ABB AF40B-22-00-13 Block Contactor - 690V IEC/UL

Part Number: 1SBL347561R1300
Manufacturer
ABB
Part number
1SBL347561R1300

Quick Summary

The ABB AF40B-22-00-13 block contactor is designed to reliably control three-phase motors up to 18.5 kW at 400 V AC. In demanding panel environments, voltage fluctuations can cause nuisance tripping and inconsistent performance; this device addresses that by leveraging AF technology and a wide control voltage range. It complies with IEC/EN 60947-1, IEC/EN 60947-4-1, and UL 60335-2-40 (with CSA recognition), providing robust safety and interoperability in global installations. By integrating surge protection and a compact, extendable block design, the AF40B reduces panel footprint and enables easy expansion with auxiliary contact blocks, delivering measurable cost savings and faster commissioning for industrial automation projects.

Product Information

Extended Description

1SBL347561R1300 ABB: The AF40B-22-00-13 is a 4 pole - 690 V IEC or 600 UL contactor with screw terminals, controlling motors up to 18.5 kW / 400 V AC (AC-3) and switching power circuits up to 70 A (AC-1) or 60 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
Motor control and protection for Rolling stock application_PDF
Instructions and Manuals
Installation instructions AF(C)40(B)...80(B)-40/22 Contactors, CA4, CAL4, CAT4, CC4, LDC4 Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
70 mm
Product Net Depth / Length
113.5 mm
Product Net Height
125.5 mm
Product Net Weight
1.16 kg
Number of Main Contacts NO
2
Number of Main Contacts NC
2
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Number of Poles
4P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives.
Rated Operational Voltage
Main Circuit 690 V
Rated Frequency (f)
Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 105 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 70 A | (690 V) 60 °C 60 A | (690 V) 70 °C 50 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 40 A | (440 V) 60 °C 40 A | (500 V) 60 °C 35 A | (690 V) 60 °C 25 A | (380 / 400 V) 60 °C 40 A | (220 / 230 / 240 V) 60 °C 40 A
Rated Operational Power AC-3 (Pe)
(415 V) 22 kW | (440 V) 22 kW | (500 V) 22 kW | (690 V) 22 kW | (380 / 400 V) 18.5 kW | (220 / 230 / 240 V) 11 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 600 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 V | acc. to UL/CSA 600 V
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 100 ... 250 V | 60 Hz 100 ... 250 V | DC Operation 100 ... 250 V
Coil Consumption
Average Holding Value 50 / 60 Hz 4 V·A | Average Holding Value DC 2 W
Power Loss
at Rated Operating Conditions AC-1 per Pole 3 W | at Rated Operating Conditions AC-3 per Pole 1 W
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 4 ... 35 mm² | Flexible with Insulated Ferrule 1/2x 4 ... 35 mm² | Rigid Stranded 1/2x 6 ... 35 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Auxiliary Circuit 0 mm | Control Circuit 10 mm | Main Circuit 16 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Recommended Screw Driver
Pozidriv PZ
Tightening Torque
Control Circuit 1.2 N·m | Main Circuit 4 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
Continuous Current Rating NEMA
0 A
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 60 A
Connecting Capacity Main Circuit UL/CSA
Rigid Stranded 1/2x 10-2 AWG
Connecting Capacity Control Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG | Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSA
Control Circuit 11 in·lb | Main Circuit 35 in·lb
Ambient Air Temperature
Close to Contactor for Storage -60 ... +80 °C | Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Shock and Vibration Withstand acc. to IEC 61373
Category 1, Class B
Pollution Degree
3
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
Yes
End Of Life Disassembling Instructions
End of life instruction AF(S)40/52/65/80/96(B)(RT) Contactors
Environmental Product Declaration - EPD
Environmental Product Declaration AF(S)40(B), AF(S)52(B), AF(S)65(B) (FR)
Sustainable Material Content in Packaging (wt. %)
FSC Recycled Paper - 94.6 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 28.2 %
A2L Certificate – UL
UL-US Certificate of Compliance AF40 ... AF96 3-pole contactors - UL 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers | UL-CA Certificate of Compliance AF40 ... AF96 3-pole contactors - CSA C22.2 No. 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers
CB Certificate
CB Certificate AF(S)40(B), (S)AF52(B), AF(S)65(B) 3 and 4-pole contactors
CCC Certificate
CQC Certificate, Contactor, AF*40-30-**-**, AF40-40-**-**, AF40-22-**-**, AF*52-30-**-**, AF52-40-**-**,AF*65-30-**-**, Made in France
Declaration of Conformity - CE
EU Declaration of Conformity AF09 ... AF38(Z)B..(K), AF40B ... AF96B 3 and 4-pole contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09 ... AF38(Z)B..(K), AF40B ... AF96B 3 and 4-pole contactors
UL Certificate
UL-US Certificate of Compliance AF40(B)...80(B) 4-pole contactors | UL-CA Certificate of Compliance AF40(B)...80(B) 4-pole contactors
Package Level 1 Units
box 1 piece
Package Level 1 Width
150 mm
Package Level 1 Depth / Length
150 mm
Package Level 1 Height
103 mm
Package Level 1 Gross Weight
1.27 kg
Package Level 1 EAN
3471523024946
Package Level 2 Units
box 8 piece
Package Level 2 Width
250 mm
Package Level 2 Depth / Length
300 mm
Package Level 2 Height
300 mm
Package Level 2 Gross Weight
10.16 kg
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
Feature: Wide control voltage range (100-250 V AC/60 Hz, 100-250 V AC/50 Hz and DC operation) → Business Impact: Minimal control voltage sensitivity across supply variations reduces coil burnout, energy waste, and panel heat; Application: Ideal for industrial environments with volatile power quality. The AF technology ensures consistent operation even with voltage swings. Feature: Four poles with 2 NO and 2 NC main contacts → Business Impact: Enhanced motor control and protection for common start/stop sequences; Application: 4P configuration suits standard motor loads in automation panels. Feature: Built-in surge protection → Business Impact: Increases reliability, reduces external protection components, and extends device life; Application: Critical in OEM machinery and rolling stock applications. Feature: Compact block design with DIN rail mounting TH35-15 → Business Impact: Saves panel space and simplifies installation; Application: Quick, scalable deployments in control cabinets. Feature: Extendable with auxiliary contact blocks → Business Impact: Flexible control schemes and fault monitoring without replacing the base device; Application: Customizable safety and signaling configurations. Feature: Mounting and connection specifics (IP20 coil terminals, IP10 main terminals; screw terminals) → Business Impact: Safe, durable connections with straightforward maintenance; Application: Suitable for rigid and flexible conductor terminations up to 35 mm² main circuit and 2.5 mm² control circuit. Feature: Rated Operation and ratings (AC-1 up to 70 A at 690 V; AC-3 up to 40 A at 415–690 V) → Business Impact: Clear, verifiable motor switching capacity; Application: Clear fit for standard industrial motors and conveyors. Feature: Compliance and lifecycle considerations (REACH, RoHS, UL/CSA, EPD) → Business Impact: Regulatory alignment and sustainability messaging for procurement; Application: Global deployments with responsible sourcing. Insight: The device’s performance data supports engineers in design reviews, helping to reduce risk during commissioning and ensuring long-term operational reliability in harsh environments.

Get a Quick Quote for a ABB 1SBL347561R1300

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SBL347561R1300? Enquire Now

FAQs

The AF40B-22-00-13 is mounted on a TH35-15 DIN rail (35 x 15 mm). It can also be screwed to a panel using 2 x M4 or 2 x M6 screws placed diagonally. For installation, ensure the device is securely seated on the rail and torque the connections to 4 N·m for the main circuit and 1.2 N·m for the control circuit to maintain reliability and compliance.
Main circuit rated current AC-1 at 690 V is 70 A (40 °C), 60 A (60 °C), and 50 A (70 °C). For AC-3 at 690 V, the device is rated to 25 A. Rated insulating voltage is 690 V, with a coil voltage range of 100–250 V for AC or DC operation. These figures support motor control and switching in high-voltage applications.
Yes. The coil accepts 100–250 V for 50 Hz or 60 Hz operation and also supports DC control within the same voltage range. This wide tolerance helps accommodate varying control signals and unstable networks, reducing the need for multiple accessory components and enabling simpler control schemes.
The AF40B-22-00-13 complies with IEC/EN 60947-1 and 60947-4-1, UL 60335-2-40, CSA and related safety standards. Documentation includes CE and UKCA declarations, UL and CSA certificates, and RoHS/REACH declarations. For specific applicability, consult ABB literature or contact a sales engineer to verify alignment with your regulatory requirements.
Built-in surge protection, a wide control voltage range, and a compact, extendable design reduce panel complexity and part count. The ability to add auxiliary contact blocks without replacing the base unit simplifies upgrades, while robust ratings and regulatory compliance minimize downtime and maintenance costs in demanding environments.