ABB 1SBL291501R8400 Block Contactor - 690V UL/CE

Part Number: 1SBL291501R8400
Manufacturer
ABB
Part number
1SBL291501R8400

Quick Summary

Block Contactor ABB 1SBL291501R8400 provides reliable AC switching for motor and power circuits in industrial automation. Engineers often face coil compatibility, panel space, and mounting complexity when upgrading power control in compact enclosures. This device carries CE and UKCA markings, plus UL/CSA listings and BV certificate for global compliance in demanding environments. With DIN rail mounting options, screw terminals, and a compact 4-pole design, it minimizes panel footprint while accelerating installation and service. Coupled with 50/60 Hz control voltage and 690 V main circuit ratings, it enables safer, more efficient control of motors and conveyors, reducing downtime and maintenance costs.

Product Information

Extended Description

1SBL291501R8400 ABB: The AFC38-22-00-84 is a 4-pole (2 N.O + 2 N.C) - 690 V IEC or 600 V UL contactor withScrew terminals, mainly controlling power circuits up to 55 A (IEC AC-1) or 55 A UL general use. Within the AF platform, AFC contactors offer an optimized operating time for AC controlled applications with electromagnetic coil (control voltage : 110 V AC 50 Hz / 110 ... 120 V AC 60 Hz). AFC contactors have a block type design and can be easily extended with add-on auxiliary contact blocks and a wide range of additionnal accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
1SBC100219C0201 AFC contactors for AC control applications_Catalog PDF
Instructions and Manuals
Installation instructions AF(C)09...38(Z)(B) Contactors, NF(C)(Z)(B)22...80E Contactor relays and CA4, CAL4, CAT4, CC4, LDC4 Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
45 mm
Product Net Depth / Length
101 mm
Product Net Height
86 mm
Product Net Weight
0.399 kg
Number of Main Contacts NO
2
Number of Main Contacts NC
2
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Number of Poles
4P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-1, UL 60947-4-1, CAN/CSA C22.2 No.60947-1, CAN/CSA C22.2 No.60947-4-1
Rated Operational Voltage
Main Circuit 690 V
Rated Frequency (f)
Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 55 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 55 A | (690 V) 60 °C 45 A | (690 V) 70 °C 37 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 21.2 A | (440 V) 60 °C 20 A | (500 V) 60 °C 17.6 A | (690 V) 60 °C 10.5 A | (380 / 400 V) 60 °C 22 A | (220 / 230 / 240 V) 60 °C 23.2 A
Rated Operational Power AC-3 (Pe)
(415 V) 11 kW | (440 V) 11 kW | (500 V) 11 kW | (690 V) 9 kW | (220 / 230 / 240 V) 5.5 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 300 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 55 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 150 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 450 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 225 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-15) 0 cycles per hour | (AC-2 / AC-4) 0 cycles per hour | (AC-3) 0 cycles per hour | (DC-13) 0 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 110 V | 60 Hz 110 ... 120 V
Coil Consumption
Average Holding Value 50 / 60 Hz 8 V·A | Average Pull-in Value 50 Hz 70 V·A | Average Pull-in Value 60 Hz 66 V·A
Power Loss
at Rated Operating Conditions AC-1 per Pole 2.3 W | at Rated Operating Conditions AC-3 per Pole 0.42 W
Operate Time
Between Coil De-energization and NC Contact Closing 9 ... 20 ms | Between Coil De-energization and NO Contact Opening 4 ... 18 ms | Between Coil Energization and NC Contact Opening 7 ... 21 ms | Between Coil Energization and NO Contact Closing 10 ... 26 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 1.5 ... 16 mm² | Flexible with Insulated Ferrule 1/2x 1.5 ... 16 mm² | Rigid Solid 1/2x 1.5 ... 4 mm² | Rigid Stranded 1/2x 1.5 ... 16 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Control Circuit 10 mm | Main Circuit 12 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Tightening Torque
Control Circuit 1.2 N·m | Main Circuit 2.5 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 55 A
Connecting Capacity Main Circuit UL/CSA
Rigid Solid 1/2x 16-10 AWG | Rigid Stranded 1/2x 16-6 AWG
Connecting Capacity Control Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG | Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSA
Control Circuit 11 in·lb | Main Circuit 22 in·lb
Ambient Air Temperature
Close to Contactor for Storage -60 ... +80 °C | Near Contactor for Operation in Free Air -40 ... 70 °C | Near Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... +60 °C | Near Contactor for Operation in Free Air (Uc) -40 ... 70 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27
Closed, Shock Direction: B1 25 g | Open, Shock Direction: B1 5 g
Resistance to Vibrations
4g Closed Position & 2g Open position 5 ... 300 Hz
Pollution Degree
3
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
BV Certificate
BV Certificate AF(C)09...AF(C)38 3-pole and 4-pole contactors with screw and Push-in Spring terminals
CB Certificate
CB Certificate AF(C)26, AF(C)38, AF26(Z)B, AF38(Z)B 4-pole contactors
CQC Certificate
CQC Certificate, Contactor, AF*26, AF*30, AF*38, Made in France
Declaration of Conformity - CCC
CCC Declaration of Conformity, Contactor, AF26, AF30, AF38, AFS26, AFS30, AFS38 Made in France
Declaration of Conformity - CE
EU Declaration of Conformity AFC09 ... AFC80 4-pole Contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AFC09 ... AFC80 4-pole Contactors
DNV Certificate
DNV Certificate AFC09...96 3-pole & AFC09...80 4-pole contactors with screw, push-in terminals
RINA Certificate
Rina Certificate for AFC09...AFC96 3 pole and 4 pole contactors, NFC relays ,screw and spring terminals
UL Certificate
UL-US Certificate of Compliance AFC09 ... AFC38 4-pole contactors | UL-CA Certificate of Compliance AFC09 ... AFC38 4-pole contactors
Package Level 1 Units
box 1 piece
Package Level 1 Width
87 mm
Package Level 1 Depth / Length
103 mm
Package Level 1 Height
47 mm
Package Level 1 Gross Weight
0.42 kg
Package Level 1 EAN
3471523016378
Package Level 3 Units
864 piece
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4755 >> Contactors
Feature → Business Impact → Application: The 4-pole (2 normally open + 2 normally closed) design provides robust motor control with clear break/make paths, improving switch reliability and reducing wear on start-up sequences in conveyors and pumps. This translates to measurable downtime reduction and smoother start/stop cycles in duty-critical automation panels. Feature → Application: Main circuit rated up to 690 V, AC-1 55 A at 40 °C, 45 A at 60 °C, and 37 A at 70 °C, enabling compact drives and contactor ensembles for medium-power motors in packaging lines and material handling. Feature → Compatibility: Coil voltage options 110 V AC 50 Hz or 110–120 V AC 60 Hz ensure seamless integration with standard control circuits and legacy systems, reducing engineering time and change control risk. Feature → Mounting & Wiring: DIN rail TH35-15 or TH35-7.5 mounting and screw terminals with versatile conductor ranges simplify installation, cut wiring errors, and improve serviceability during maintenance. Feature → Space & Accessories: 45 mm width and add-on auxiliary contact blocks support scalable control schemes while preserving cabinet space and improving fault isolation. Feature → Compliance & Safety: CE, UKCA, UL/CSA certifications and IP20 protection mitigate regulatory and safety concerns, enabling faster project approvals and safer operation across global sites.

Get a Quick Quote for a ABB 1SBL291501R8400

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SBL291501R8400? Enquire Now

FAQs

The device supports DIN rail mounting on TH35-15 or TH35-7.5 rails and uses screw terminals for the main and control circuits. It also accommodates mounting with two M4 screws, enabling flexible installation in compact panels and reducing time spent on mechanical mounting during commissioning.
AC-1 rating is up to 55 A at 690 V (40 °C), 45 A at 690 V (60 °C), and 37 A at 690 V (70 °C). AC-3 ratings vary with voltage and temperature (e.g., 23.2 A at 240 V, 22 A at 440 V, 21.2 A at 415 V, down to 10.5 A at 690 V), suitable for motor starting and switching per IEC/UL standards.
Yes. The coil is available for 110 V AC at 50 Hz or 110–120 V AC at 60 Hz, matching standard control circuits in North America and Europe. This reduces the need for voltage adapters and simplifies panel design while ensuring reliable coil energization.
The contactor carries CE and UKCA marks for Europe, UL/CSA listings for North America, plus BV, DNV, and other regional certificates. It also aligns with RoHS/REACH requirements and provides IP20 protection, supporting global deployments in strict regulatory environments.
The 4-pole, 2 NO + 2 NC design provides predictable switching paths, enabling longer service intervals for motor control. With 3600 mechanical cycles per hour and robust screw-terminal connections, maintenance is straightforward, reducing shutdown time and extending component life in challenging industrial settings.