and NC Contact Opening 38 ... 90 ms | Between Coil Energization and NO Contact Closing 40 ... 95 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 screws placed diagonally
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP10 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Tightening Torque
Control Circuit 1.2 N·m | Main Circuit 2.5 N·m
Terminal Type
Ring-Tongue Terminals
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 50 A
Horsepower Rating UL/CSA
(120 V AC) Single Phase 2 hp | (200 ... 208 V AC) Three Phase 10 hp | (220 ... 240 V AC) Three Phase 10 hp | (240 V AC) Single Phase 5 hp | (440 ... 480 V AC) Three Phase 20 hp | (550 ... 600 V AC) Three Phase 25 hp
Tightening Torque UL/CSA
Control Circuit 11 in·lb | Main Circuit 22 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 24 A | (200 ... 208 V AC) Three Phase 32.2 A | (220 ... 240 V AC) Three Phase 28 A | (240 V AC) Single Phase 28 A | (440 ... 480 V AC) Three Phase 27 A | (550 ... 600 V AC) Three Phase 27 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -25 ... 60 °C | Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C
Climatic Withstand
acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
Maximum Operating Altitude Permissible
Without Derating 3000 m
Shock and Vibration Withstand acc. to IEC 61373
Category 1, Class B
Pollution Degree
3
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
54fad34d-52fb-4f78-b790-33a03c8600d8 China (CN)
Simplified SCIP
30d8ecf0-3050-4756-a69c-feb2deaf7831 Greece (GR) | a97f4eac-1274-4e5e-a8f0-7ddd614fba4a Estonia (EE) | 42507a2b-d40b-4cf1-b393-c3f62f6f936c Netherlands (NL) | cff74160-89d9-47c3-b663-27fa2fe6acfe Poland (PL) | b8b32315-ed50-45e9-9d8d-42a472b37d38 Hungary (HU) | 1c3da7c6-4c12-471b-9f67-9e0875f17ccf Croatia (HR) | dd837d12-3408-41c7-b56a-e4c75c9d913f Germany (DE) | 057792d0-9483-4a01-b321-721a3e198ede Germany (DE) | 827a938d-f1c2-4aa5-a05c-29dd5dedc573 Denmark (DK) | 023b6ffd-a9ab-49c9-a868-7e30dda8b706 Belgium (BE) | 7841c9d2-6cc7-4e5a-954d-c8435240fdec Poland (PL) | 123f961e-1aea-4ac0-9617-eda9cdb221d5 France (FR) | 5bbb4d43-9ef3-4ac2-bd61-26f966239a03 Germany (DE) | 0ba5520d-ec37-4a39-b235-767cd8b78044 Portugal (PT) | 769add60-4556-4c58-9162-70054cbb64d7 Sweden (SE) | 26ad645a-9868-47be-8086-e83b1747a829 Bulgaria (BG) | 935be18d-610a-4f5e-ab5a-f892e439c2d6 Belgium (BE) | 60b85abe-be8f-47e7-aaed-c9f1147e3608 Hungary (HU) | d7eb9608-c71e-436c-b0ae-ab0d7770973a Germany (DE) | 8e30ddd1-285a-48f0-9fae-579737548fb4 France (FR) | 6514abd3-0842-4e8e-89fb-f3720954ef21 Sweden (SE) | 79c11f80-57fc-4d3d-8eb4-b848b733aad1 Finland (FI) | b0f0b4a0-b73f-44ec-88b2-d14b51e5aaf2 Norway (NO) | 29160330-81a3-4756-8e63-2d0017fcdc1a Poland (PL) | e64d5989-bde1-48bb-933c-67c703adcae6 Czech Republic (CZ) | ef244c4d-0a21-48dc-bec7-5028d995b794 Spain (ES) | a283f804-6a68-49a7-b12f-d619b6d0eabe Germany (DE)
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
End Of Life Disassembling Instructions
End of life instruction AF(S)09/12/16/26/30/38(Z)(B)(K)(RT) Contactors & NF(Z)(B)(K)(RT) Contactors relays
Environmental Product Declaration - EPD
Environmental Product Declaration AF(S)26/30/38(Z)(B) Contactors (FR) | Environmental Product Declaration AF26/30/38(Z)(B) Contactors (CN)
Sustainable Material Content in Packaging (wt. %)
Recycled Cardboard - 86 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 28 %
CB Certificate
CB Certificate AF26(Z)(B), AF30(Z)(B), AF(Z)(B)38 3-pole contactors, AFS26, AFS30, AFS38 safety contactors
CCC Certificate
CCC Certificate AF26, AF30, AF38, AF26(Z)B, AF30(Z)B, AF38(Z)B 3 and 4-pole contactors, AFS26, AFS30, AFS38 safety contactors
CQC Certificate
CQC Certificate, Contactor, AF*26, AF*30, AF*38, Made in France
Declaration of Conformity - CCC
CCC Declaration of Conformity, Contactor, AF26, AF30, AF38, AFS26, AFS30, AFS38 Made in France
Declaration of Conformity - CE
EU Declaration of Conformity AF09 to AF38(Z)B..RT 3 and 4-pole contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09 to AF38(Z)B..RT 3 and 4-pole contactors
UL Listing Card
UL_E312527
UR Certificate
UR Certificate of Compliance AF09...AF38(Z)B..RT 3-pole contactors with ring tongue terminals
Package Level 1 Units
box 1 piece
Package Level 1 Width
87 mm
Package Level 1 Depth / Length
87 mm
Package Level 1 Height
47 mm
Package Level 1 Gross Weight
0.36 kg
Package Level 1 EAN
3471523128828
Package Level 2 Units
box 21 piece
Package Level 2 Width
250 mm
Package Level 2 Depth / Length
300 mm
Package Level 2 Height
315 mm
Package Level 2 Gross Weight
16.2 kg
Package Level 3 Units
1080 piece
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
Feature: Wide control voltage tolerance of 48-130 V AC, 50/60 Hz and DC. Business impact: Reduces nuisance trips and energy waste caused by voltage variation, improving uptime. Application: Industrial conveyors and packaging lines operating in grids with fluctuations. Feature: AF technology with a robust block design and extendable auxiliary blocks. Business impact: Modular scalability lowers spare parts and enables fast expansion as plant needs grow. Application: Control panels that evolve with line productivity. Feature: Rated main current and power for AC-3/AC-3e at 690 V, with 32 A at 60 °C and 21 A at 60 °C for higher load variants. Business impact: Clear sizing reduces overdesign and improves motor efficiency. Application: HVAC, pumps, and large-motor drives. Feature: Built-in surge protection. Business impact: Protects contactors and downstream electronics, reducing maintenance costs. Application: Harsh electrical environments and rolling stock. Feature: DIN rail mounting support (TH35-15 or TH35-7.5) and compatibility with add-on contact blocks. Business impact: Quick installation, simplified retrofits, and minimal panel rework. Application: Control cabinets and retrofits in existing lines. Feature: Compliance with IEC/EN 60947-1, 60947-4-1, UL/CSA, EN 50155. Business impact: Streamlined regulatory approvals and safer global deployment. Application: Global manufacturing and railway projects.

Get a Quick Quote for a ABB 1SBL276060R2200

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SBL276060R2200? Enquire Now

FAQs

The AF30ZB-30-00RT-22 is a 3-pole contactor designed to switch 690 V motors in industrial automation. It supports a wide control voltage range (48–130 V AC/DC) and includes built‑in surge protection, making it suitable for applications requiring robust performance in fluctuating power conditions, such as conveyors, pumps, and rolling stock control panels.
Yes. The device supports DIN rail mounting (TH35-15 and TH35-7.5) and can be easily extended with auxiliary contact blocks, which simplifies panel wiring, reduces installation time, and enables scalable control architectures in evolving automation projects.
For AC-3 at 690 V, the device provides up to 21 A (60 °C) and up to 32 A at other voltages as listed, with AC-1 ratings around 50 A at 690 V, depending on ambient temperature. These ratings help guide safe motor starting and continuous operation for standard industrial motors.
The product carries IEC/EN 60947-1 and 60947-4-1 compatibility, UL 60947-4-1 and CSA C22.2 listings, EN 50155 applicability for rolling stock, and related DoC/CE/UKCA documentation, ensuring broad regulatory acceptance and safe integration in global plants.
The AF30ZB-30-00RT-22 offers reduced energy waste due to wide control voltage tolerance, modular expandability with add-on blocks, and lower maintenance thanks to built‑in surge protection. In retrofit projects, these features translate to faster commissioning, fewer spare parts, and improved uptime, delivering a favorable total cost of ownership.