ABB 1SBL341201R8000 Block Contactor - 690 V IEC/UL

Part Number: 1SBL341201R8000
Manufacturer
ABB
Part number
1SBL341201R8000

Quick Summary

Block Contactor ABB 1SBL341201R8000 controls motor power in industrial automation applications. Engineers often struggle with coil voltage compatibility and retrofit integration across existing panels. It complies with IEC/EN 60947-1 and 60947-4-1, UL 60947-1, UL 60947-4-1, and CE/UKCA marks, delivering certified reliability for global installations. With DIN-rail mounting, add-on auxiliary contact blocks, and a wide accessories range, it streamlines installation, reduces downtime, and supports scalable control for motors, conveyors, and line equipment.

Product Information

Extended Description

1SBL341201R8000 ABB: The AFC40-40-00-80 is a 4-pole (4 N.O) - 690 V IEC or 600 V UL contactor with Screw terminals, mainly controlling power circuits up to 70 A (IEC AC-1) or 60 A UL general use. Within the AF platform, AFC contactors offer an optimized operating time for AC controlled applications with electromagnetic coil (control voltage : 220 ... 230 V AC 50 Hz / 230 ... 240 V AC 60 Hz). AFC contactors have a block type design and can be easily extended with add-on auxiliary contact blocks and a wide range of additionnal accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
1SBC100219C0201 AFC contactors for AC control applications_Catalog PDF
Instructions and Manuals
Installation instructions AF(C)40(B)...80(B)-40/22 Contactors, CA4, CAL4, CAT4, CC4, LDC4 Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
Product Net Width
70 mm
Product Net Depth / Length
119.5 mm
Product Net Height
113.5 mm
Product Net Weight
1.18 kg
Number of Main Contacts NO
4
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Number of Poles
4P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60947-1, CSA C22.2 No. 60947-4-1
Rated Operational Voltage
Main Circuit 690 V
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 105 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 70 A | (690 V) 60 °C 60 A | (690 V) 70 °C 50 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 40 A | (440 V) 60 °C 40 A | (500 V) 60 °C 35 A | (690 V) 60 °C 25 A | (380 / 400 V) 60 °C 40 A | (220 / 230 / 240 V) 60 °C 40 A
Rated Operational Power AC-3 (Pe)
(415 V) 22 kW | (440 V) 22 kW | (500 V) 22 kW | (690 V) 22 kW | (380 / 400 V) 18.5 kW | (220 / 230 / 240 V) 11 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
Auxiliary Circuit 6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-2 / AC-4) 0 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 220 ... 230 V | 60 Hz 230 ... 240 V
Coil Consumption
Average Holding Value 50 / 60 Hz 20 V·A | Average Pull-in Value 50 Hz 150 V·A | Average Pull-in Value 60 Hz 151 V·A
Power Loss
at Rated Operating Conditions AC-1 per Pole 3 W | at Rated Operating Conditions AC-3 per Pole 1 W
Operate Time
Between Coil De-energization and NO Contact Opening 4 ... 14 ms | Between Coil Energization and NO Contact Closing 7 ... 21 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 4 ... 35 mm² | Flexible with Insulated Ferrule 1/2x 4 ... 35 mm² | Rigid 1/2x 6 ... 3 5 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Control Circuit 10 mm | Main Circuit 16 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Recommended Screw Driver
Main Circuit 6.5 | Main Circuit Slot | Control Circuit 5.5 | Control Circuit Slot
Tightening Torque
Control Circuit 1.2 N·m | Main Circuit 4 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 60 A
Tightening Torque UL/CSA
Control Circuit 11 in·lb | Main Circuit 35 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 3 A | (200 ... 208 V AC) Three Phase 10 A | (220 ... 240 V AC) Three Phase 15 A | (240 V AC) Single Phase 7-1/2 A | (440 ... 480 V AC) Three Phase 30 A | (550 ... 600 V AC) Three Phase 40 A
Ambient Air Temperature
Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C | Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Pollution Degree
3
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
BV Certificate
BV_2634H36994B1
CB Certificate
CB Certificate AFC40, AFC52, AFC65 3 or 4-pole contactors
CCC Certificate
CCC Declaration of Conformity, Contactor, AF(C)40, AF52(C), AF65(C),AFC78 Made in China
CQC Certificate
CQC Certificate, Contactor, AF40, AF52, AF65, AFC40, AFC52, AFC65, Made in China
Declaration of Conformity - CE
EU Declaration of Conformity AFC09 ... AFC80 4-pole Contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AFC09 ... AFC80 4-pole Contactors
DNV Certificate
DNV Certificate AFC09...96 3-pole & AFC09...80 4-pole contactors with screw, push-in terminals
RINA Certificate
Rina Certificate for AFC09...AFC96 3 pole and 4 pole contactors, NFC relays ,screw and spring terminals
UL Certificate
UL-CA Certificate of Compliance AFC40 ... AFC80 4-pole contactors | UL-US Certificate of Compliance AFC40 ... AFC80 4-pole contactors
Package Level 1 Units
box 1 piece
Package Level 1 Width
146.5 mm
Package Level 1 Depth / Length
96.5 mm
Package Level 1 Height
146.5 mm
Package Level 1 Gross Weight
1.3 kg
Package Level 1 EAN
3471523019065
Package Level 3 Units
192 piece
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4755 >> Contactors
The 4 NO main contacts and 4-pole design enable direct, robust control of multi-phase motors with a single device, reducing panel density and wiring complexity while delivering reliable switching up to 690 V and up to 70 A AC-1 (40 °C) / 60 A (60 °C). This translates to lower lifecycle costs and simpler servicing in conveyors and pumps. The coil is available at 50 Hz 220-230 V and 60 Hz 230-240 V, delivering fast operate times of 4-14 ms (coil de-energization to NO opening) and 7-21 ms (energization to NO closing), which minimizes electrical arc exposure and wear on contacts. Energy efficiency is improved through a low coil power loss of 3 W per pole (AC-1) and 1 W (AC-3), helping to reduce cabinet heat and cooling needs. Installation and expansion are straightforward thanks to screw terminals and a broad accessory ecosystem for add-on auxiliary contacts and mounting options, enabling scalable control without replacing the base unit. The device supports flexible conductor connections—1/2x 4-35 mm² for main circuit and 1/2x 0.75-2.5 mm² for control circuit—while offering DIN rail mounting TH35-15 and optional screw mounting for bespoke enclosures. Reliability is reinforced by robust IP ratings (coil and auxiliary IP20, main terminals IP10) and broad conformity certificates (IEC/UL/CSA/UKCA/CE, CB, CCC, CQC, BV, DNV, RINA), making it suitable for heavy-duty industrial environments.

Get a Quick Quote for a ABB 1SBL341201R8000

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SBL341201R8000? Enquire Now

FAQs

Mount the unit on a TH35-15 DIN rail per IEC 60715. It also supports mounting by screws, using 2 x M4 or 2 x M6 screws placed diagonally. Ensure sufficient clearance for coil access and wire routing, and tighten main and control terminals to the recommended torques: 4 N·m for the main circuit and 1.2 N·m for the control circuit.
For AC-1 operation at 690 V, the device supports up to 70 A at 40 °C (60 °C 60 A, 70 °C 50 A). For AC-3, ratings vary by voltage, with up to about 40 A across common industrial voltages (e.g., 415–690 V). This makes the contactor suitable for motor starting and general power switching in DC-free AC motor circuits.
Yes. The product specifies maximum operating altitude without derating at 3000 meters, which supports reliable performance in many industrial installations located at higher elevations.
The AFC40 family, including 1SBL341201R8000, carries CE and UKCA declarations, UL/CSA certifications, and other global approvals (CB, CCC, CQC, BV, DNV, RINA). This broad certification portfolio supports global deployment and regulatory compliance in diverse markets.
ABB offers a wide range of add-on auxiliary contact blocks and compatible accessories for the AFC platform, enabling expansion of auxiliary outputs and tailored control configurations without replacing the main unit. This supports scalable automation and simplified panel integration.