ABB Block Contactor 1SBL341501R8400 - IEC/UL 60947

Part Number: 1SBL341501R8400
Manufacturer
ABB
Part number
1SBL341501R8400

Quick Summary

ABB Block Contactor 1SBL341501R8400 enables four-pole AC power control for motors in industrial automation. Engineers often wrestle with coil voltage mismatch, limited expansion options, and cabinet space constraints. This model carries IEC/EN 60947-1 and 60947-4-1 ratings along with UL/CSA and CE (and UKCA) documentation, supporting global compliance. Its compact 70 mm width and TH35 DIN rail mounting simplify panel integration, while the block design accepts add-on auxiliary contact blocks for scalable control. With robust ratings for AC-1 and AC-3 service, it minimizes downtime while enabling straightforward procurement and maintenance in demanding environments.

Product Information

Extended Description

1SBL341501R8400 ABB: The AFC40-22-00-84 is a 4-pole (2 N.O + 2 N.C) - 690 V IEC or 600 V UL contactor with Screw terminals, mainly controlling power circuits up to 70 A (IEC AC-1) or 60 A UL general use. Within the AF platform, AFC contactors offer an optimized operating time for AC controlled applications with electromagnetic coil (control voltage : 110 V AC 50 Hz / 110 ... 120 V AC 60 Hz). AFC contactors have a block type design and can be easily extended with add-on auxiliary contact blocks and a wide range of additionnal accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
1SBC100219C0201 AFC contactors for AC control applications_Catalog PDF
Instructions and Manuals
Installation instructions AF(C)40(B)...80(B)-40/22 Contactors, CA4, CAL4, CAT4, CC4, LDC4 Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
Product Net Width
70 mm
Product Net Depth / Length
119.5 mm
Product Net Height
113.5 mm
Product Net Weight
1.18 kg
Number of Main Contacts NO
2
Number of Main Contacts NC
2
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Number of Poles
4P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60947-1, CSA C22.2 No. 60947-4-1
Rated Operational Voltage
Main Circuit 690 V
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 105 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 70 A | (690 V) 60 °C 60 A | (690 V) 70 °C 50 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 40 A | (440 V) 60 °C 40 A | (500 V) 60 °C 35 A | (690 V) 60 °C 25 A | (380 / 400 V) 60 °C 40 A | (220 / 230 / 240 V) 60 °C 40 A
Rated Operational Power AC-3 (Pe)
(415 V) 22 kW | (440 V) 22 kW | (500 V) 22 kW | (690 V) 22 kW | (380 / 400 V) 18.5 kW | (220 / 230 / 240 V) 11 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
Auxiliary Circuit 6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-2 / AC-4) 0 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 110 V | 60 Hz 110 ... 120 V
Coil Consumption
Average Holding Value 50 / 60 Hz 20 V·A | Average Pull-in Value 50 Hz 150 V·A | Average Pull-in Value 60 Hz 151 V·A
Power Loss
at Rated Operating Conditions AC-1 per Pole 3 W | at Rated Operating Conditions AC-3 per Pole 1 W
Operate Time
Between Coil De-energization and NO Contact Opening 4 ... 14 ms | Between Coil Energization and NO Contact Closing 7 ... 21 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 4 ... 35 mm² | Flexible with Insulated Ferrule 1/2x 4 ... 35 mm² | Rigid 1/2x 6 ... 3 5 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Control Circuit 10 mm | Main Circuit 16 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Recommended Screw Driver
Main Circuit 6.5 | Main Circuit Slot | Control Circuit 5.5 | Control Circuit Slot
Tightening Torque
Control Circuit 1.2 N·m | Main Circuit 4 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 60 A
Tightening Torque UL/CSA
Control Circuit 11 in·lb | Main Circuit 35 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 3 A | (200 ... 208 V AC) Three Phase 10 A | (220 ... 240 V AC) Three Phase 15 A | (240 V AC) Single Phase 7-1/2 A | (440 ... 480 V AC) Three Phase 30 A | (550 ... 600 V AC) Three Phase 40 A
Ambient Air Temperature
Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C | Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Pollution Degree
3
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
BV Certificate
BV_2634H36994B1
CB Certificate
CB Certificate AFC40, AFC52, AFC65 3 or 4-pole contactors
CCC Certificate
CCC Declaration of Conformity, Contactor, AF(C)40, AF52(C), AF65(C),AFC78 Made in China
CQC Certificate
CQC Certificate, Contactor, AF40, AF52, AF65, AFC40, AFC52, AFC65, Made in China
Declaration of Conformity - CE
EU Declaration of Conformity AFC09 ... AFC80 4-pole Contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AFC09 ... AFC80 4-pole Contactors
DNV Certificate
DNV Certificate AFC09...96 3-pole & AFC09...80 4-pole contactors with screw, push-in terminals
RINA Certificate
Rina Certificate for AFC09...AFC96 3 pole and 4 pole contactors, NFC relays ,screw and spring terminals
UL Certificate
UL-CA Certificate of Compliance AFC40 ... AFC80 4-pole contactors | UL-US Certificate of Compliance AFC40 ... AFC80 4-pole contactors
Package Level 1 Units
box 1 piece
Package Level 1 Width
146.5 mm
Package Level 1 Depth / Length
96.5 mm
Package Level 1 Height
146.5 mm
Package Level 1 Gross Weight
1.3 kg
Package Level 1 EAN
3471523019140
Package Level 3 Units
192 piece
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4755 >> Contactors
Feature → Business Impact → Application: Coil voltage compatibility and coil consumption aligned to 110 V AC (50/60 Hz) reduces transformer needs and energy draw, accelerating control cycles for all coil-driven applications in conveyor and machine control. Feature → Business Impact → Application: Four-pole design (2 NO + 2 NC) supports safe motor start/stop sequences and defined breaking behavior across 690 V mains, ideal for heavy-duty drives in packaging, textiles, and material handling. Feature → Business Impact → Application: Main circuit rated up to 690 V with Ie up to 70 A (AC-1) and 60 A at 690 V (60 °C), plus 40 A AC-3 at various voltages, delivering reliable switching for motor loads and general use across diverse industrial processes. Feature → Business Impact → Application: Compact footprint (70 mm width, 119.5 mm depth, 113.5 mm height) and DIN rail mounting TH35-15 enable dense panels and quick installations, reducing cabinet size and wiring complexity. Feature → Business Impact → Application: Screw terminals with flexible conductor connections and defined torque values streamline installation and maintenance, lowering labor time and risk of loose connections. Feature → Business Impact → Application: Add-on auxiliary contact blocks and wide accessory options provide scalable control architectures, supporting future expansion without replacing devices. Feature → Business Impact → Application: Compliance and safety features including IP20 coil terminals and IP10 main terminals, along with EN/IEC and UL/CSA certifications, ensure regulatory readiness and safe operation in harsh environments.

Get a Quick Quote for a ABB 1SBL341501R8400

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SBL341501R8400? Enquire Now

FAQs

The unit is designed for TH35-15 DIN rail mounting, with additional mounting by screws (2 x M4 or 2 x M6 placed diagonally). It uses screw terminals for both main and control circuits, and its compact 70 mm width, 119.5 mm depth, and 113.5 mm height support dense panel layouts while maintaining safe access to terminations.
The contactor features a 4P arrangement with 2 NO and 2 NC contacts. It has a main circuit rated up to 690 V and Ie up to 70 A (AC-1) or 60 A at 690 V, with a control coil of 110 V AC (50 Hz) / 110–120 V AC (60 Hz), enabling broad compatibility with standard industrial control voltages.
Yes. It supports motor control with a maximum mechanical switching frequency of 3600 cycles per hour and a maximum short-time withstand current (Icw) up to 1000 A for 1 s at 40 °C, ensuring reliable engagement during startup and protection during transient events in demanding drive applications.
The product complies with IEC/EN 60947-1 and 60947-4-1, UL/CSA requirements, CE, and UKCA marking. It also meets RoHS and REACH declarations, with BV, CB, CCC, and other certifications documented for global market access and customer assurance.
The contactor has a net width of 70 mm, depth of 119.5 mm, and height of 113.5 mm, weighing about 1.18 kg. Terminals are screw-type with standard torque values (Main Circuit 4 N·m; Control Circuit 1.2 N·m), and it supports flexible or rigid conductor connections up to 35 mm² for the main circuit and 2.5 mm² for the control circuit.