ABB 1SBL296560R2200 Block Contactor - UL/CSA 55 A
Part Number: 1SBL296560R2200
Quick Summary
ABB 1SBL296560R2200 Block Contactor is a robust four-pole device for motor control in demanding environments. In plants with fluctuating control voltages, coil compatibility and energy waste can cause instability and nuisance trips. It complies with IEC/EN 60947-4-1 and UL 60947-4-1, with CE and UKCA marks, and offers IP10 protection on coil terminals for safe operation. By combining AF technology with a wide control voltage range of 48–130 V and a compact DIN-rail footprint, it reduces panel space, enhances reliability, and lowers wiring complexity across conveyors, pumps, and fans.
Product Information
Extended Description
1SBL296560R2200 ABB: The AF38ZB-22-00RT-22 is a 4 pole - 690 V IEC or 600 UL contactor with Ring-Tongue Terminals, controlling motors up to 11 kW / 400 V AC (AC-3) and switching power circuits up to 55 A (AC-1) or 55 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (48-130 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
Motor control and protection for Rolling stock application_PDF
Instructions and Manuals
Installation instructions AF09...38(Z)B-..RT Contactors, NF(Z)B..ERT Contactor relays and CA4..RT, CAL4..RT, CAT4..RT, LDC4RT Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
45 mm
Product Net Depth / Length
101 mm
Product Net Height
86 mm
Product Net Weight
0.39 kg
Number of Main Contacts NO
2
Number of Main Contacts NC
2
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Number of Poles
4P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives.
Rated Operational Voltage
Main Circuit 690 V
Rated Frequency (f)
Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 55 A
Rated Operational Current AC-1 (Ie)
(1000 V) 60 °C 45 A | (690 V) 40 °C 55 A | (690 V) 70 °C 37 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 21.2 A | (440 V) 60 °C 20 A | (500 V) 60 °C 17.6 A | (690 V) 60 °C 10.5 A | (380 / 400 V) 60 °C 22 A | (220 / 230 / 240 V) 60 °C 23.2 A
Rated Operational Power AC-3 (Pe)
(400 V) 11 kW | (415 V) 11 kW | (440 V) 11 kW | (500 V) 11 kW | (690 V) 9 kW | (220 / 230 / 240 V) 5.5 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 300 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 55 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 150 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 450 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 225 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
6 kV
Rated Control Circuit Voltage (Uc)
50 Hz 48 ... 130 V | 60 Hz 48 ... 130 V | DC Operation 48 ... 130 V
Power Loss
at Rated Operating Conditions AC-1 per Pole 2.3 W | at Rated Operating Conditions AC-3 per Pole 0.42 W
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 screws placed diagonally
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP10 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Tightening Torque
Control Circuit 1.2 N·m | Main Circuit 2.5 N·m
Terminal Type
Ring-Tongue Terminals
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 55 A
Tightening Torque UL/CSA
Control Circuit 11 in·lb | Main Circuit 22 in·lb
Ambient Air Temperature
Close to Contactor for Storage -60 ... +80 °C | Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Shock and Vibration Withstand acc. to IEC 61373
Category 1, Class B
Pollution Degree
3
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
End Of Life Disassembling Instructions
End of life instruction AF(S)09/12/16/26/30/38(Z)(B)(K)(RT) Contactors & NF(Z)(B)(K)(RT) Contactors relays
Environmental Product Declaration - EPD
Environmental Product Declaration AF(S)26/30/38(Z)(B) Contactors (FR)
Sustainable Material Content in Packaging (wt. %)
Recycled Cardboard - 86 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 28 %
CB Certificate
CB Certificate AF26, AF38, AF26(Z)B, AF38(Z)B 4-pole contactors
CCC Certificate
CCC Certificate AF26, AF30, AF38, AF26(Z)B, AF30(Z)B, AF38(Z)B 3 and 4-pole contactors, AFS26, AFS30, AFS38 safety contactors
CQC Certificate
CQC Certificate, Contactor, AF*26, AF*30, AF*38, Made in France
Declaration of Conformity - CCC
CCC Declaration of Conformity, Contactor, AF26, AF30, AF38, AFS26, AFS30, AFS38 Made in France
Declaration of Conformity - CE
EU Declaration of Conformity AF09 to AF38(Z)B..RT 3 and 4-pole contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09 to AF38(Z)B..RT 3 and 4-pole contactors
UL Listing Card
UL_E319322
UR Certificate
UR Certificate of Compliance AF09...AF38(Z)B-..RT 4-pole contactors with ring tongue terminals
Package Level 1 Units
box 1 piece
Package Level 1 Width
87 mm
Package Level 1 Depth / Length
103 mm
Package Level 1 Height
47 mm
Package Level 1 Gross Weight
0.4 kg
Package Level 1 EAN
3471523129221
Package Level 2 Units
box 18 piece
Package Level 2 Width
250 mm
Package Level 2 Depth / Length
300 mm
Package Level 2 Height
315 mm
Package Level 2 Gross Weight
14.4 kg
Package Level 3 Units
864 piece
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
The AF technology 4-pole block contactor delivers reliable motor control with a clear business impact: reduced energy fluctuations and stable operation in networks that swing between 48 and 130 V AC or DC. This translates to fewer nuisance trips and longer equipment life in AC-3 duty at up to 11 kW for 400–690 V applications, and dependable AC-1 switching up to 55 A. The coil terminals are Ring-Tongue style, simplifying field wiring and ensuring solid connections under vibration. DIN-rail mounting on TH35-15 or TH35-7.5 plus optional add-on auxiliary blocks enables scalable control logic without reworking panels. With 2 NO and 2 NC main contacts, and 0 auxiliary contacts, the unit keeps a compact silhouette (45 mm width, 101 mm depth, 86 mm height) at approximately 0.39 kg. The device is designed for easy integration with existing ABB NF/RT accessories and standard installation practices, reducing commissioning time and total cost of ownership. Compliance with IEC/EN 60947-1, IEC 60947-4-1, UL/CSA, CE, UKCA ensures regulatory readiness across global sites. Customer-specific configurations can be achieved through the wide accessory ecosystem and documented installation guides.
Get a Quick Quote for a ABB 1SBL296560R2200
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SBL296560R2200?
Enquire Now
FAQs
This unit supports DIN-rail mounting on TH35-15 or TH35-7.5 rails and can be mounted with two M4 screws for a secure installation. Wiring uses Ring-Tongue terminals for coil connections and main terminals, providing robust, vibration-resistant connections suitable for industrial environments. The footprint is compact, facilitating easy integration in existing panel layouts.
For AC-1 operation at 1000 V and 60 °C, the Rated Operational Current is 45 A (690 V) and 55 A (690 V) at 40 °C. For AC-3, the ratings include 21.2 A at 415 V, 20 A at 440 V, 17.6 A at 500 V, 10.5 A at 690 V, with Power up to 11 kW at 400 V and 11 kW at 415/440 V, depending on voltage class.
Yes. The data sheet references motor control and protection suitable for rolling stock applications, while the device is equally applicable to conveyors, pumps, and fans in general plant automation. Its wide control voltage range, surge protection, and 4-pole 690 V capability make it versatile for both mobility-related systems and stationary industrial processes.
The product complies with IEC/EN 60947-1 and IEC/EN 60947-4-1, UL 60947-4-1, and CSA C22.2 No. 60947-4-1, with CE and UKCA marks. It also aligns with EN 50155 in applicable parts, and supports RoHS, REACH, CMRT declarations. These certifications ensure regulatory compliance for global installations and safe integration into modern control systems.
The device’s built-in surge protection and AF technology reduce nuisance trips and energy waste, improving availability and lowering energy costs. Its modular design allows easy expansion with auxiliary blocks, simplifying control logic upgrades. DIN-rail mounting plus compact dimensions reduce cabinet space and installation time, delivering faster commissioning and long-term maintenance efficiency.