ABB 1SBL347061R1111 Block Contactor - 690 V IEC/UL
Part Number: 1SBL347061R1111
Quick Summary
Block Contactor ABB 1SBL347061R1111 controls motors in industrial drives and rolling stock applications. When control voltage swings or unstable networks cause trips, you need a device with a wide coil voltage range and built-in surge protection. This ABB device adheres to IEC/EN 60947-1, IEC/EN 60947-4-1 and UL 60335-2-40, ensuring safe, compliant operation across global markets. It also supports DIN rail mounting and add-on auxiliary contact blocks, delivering flexible integration and reduced panel wiring for improved reliability and lower installation costs.
Product Information
Extended Description
1SBL347061R1111 ABB: The AF40B-30-11-11 is a 3 pole - 690 V IEC or 600 UL contactor with pre-mounted auxiliary contacts and screw terminals, controlling motors up to 18.5 kW / 400 V AC (AC-3) or 30 hp / 480 V UL and switching power circuits up to 70 A (AC-1) or 60 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (24-60 V 50/60 Hz and 20-60 V DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
Motor control and protection for Rolling stock application_PDF
Instructions and Manuals
Installation instructions AF(C)40(B)...96(B)-30 Contactors, CA4, CAL4, CAT4, CC4, LDC4 Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
67 mm
Product Net Depth / Length
111 mm
Product Net Height
125.5 mm
Product Net Weight
1.01 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
1
Number of Poles
3P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives.
Rated Operational Voltage
Auxiliary Circuit 690 V | Main Circuit 690 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 Hz | Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 105 A | acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 70 A | (690 V) 60 °C 60 A | (690 V) 70 °C 50 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 40 A | (440 V) 60 °C 40 A | (500 V) 60 °C 35 A | (690 V) 60 °C 25 A | (380 / 400 V) 60 °C 40 A | (220 / 230 / 240 V) 60 °C 40 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 40 A | (440 V) 60 °C 40 A | (500 V) 60 °C 35 A | (690 V) 60 °C 25 A | (380 / 400 V) 60 °C 40 A | (220 / 230 / 240 V) 60 °C 40 A
Rated Operational Current AC-15 (Ie)
(500 V) 2 A | (690 V) 2 A | (24 / 127 V) 6 A | (220 / 240 V) 4 A | (400 / 440 V) 3 A
Rated Operational Current DC-1 (Ie)
(110 V) 2 Poles in Series, 40 °C 70 A | (110 V) 2 Poles in Series, 60 °C 60 A | (110 V) 2 Poles in Series, 70 °C 50 A | (110 V) 3 Poles in Series, 40 °C 70 A | (110 V) 3 Poles in Series, 60 °C 60 A | (110 V) 3 Poles in Series, 70 °C 50 A | (220 V) 3 Poles in Series, 40 °C 70 A | (220 V) 3 Poles in Series, 60 °C 60 A | (220 V) 3 Poles in Series, 70 °C 50 A | (72 V) 1-Pole, 40 °C 70 A | (72 V) 1-Pole, 60 °C 60 A | (72 V) 1-Pole, 70 °C 50 A | (72 V) 2 Poles in Series, 40 °C 70 A | (72 V) 2 Poles in Series, 60 °C 60 A | (72 V) 2 Poles in Series, 70 °C 50 A | (72 V) 3 Poles in Series, 40 °C 70 A | (72 V) 3 Poles in Series, 60 °C 60 A | (72 V) 3 Poles in Series, 70 °C 50 A
Rated Operational Current DC-3 (Ie)
(110 V) 2 Poles in Series, 40 °C 70 A | (110 V) 2 Poles in Series, 60 °C 60 A | (110 V) 2 Poles in Series, 70 °C 50 A | (110 V) 3 Poles in Series, 40 °C 70 A | (110 V) 3 Poles in Series, 60 °C 60 A | (110 V) 3 Poles in Series, 70 °C 50 A | (220 V) 3 Poles in Series, 40 °C 70 A | (220 V) 3 Poles in Series, 60 °C 60 A | (220 V) 3 Poles in Series, 70 °C 50 A | (72 V) 1-Pole, 40 °C 70 A | (72 V) 1-Pole, 60 °C 60 A | (72 V) 1-Pole, 70 °C 50 A | (72 V) 2 Poles in Series, 40 °C 70 A | (72 V) 2 Poles in Series, 60 °C 60 A | (72 V) 2 Poles in Series, 70 °C 50 A | (72 V) 3 Poles in Series, 40 °C 70 A | (72 V) 3 Poles in Series, 60 °C 60 A | (72 V) 3 Poles in Series, 70 °C 50 A
Rated Operational Current DC-5 (Ie)
(110 V) 2 Poles in Series, 40 °C 70 A | (110 V) 2 Poles in Series, 60 °C 60 A | (110 V) 2 Poles in Series, 70 °C 50 A | (110 V) 3 Poles in Series, 40 °C 70 A | (110 V) 3 Poles in Series, 60 °C 60 A | (110 V) 3 Poles in Series, 70 °C 50 A | (220 V) 3 Poles in Series, 40 °C 70 A | (220 V) 3 Poles in Series, 60 °C 60 A | (220 V) 3 Poles in Series, 70 °C 50 A | (72 V) 1-Pole, 40 °C 70 A | (72 V) 1-Pole, 60 °C 60 A | (72 V) 1-Pole, 70 °C 50 A | (72 V) 2 Poles in Series, 40 °C 70 A | (72 V) 2 Poles in Series, 60 °C 60 A | (72 V) 2 Poles in Series, 70 °C 50 A | (72 V) 3 Poles in Series, 40 °C 70 A | (72 V) 3 Poles in Series, 60 °C 60 A | (72 V) 3 Poles in Series, 70 °C 50 A
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W | (48 V) 2.8 A / 134 W | (72 V) 1 A / 72 W | (110 V) 0.55 A / 60 W | (125 V) 0.55 A / 69 W | (220 V) 0.27 A / 60 W | (250 V) 0.27 A / 68 W | (400 V) 0.15 A / 60 W | (500 V) 0.13 A / 65 W | (600 V) 0.1 A / 60 W
Rated Operational Power AC-3 (Pe)
(400 V) 18.5 kW | (415 V) 22 kW | (440 V) 22 kW | (500 V) 22 kW | (690 V) 22 kW | (380 / 400 V) 18.5 kW | (220 / 230 / 240 V) 11 kW
Rated Operational Power AC-3e (Pe)
(415 V) 22 kW | (440 V) 22 kW | (500 V) 22 kW | (690 V) 22 kW | (380 / 400 V) 18.5 kW | (220 / 230 / 240 V) 11 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 600 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A | for 0.1 s 140 A | for 1 s 100 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 V | acc. to IEC 60947-5-1 690 V | acc. to UL/CSA 600 V
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-15) 1200 cycles per hour | (AC-2 / AC-4) 150 cycles per hour | (AC-3) 1200 cycles per hour | (DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 24 ... 60 V | 60 Hz 24 ... 60 V | DC Operation 20 ... 60 V
Coil Consumption
Average Holding Value 50 / 60 Hz 4 V·A | Average Holding Value DC 2 W
Power Loss
at Rated Operating Conditions AC-1 per Pole 3 W | at Rated Operating Conditions AC-3 per Pole 1 W
Operate Time
Between Coil De-energization and NC Contact Closing 19 ... 105 ms | Between Coil De-energization and NO Contact Opening 17 ... 100 ms | Between Coil Energization and NC Contact Opening 38 ... 95 ms | Between Coil Energization and NO Contact Closing 42 ... 100 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 4 ... 35 mm² | Flexible with Insulated Ferrule 1/2x 4 ... 35 mm² | Rigid Stranded 1/2x 6 ... 35 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Auxiliary Circuit 10 mm | Control Circuit 10 mm | Main Circuit 16 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Recommended Screw Driver
Pozidriv PZ
Tightening Torque
Auxiliary Circuit 1.2 N·m | Control Circuit 1.2 N·m | Main Circuit 4 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
NEMA Size
2
Continuous Current Rating NEMA
45 A
Horsepower Rating NEMA
(115 V AC) Single Phase 3 Hp | (200 V AC) Three Phase 10 Hp | (230 V AC) Single Phase 7-1/2 Hp | (230 V AC) Three Phase 15 Hp | (460 V AC) Three Phase 25 Hp | (575 V AC) Three Phase 25 Hp
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 60 A
Horsepower Rating UL/CSA
(120 V AC) Single Phase 3 hp | (200 ... 208 V AC) Three Phase 10 hp | (220 ... 240 V AC) Three Phase 15 hp | (240 V AC) Single Phase 7-1/2 hp | (440 ... 480 V AC) Three Phase 30 hp | (550 ... 600 V AC) Three Phase 40 hp
Connecting Capacity Main Circuit UL/CSA
Rigid Stranded 1/2x 10-2 AWG
Connecting Capacity Control Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG | Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSA
Auxiliary Circuit 11 in·lb | Control Circuit 11 in·lb | Main Circuit 35 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 34 A | (200 ... 208 V AC) Three Phase 32.2 A | (220 ... 240 V AC) Three Phase 42 A | (240 V AC) Single Phase 40 A | (440 ... 480 V AC) Three Phase 41 A | (550 ... 600 V AC) Three Phase 40 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -40 ... 70 °C | Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Shock and Vibration Withstand acc. to IEC 61373
Category 1, Class B
Pollution Degree
3
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
Yes
End Of Life Disassembling Instructions
End of life instruction AF(S)40/52/65/80/96(B)(RT) Contactors
Environmental Product Declaration - EPD
Environmental Product Declaration AF(S)40(B), AF(S)52(B), AF(S)65(B) (FR)
Sustainable Material Content in Packaging (wt. %)
FSC Recycled Paper - 94.6 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 28.2 %
A2L Certificate – UL
UL-US Certificate of Compliance AF40 ... AF96 3-pole contactors - UL 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers | UL-CA Certificate of Compliance AF40 ... AF96 3-pole contactors - CSA C22.2 No. 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers
CB Certificate
CB Certificate AF(S)40(B), (S)AF52(B), AF(S)65(B) 3 and 4-pole contactors
CCC Certificate
CQC Certificate, Contactor, AF*40-30-**-**, AF40-40-**-**, AF40-22-**-**, AF*52-30-**-**, AF52-40-**-**,AF*65-30-**-**, Made in France
Declaration of Conformity - CE
EU Declaration of Conformity AF09 ... AF38(Z)B..(K), AF40B ... AF96B 3 and 4-pole contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09 ... AF38(Z)B..(K), AF40B ... AF96B 3 and 4-pole contactors
UL Certificate
UL-US-L312527-1141-10303102-9 | UL-CA-L312527-4141-10303102-9
Package Level 1 Units
box 1 piece
Package Level 1 Width
150 mm
Package Level 1 Depth / Length
150 mm
Package Level 1 Height
97 mm
Package Level 1 Gross Weight
1.11 kg
Package Level 1 EAN
3471523024779
Package Level 2 Units
box 10 piece
Package Level 2 Width
250 mm
Package Level 2 Depth / Length
300 mm
Package Level 2 Height
300 mm
Package Level 2 Gross Weight
11.1 kg
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
Feature → Business Impact → Application: The AF-style technology delivers a wide control voltage range (24-60 VAC/50/60 Hz and 20-60 VDC) with built-in surge protection, which reduces start-up variability and energy waste in panel power supplies, benefiting motor control panels in conveyor systems and process lines. This translates to tighter uptime and lower energy costs in manufacturing environments. Feature → Business Impact → Application: The 3-pole configuration with one NO and one NC auxiliary contact simplifies interlocking and status signaling, cutting wiring complexity and enabling more reliable motor protection schemes in HVAC, pumps, and steel mill drives. Feature → Business Impact → Application: Block-type, compact design with screw terminals plus compatible DIN rail mounting (TH35) allows fast, vibration-resistant installations and easy retrofits in existing control cabinets, improving serviceability in rail signaling and material handling. Feature → Business Impact → Application: Broad compliance (IEC/EN 60947-1, 60947-4-1; UL/CSA) provides proven safety and performance for cross-border projects, supporting procurement with fewer certifications to manage, while high short-time withstand and maximum breaking capacity support demanding starting currents in conveyors and hoists. Feature → Business Impact → Application: The capacity to extend with add-on auxiliary contact blocks and a wide array of accessories offers scalable automation, enabling future expansion without replacing the base contactor in industrial plants and rolling stock systems.
Get a Quick Quote for a ABB 1SBL347061R1111
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SBL347061R1111?
Enquire Now
FAQs
The 1SBL347061R1111 is designed for DIN rail mounting using TH35-15 or TH35-7.5 standards, and it also supports screw mounting. This versatility simplifies retrofits and new installations, reduces panel space requirements, and speeds commissioning in control cabinets for conveyors, pumps, and industrial drives.
Key ratings include 3 main contacts with 1 NO and 1 NC auxiliary contact, rated for 690 V auxiliary and main circuits, 50/60 Hz control, coil range of 24-60 VAC or 20-60 VDC. AC-1 rated current up to 70 A at 690 V, AC-3 up to 40 A at common voltages, and high short-time withstand currents for demanding start transients.
Yes. Data sheets reference rolling stock motor protection and control applications, with application notes and standards alignment (IEC/EN 60947-1, 60947-4-1, EN 50155 considerations) that support railway environments, along with UL/CSA listings for global compliance.
The product carries IEC/EN 60947-1 and 60947-4-1 standards, UL 60335-2-40, CSA variants, CE/UKCA declarations, CB certificates, and RoHS/REACH declarations. This broad certification set helps streamline cross-border procurement and conformity testing for customer installations.
AF technology provides a wide control voltage range that tolerates voltage variations, reducing panel energy consumption and avoiding nuisance trips. Built-in surge protection lowers wiring and protection components, while add-on auxiliary blocks enable scalable maintenance and expansion without replacing the base contactor.