ABB 1SBL321074R8110 Block Contactor - 690V Rating
Part Number: 1SBL321074R8110
Quick Summary
ABB Block Contactor 1SBL321074R8110 controls 3-phase motors up to 690 V in industrial drives. The compact, 3-pole design with a built-in auxiliary contact streamlines wiring and control logic, reducing panel depth and wiring errors. Engineers often struggle with space, mounting versatility, and meeting global approvals; this device addresses those challenges with a 54 mm width and 90 mm depth footprint and 0.667 kg weight for easy integration. It supports 24 V control circuits and a full range of add-on auxiliary blocks for front or side mounting. Certifications include CE conformity and UL/CSA listings, alongside RoHS/REACH compliance, giving you clear regulatory alignment and simplified sourcing.
Product Information
Extended Description
1SBL321074R8110 ABB: AX32, AX40 contactors are mainly used for controlling 3-phase motors and power circuits up to 690 V AC. These contactors are of the block type design with: – 3 main poles and 1 built-in auxiliary contact – control circuit: AC operated – add-on auxiliary contact blocks for front or side mounting and a wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
1SBC100187L0203
Instructions and Manuals
AX 06~40A instructions
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
54 mm
Product Net Depth / Length
90 mm
Product Net Height
108.3 mm
Product Net Weight
0.667 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
0
Rated Operational Voltage
Auxiliary Circuit 690 V | Main Circuit 690 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 65 A | acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)
(220 / 240 V) 55 °C 60 A | (690 V) 40 °C 60 A | (690 V) 70 °C 42 A
Rated Operational Current AC-3 (Ie)
(415 V) 55 °C 40 A | (440 V) 55 °C 37 A | (500 V) 55 °C 33 A | (690 V) 55 °C 25 A | (380 / 400 V) 55 °C 40 A | (220 / 230 / 240 V) 55 °C 40 A
Rated Operational Current AC-15 (Ie)
(500 V) NC 2 | (500 V) 2 A | (690 V) 2 A | (24 / 127 V) 6 A | (220 / 240 V) 4 A | (380 / 400 V) 3 A | (400 / 440 V) 2 A
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W | (110 V) 0.55 A / 60 W | (125 V) 1.1 A / 138 W | (220 V) 0.55 A / 121 W | (250 V) 0.55 A / 138 W | (400 V) 2.8 A / 134 W | (500 V) 2 A / 144 W
Rated Operational Power AC-3 (Pe)
(415 V) 18.5 kW | (440 V) 22 kW | (500 V) 22 kW | (690 V) 22 kW | (380 / 400 V) 18.5 kW | (220 / 230 / 240 V) 11 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 400 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 65 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 150 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 600 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 225 A | for 0.1 s 140 A | for 1 s 100 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 820 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 340 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
Rated Impulse Withstand Voltage (Uimp)
Auxiliary Circuit 6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-15) 1200 cycles per hour | (AC-3) 1200 cycles per hour | (DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 24 V | 60 Hz 24 V
Power Loss
at Rated Operating Conditions AC-1 per Pole 3 W | at Rated Operating Conditions AC-3 per Pole 1.3 W
Operate Time
Between Coil De-energization and NC Contact Closing 7 ... 14 ms | Between Coil De-energization and NO Contact Opening 4 ... 11 ms | Between Coil Energization and NC Contact Opening 6 ... 18 ms | Between Coil Energization and NO Contact Closing 8 ... 21 ms
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Tightening Torque
Auxiliary Circuit 1 N·m | Control Circuit 1 N·m | Main Circuit 2.3 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
General Use Rating UL/CSA
(600 V AC) 60 A
Horsepower Rating UL/CSA
(120 V AC) Single Phase 3 hp | (200 ... 208 V AC) Three Phase 10 hp | (220 ... 240 V AC) Three Phase 15 hp | (240 V AC) Single Phase 7.5 hp | (440 ... 480 V AC) Three Phase 30 hp | (550 ... 600 V AC) Three Phase 40 hp
Tightening Torque UL/CSA
Auxiliary Circuit 9 in·lb | Control Circuit 9 in·lb | Main Circuit 20 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 34 A | (200 ... 208 V AC) Three Phase 32.2 A | (220 ... 240 V AC) Three Phase 42 A | (240 V AC) Single Phase 40 A | (440 ... 480 V AC) Three Phase 40 A | (550 ... 600 V AC) Three Phase 41 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -25 ... 55 °C | Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C | Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
Maximum Operating Altitude Permissible
Without Derating 3000 m
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
CB Certificate
AX 32~40A CB certification
CCC Certificate
9AKK107492A7090
CCS Certificate
CCS Certificate of AFC09 ... AFC96 , AX09-AX370 contactors
CQC Certificate
CQC Certificate, Contactor, AX32, AX40, Made in China
Declaration of Conformity - CCC
CCC Declaration of Conformity, Contactor, AX32, AX40, Made in China
Declaration of Conformity - CE
EU Declaration of Conformity AX06, AX09, AX12, AX18, AX25, AX32, AX40, AX50, AX65, AX80 3-pole Contactors
UL Certificate
UL Certificate of Compliance – AX06, AX09, AX12, AX18, AX25
Package Level 1 Units
box 1 piece
Package Level 1 Width
65 mm
Package Level 1 Depth / Length
101 mm
Package Level 1 Height
115 mm
Package Level 1 Gross Weight
0.71 kg
Package Level 1 EAN
3471522401816
Package Level 2 Units
12 piece
Package Level 2 Width
240 mm
Package Level 2 Depth / Length
295 mm
Package Level 2 Height
145 mm
Package Level 2 Gross Weight
8.52 kg
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4755 >> Contactors
E-Number (Finland)
3707350
The 3-pole block design concentrates motor switching power with a single integrated auxiliary contact, which reduces wiring complexity and accelerates panel assembly. This translates to lower wiring errors and faster commissioning in automation projects. The 24 V control circuit is compatible with standard PLCs and control electronics, enabling reliable interlocks and safe de-energization sequences for motor startups. With a compact 54 mm width and 90 mm depth, the device frees rack space in control cabinets, supporting denser layouts and easier maintenance. Rated operational currents (AC-3 up to 40 A at 690 V) deliver robust motor control for common fans, conveyors, and mixers, while the 3 NO main contacts and 1 NO auxiliary contact provide essential feedback and interlocking. Screw terminals and IP20 protection simplify installation and ensure dependable operation in standard factory environments. End-user benefits include improved control reliability, reduced lifecycle cost through fewer components, and straightforward integration with existing ABB accessories and add-on auxiliary blocks for front or side mounting.
Get a Quick Quote for a ABB 1SBL321074R8110
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SBL321074R8110?
Enquire Now
FAQs
Install the device using the screw terminals for main, auxiliary, and control circuits. Connect the 24 V control coil and ensure the main terminals carry up to 690 V. Use the included space for an auxiliary contact block if needed and tighten all connections to the specified torque: 2.3 N·m for the main circuit, and 1 N·m for auxiliary and control circuits. Verify IP20 protection and clearance for safe maintenance.
At 690 V and 55 °C, AC-3 rated current is 25 A; AC-1 rated current varies by voltage (for example 60 A at 220/240 V, 4 A at 690 V NC if applicable). The product supports typical motor control duties with 3 main NO contacts and one auxiliary NO contact, suitable for common 3‑phase motor starts in industrial settings.
Yes. The ABB 1SBL321074R8110 is a 3-pole Block Contactor designed to control 3-phase motors and power circuits up to 690 V AC, with 24 V control, and built-in auxiliary contact for interlocking and feedback, making it appropriate for typical industrial motor control applications.
The device carries CE conformity and UL/CSA certifications, plus RoHS and REACH declarations. It also includes 690 V insulation ratings, IP20 protection on terminals, and design compliance with relevant EN/IEC standards, supporting regulatory alignment across global supply chains.
The unit is 54 mm wide, 90 mm deep, and 108.3 mm high, weighing 0.667 kg (0.71 kg packaged). This compact footprint helps maximize panel density, simplifies wiring runs, and allows easier cooling and maintenance in crowded control cabinets.