ABB 1SBL347261R1100 Block Contactor - AF Technology
Part Number: 1SBL347261R1100
Quick Summary
Block Contactor is a rugged motor switching device used to control 4-pole motors in manufacturing and packaging lines. It is designed to help engineers overcome voltage fluctuations by employing a wide control voltage range and built-in surge protection that reduce panel energy waste. With IEC/EN 60947-4-1, UL 60335-2-40 and CSA compatibility, this ABB AF-based contactor meets essential safety and performance standards while staying compact enough for dense control panels. For OEMs and system integrators, its modular block design and add-on auxiliary contact blocks simplify expansion and maintenance, delivering dependable motor control with lower total cost of ownership. In short, it combines reliability with ease of installation for industrial automation.
Product Information
Extended Description
1SBL347261R1100 ABB: The AF40B-40-00-11 is a 4 pole - 690 V IEC or 600 UL contactor with screw terminals, controlling motors up to 18.5 kW / 400 V AC (AC-3) and switching power circuits up to 70 A (AC-1) or 60 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (24-60 V 50/60 Hz and 20-60 V DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
Motor control and protection for Rolling stock application_PDF
Instructions and Manuals
Installation instructions AF(C)40(B)...80(B)-40/22 Contactors, CA4, CAL4, CAT4, CC4, LDC4 Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
70 mm
Product Net Depth / Length
113.5 mm
Product Net Height
125.5 mm
Product Net Weight
1.21 kg
Number of Main Contacts NO
4
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Number of Poles
4P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives.
Rated Operational Voltage
Main Circuit 690 V
Rated Frequency (f)
Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 105 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 70 A | (690 V) 60 °C 60 A | (690 V) 70 °C 50 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 40 A | (440 V) 60 °C 40 A | (500 V) 60 °C 35 A | (690 V) 60 °C 25 A | (380 / 400 V) 60 °C 40 A | (220 / 230 / 240 V) 60 °C 40 A
Rated Operational Power AC-3 (Pe)
(415 V) 22 kW | (440 V) 22 kW | (500 V) 22 kW | (690 V) 22 kW | (380 / 400 V) 18.5 kW | (220 / 230 / 240 V) 11 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 600 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 V | acc. to UL/CSA 600 V
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 24 ... 60 V | 60 Hz 24 ... 60 V | DC Operation 20 ... 60 V
Coil Consumption
Average Holding Value 50 / 60 Hz 4 V·A | Average Holding Value DC 2 W
Power Loss
at Rated Operating Conditions AC-1 per Pole 3 W | at Rated Operating Conditions AC-3 per Pole 1 W
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 4 ... 35 mm² | Flexible with Insulated Ferrule 1/2x 4 ... 35 mm² | Rigid Stranded 1/2x 6 ... 35 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Auxiliary Circuit 0 mm | Control Circuit 10 mm | Main Circuit 16 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Recommended Screw Driver
Pozidriv PZ
Tightening Torque
Control Circuit 1.2 N·m | Main Circuit 4 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
Continuous Current Rating NEMA
0 A
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 60 A
Connecting Capacity Main Circuit UL/CSA
Rigid Stranded 1/2x 10-2 AWG
Connecting Capacity Control Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG | Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSA
Control Circuit 11 in·lb | Main Circuit 35 in·lb
Ambient Air Temperature
Close to Contactor for Storage -60 ... +80 °C | Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Shock and Vibration Withstand acc. to IEC 61373
Category 1, Class B
Pollution Degree
3
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
Yes
End Of Life Disassembling Instructions
End of life instruction AF(S)40/52/65/80/96(B)(RT) Contactors
Environmental Product Declaration - EPD
Environmental Product Declaration AF(S)40(B), AF(S)52(B), AF(S)65(B) (FR)
Sustainable Material Content in Packaging (wt. %)
FSC Recycled Paper - 94.6 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 28.2 %
A2L Certificate – UL
UL-US Certificate of Compliance AF40 ... AF96 3-pole contactors - UL 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers | UL-CA Certificate of Compliance AF40 ... AF96 3-pole contactors - CSA C22.2 No. 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers
CB Certificate
CB Certificate AF(S)40(B), (S)AF52(B), AF(S)65(B) 3 and 4-pole contactors
CCC Certificate
CQC Certificate, Contactor, AF*40-30-**-**, AF40-40-**-**, AF40-22-**-**, AF*52-30-**-**, AF52-40-**-**,AF*65-30-**-**, Made in France
Declaration of Conformity - CE
EU Declaration of Conformity AF09 ... AF38(Z)B..(K), AF40B ... AF96B 3 and 4-pole contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09 ... AF38(Z)B..(K), AF40B ... AF96B 3 and 4-pole contactors
UL Certificate
UL-US Certificate of Compliance AF40(B)...80(B) 4-pole contactors | UL-CA Certificate of Compliance AF40(B)...80(B) 4-pole contactors
Package Level 1 Units
box 1 piece
Package Level 1 Width
150 mm
Package Level 1 Depth / Length
150 mm
Package Level 1 Height
103 mm
Package Level 1 Gross Weight
1.32 kg
Package Level 1 EAN
3471523024847
Package Level 2 Units
box 8 piece
Package Level 2 Width
250 mm
Package Level 2 Depth / Length
300 mm
Package Level 2 Height
300 mm
Package Level 2 Gross Weight
10.56 kg
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
The AF technology enables a wide control voltage range, reducing energy consumption and improving reliability in networks with fluctuations, which translates to lower operating costs for industrial automation projects. Feature → Business Impact → Application: 4-pole, 690 V main circuit with AC-1 70 A / AC-3 25 A at 690 V enables robust motor switching for conveyors and pumps; this supports compact panel design with fewer components and easier service in machine rooms. The screw-terminal wiring and DIN rail mounting (TH35-15) simplify installation and future upgrades, saving commissioning time on new lines and retrofit projects. The device offers built-in surge protection, protecting both drives and loads from transients common in heavy industry, reducing downtime and maintenance costs. The compact block layout supports add-on auxiliary contact blocks, enabling scalable expansion for complex machine controls without replacing the base unit. With 24–60 V control voltage and 20–60 V DC options, it tolerates control network variation, ensuring consistent operation in environments with unstable power quality.
Get a Quick Quote for a ABB 1SBL347261R1100
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SBL347261R1100?
Enquire Now
FAQs
Mount the unit on a TH35-15 DIN rail or secure it with two screws (M4 or M6) placed diagonally. Connect the main circuit with flexible ferrule 1/2x 6–35 mm² or rigid 1/2x 6–35 mm² and the control circuit with flexible ferrule 0.75–2.5 mm² or rigid 1/2x 1–2.5 mm². Leave 10 mm stripping for control, 16 mm for main circuit, and ensure IP20 coil terminals are compliant with enclosure standards.
The coil supports 24–60 V AC (50/60 Hz) and 20–60 V DC operation, with holding values of 4 V·A (50/60 Hz) and 2 W (DC). This enables broad compatibility with common control networks while maintaining reliable operation across voltage variations typical in industrial panels.
Yes. The device is designed for rolling stock applications and general motor control in industrial settings, offering 4-pole switching, high main circuit ratings up to 690 V, and robust protection. Its compact AF technology and add-on auxiliary contact blocks make it suitable for space-constrained control cabinets in rolling stock and production lines.
Expect IEC/EN 60947-1 and IEC/EN 60947-4-1 along with UL 60335-2-40, UL 60947-1, UL 60947-4-1, CSA equivalents, CE/UKCA declarations, RoHS/REACH compliance, and WEEE considerations. This combination supports global manufacturing requirements and ensures safety, interoperability, and environmental responsibility.
Maintenance benefits come from built-in surge protection, a compact block design for easier wiring, and expandability with auxiliary contact blocks, reducing downtime and part counts. Return on investment is driven by energy efficiency from AF technology, reduced panel footprint, and lower installation labor costs during upgrades or line changes.