ABB 1SBL341501R8100 Block Contactor - 690V IEC/UL
Part Number: 1SBL341501R8100
Quick Summary
ABB 1SBL341501R8100 Block Contactor is a 4-pole control device designed to manage power circuits up to 70 A (IEC AC-1) with a 24 V AC control coil. This compact solution helps reduce panel space and simplify wiring by integrating NO and NC contacts in one enclosure. Users often struggle with mismatched control voltages, installation in crowded panels, and limited accessory options. The device complies with IEC/EN 60947-1 and 60947-4-1, UL 60947-1 and 60947-4-1, and CSA standards, supporting broad regulatory requirements and safe operation. By combining robust ratings with DIN rail mounting, screw-terminal connections, and extensive accessories, it delivers reliable, scalable control for motor starters, conveyors, and other power circuits.
Product Information
Extended Description
1SBL341501R8100 ABB: The AFC40-22-00-81 is a 4-pole (2 N.O + 2 N.C) - 690 V IEC or 600 V UL contactor with Screw terminals, mainly controlling power circuits up to 70 A (IEC AC-1) or 60 A UL general use. Within the AF platform, AFC contactors offer an optimized operating time for AC controlled applications with electromagnetic coil (control voltage : 24 V AC 50 Hz / 24 V AC 60 Hz). AFC contactors have a block type design and can be easily extended with add-on auxiliary contact blocks and a wide range of additionnal accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
1SBC100219C0201 AFC contactors for AC control applications_Catalog PDF
Instructions and Manuals
Installation instructions AF(C)40(B)...80(B)-40/22 Contactors, CA4, CAL4, CAT4, CC4, LDC4 Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
Product Net Width
70 mm
Product Net Depth / Length
119.5 mm
Product Net Height
113.5 mm
Product Net Weight
1.18 kg
Number of Main Contacts NO
2
Number of Main Contacts NC
2
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Number of Poles
4P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60947-1, CSA C22.2 No. 60947-4-1
Rated Operational Voltage
Main Circuit 690 V
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 105 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 70 A | (690 V) 60 °C 60 A | (690 V) 70 °C 50 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 40 A | (440 V) 60 °C 40 A | (500 V) 60 °C 35 A | (690 V) 60 °C 25 A | (380 / 400 V) 60 °C 40 A | (220 / 230 / 240 V) 60 °C 40 A
Rated Operational Power AC-3 (Pe)
(415 V) 22 kW | (440 V) 22 kW | (500 V) 22 kW | (690 V) 22 kW | (380 / 400 V) 18.5 kW | (220 / 230 / 240 V) 11 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
Auxiliary Circuit 6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-2 / AC-4) 0 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 24 V | 60 Hz 24 V
Coil Consumption
Average Holding Value 50 / 60 Hz 20 V·A | Average Pull-in Value 50 Hz 150 V·A | Average Pull-in Value 60 Hz 151 V·A
Power Loss
at Rated Operating Conditions AC-1 per Pole 3 W | at Rated Operating Conditions AC-3 per Pole 1 W
Operate Time
Between Coil De-energization and NO Contact Opening 4 ... 14 ms | Between Coil Energization and NO Contact Closing 7 ... 21 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 4 ... 35 mm² | Flexible with Insulated Ferrule 1/2x 4 ... 35 mm² | Rigid 1/2x 6 ... 3 5 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Control Circuit 10 mm | Main Circuit 16 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Recommended Screw Driver
Main Circuit 6.5 | Main Circuit Slot | Control Circuit 5.5 | Control Circuit Slot
Tightening Torque
Control Circuit 1.2 N·m | Main Circuit 4 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 60 A
Tightening Torque UL/CSA
Control Circuit 11 in·lb | Main Circuit 35 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 3 A | (200 ... 208 V AC) Three Phase 10 A | (220 ... 240 V AC) Three Phase 15 A | (240 V AC) Single Phase 7-1/2 A | (440 ... 480 V AC) Three Phase 30 A | (550 ... 600 V AC) Three Phase 40 A
Ambient Air Temperature
Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C | Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Pollution Degree
3
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
BV Certificate
BV_2634H36994B1
CB Certificate
CB Certificate AFC40, AFC52, AFC65 3 or 4-pole contactors
CCC Certificate
CCC Declaration of Conformity, Contactor, AF(C)40, AF52(C), AF65(C),AFC78 Made in China
CQC Certificate
CQC Certificate, Contactor, AF40, AF52, AF65, AFC40, AFC52, AFC65, Made in China
Declaration of Conformity - CE
EU Declaration of Conformity AFC09 ... AFC80 4-pole Contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AFC09 ... AFC80 4-pole Contactors
DNV Certificate
DNV Certificate AFC09...96 3-pole & AFC09...80 4-pole contactors with screw, push-in terminals
RINA Certificate
Rina Certificate for AFC09...AFC96 3 pole and 4 pole contactors, NFC relays ,screw and spring terminals
UL Certificate
UL-CA Certificate of Compliance AFC40 ... AFC80 4-pole contactors | UL-US Certificate of Compliance AFC40 ... AFC80 4-pole contactors
Package Level 1 Units
box 1 piece
Package Level 1 Width
146.5 mm
Package Level 1 Depth / Length
96.5 mm
Package Level 1 Height
146.5 mm
Package Level 1 Gross Weight
1.3 kg
Package Level 1 EAN
3471523019126
Package Level 3 Units
192 piece
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4755 >> Contactors
Feature: Four-pole design with two normally open and two normally closed contacts. Business impact: Enables in-one-device switching of complete power circuits, reducing wiring complexity and potential fault points. Application: Ideal for motor control and load switching in compact control panels. Feature: 24 V AC control coil (50 Hz / 60 Hz). Business impact: Easy integration with PLCs and automation logic, lowering control wiring costs and energy consumption. Application: Control circuits in automation panels and starter cabinets. Feature: Main circuit rated up to 690 V with IEC AC-1 70 A (60 A at 60 °C, 50 A at 70 °C). Business impact: Higher fault tolerance and broader application range for industrial presses, conveyors, and pumps. Application: Heavy-duty power switching in manufacturing lines. Feature: DIN rail mounting TH35-15 and screw terminals. Business impact: Fast installation, modular upgrades, and secure, vibration-resistant connections. Application: New builds and retrofit projects in control panels. Feature: Compact dimensions and weight (70 mm width, 119.5 mm depth, 113.5 mm height; 1.18 kg). Business impact: Saves panel space and simplifies enclosure design, reducing installation time and cost. Application: Modern machine cabinet layouts. Feature: High short-time withstand and mechanical switching frequencies. Business impact: Protects circuits from surges and enables frequent switching without premature wear. Application: Start-stop sequences for motors and drives. Feature: Broad certifications and compliance (IEC/EN 60947-1, 60947-4-1, UL CSA). Business impact: Streamlines procurement and compliance across regions. Application: Global production environments with strict regulatory requirements.
Get a Quick Quote for a ABB 1SBL341501R8100
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SBL341501R8100?
Enquire Now
FAQs
The device is a four-pole contactor with a 24 V AC control coil, rated for main circuit voltages up to 690 V and IEC AC-1 currents up to 70 A (60 A at 60 °C, 50 A at 70 °C), with 2 NO and 2 NC main contacts.
Yes. It is designed for mounting on TH35-15 DIN rails (35 x 15 mm) per IEC 60715, which enables quick installation and easy replacement in control panels.
Main circuit connections use screw terminals with flexible ferrule and insulated ferrule options (1/2 x 4 … 35 mm²; rigid 1/2 x 6 … 35 mm²). The control circuit also supports flexible and rigid terminations in the 0.75 … 2.5 mm² range.
It complies with IEC/EN 60947-1 and 60947-4-1, UL 60947-1 and 60947-4-1, CSA standards, and associated CE/UKCA declarations, supporting global regulatory compliance.
Ideal for motor starters, conveyors, pumps, and other power-control tasks in automation panels, offering reliable switching, compact installation, and compatibility with AF platform accessories for extended functionality.