ABB 1SBL361201R8100 Block Contactor - 690V IEC/UL
Part Number: 1SBL361201R8100
Quick Summary
ABB 1SBL361201R8100 is a 4-pole block contactor for AC motor control in industrial automation panels. This compact device handles main power up to 690 V and supports 100 A in IEC AC-1 duty, with a 24 V coil for reliable control. Engineers value its rugged IEC/EN and UL certifications, including CE declarations, ensuring global compliance in diverse environments. The design emphasizes ease of installation and maintenance, offering screw terminals, a block-type layout, and compatibility with add-on auxiliary blocks. For procurement teams, this translates to streamlined panel wiring, scalable control architectures, and predictable performance across international projects, all while preserving space and reducing total cost of ownership. Secondary keywords such as 4-pole contactor and DIN rail-ready mounting reinforce its suitability for modern automation lines.
Product Information
Extended Description
1SBL361201R8100 ABB: The AFC52-40-00-81 is a 4-pole (4 N.O) - 690 V IEC or 600 V UL contactor with Screw terminals, mainly controlling power circuits up to 100 A (IEC AC-1) or 80 A UL general use. Within the AF platform, AFC contactors offer an optimized operating time for AC controlled applications with electromagnetic coil (control voltage : 24 V AC 50 Hz / 24 V AC 60 Hz). AFC contactors have a block type design and can be easily extended with add-on auxiliary contact blocks and a wide range of additionnal accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
1SBC100219C0201 AFC contactors for AC control applications_Catalog PDF
Instructions and Manuals
Installation instructions AF(C)40(B)...80(B)-40/22 Contactors, CA4, CAL4, CAT4, CC4, LDC4 Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
Product Net Width
70 mm
Product Net Depth / Length
119.5 mm
Product Net Height
113.5 mm
Product Net Weight
1.18 kg
Number of Main Contacts NO
4
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Number of Poles
4P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60947-1, CSA C22.2 No. 60947-4-1
Rated Operational Voltage
Main Circuit 690 V
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 105 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 100 A | (690 V) 60 °C 80 A | (690 V) 70 °C 70 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 53 A | (440 V) 60 °C 53 A | (500 V) 60 °C 45 A | (690 V) 60 °C 35 A | (380 / 400 V) 60 °C 53 A | (220 / 230 / 240 V) 60 °C 53 A
Rated Operational Power AC-3 (Pe)
(415 V) 30 kW | (440 V) 30 kW | (500 V) 30 kW | (690 V) 30 kW | (380 / 400 V) 22 kW | (220 / 230 / 240 V) 15 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
Auxiliary Circuit 6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-2 / AC-4) 0 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 24 V | 60 Hz 24 V
Coil Consumption
Average Holding Value 50 / 60 Hz 20 V·A | Average Pull-in Value 50 Hz 150 V·A | Average Pull-in Value 60 Hz 151 V·A
Power Loss
at Rated Operating Conditions AC-1 per Pole 6.3 W | at Rated Operating Conditions AC-3 per Pole 1.7 W
Operate Time
Between Coil De-energization and NO Contact Opening 4 ... 14 ms | Between Coil Energization and NO Contact Closing 7 ... 21 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 4 ... 35 mm² | Flexible with Insulated Ferrule 1/2x 4 ... 35 mm² | Rigid 1/2x 6 ... 3 5 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Control Circuit 10 mm | Main Circuit 16 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Recommended Screw Driver
Main Circuit 6.5 | Main Circuit Slot | Control Circuit 5.5 | Control Circuit Slot
Tightening Torque
Control Circuit 1.2 N·m | Main Circuit 4 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 80 A
Tightening Torque UL/CSA
Control Circuit 11 in·lb | Main Circuit 35 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 3 A | (200 ... 208 V AC) Three Phase 15 A | (220 ... 240 V AC) Three Phase 20 A | (240 V AC) Single Phase 10 A | (440 ... 480 V AC) Three Phase 40 A | (550 ... 600 V AC) Three Phase 50 A
Ambient Air Temperature
Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C | Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Pollution Degree
3
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
BV Certificate
BV_2634H36994B1
CB Certificate
CB Certificate AFC40, AFC52, AFC65 3 or 4-pole contactors
CCC Certificate
CCC Declaration of Conformity, Contactor, AF(C)40, AF52(C), AF65(C),AFC78 Made in China
CQC Certificate
CQC Certificate, Contactor, AF40, AF52, AF65, AFC40, AFC52, AFC65, Made in China
Declaration of Conformity - CE
EU Declaration of Conformity AFC09 ... AFC80 4-pole Contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AFC09 ... AFC80 4-pole Contactors
DNV Certificate
DNV Certificate AFC09...96 3-pole & AFC09...80 4-pole contactors with screw, push-in terminals
RINA Certificate
Rina Certificate for AFC09...AFC96 3 pole and 4 pole contactors, NFC relays ,screw and spring terminals
UL Certificate
UL-CA Certificate of Compliance AFC40 ... AFC80 4-pole contactors | UL-US Certificate of Compliance AFC40 ... AFC80 4-pole contactors
Package Level 1 Units
box 1 piece
Package Level 1 Width
146.5 mm
Package Level 1 Depth / Length
96.5 mm
Package Level 1 Height
146.5 mm
Package Level 1 Gross Weight
1.3 kg
Package Level 1 EAN
3471523019300
Package Level 3 Units
192 piece
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4755 >> Contactors
Feature → Business Impact → Application: The 4 NO main contacts configured in a 4P block contactor deliver consolidated switching for multi-line power circuits, enabling up to 100 A at 690 V in IEC AC-1. This reduces the need for multiple devices, saving panel space and simplifying wiring in motor control centers used in packaging, material handling, or flow-line automation. Application: control of conveyors, pumps, and fans where reliable AC-1 switching is essential. Feature → Business Impact → Application: A 24 V AC coil (50/60 Hz) with optimized pull-in and holding values minimizes control power usage and improves switching reliability, lowering energy costs in large control cabinets. Application: start/stop sequences for heavy-duty machines with frequent cycling, such as extruders and mixers. Feature → Business Impact → Application: Screw terminals for main and control circuits support flexible conductor sizes (main 6–35 mm², control 0.75–2.5 mm²) and secure, vibration-resistant connections. Application: field wiring in harsh industrial environments where robust terminations reduce maintenance. Feature → Business Impact → Application: TH35-15 DIN rail mounting simplifies retrofits and new installations, enabling fast deployment in standardized control panels. Application: modular panel designs and rapid installation in OEM equipment. Feature → Business Impact → Application: The block design accepts add-on auxiliary contact blocks and accessories, delivering scalable control logic without replacing the base device. Application: future-proofing lines for expanding control circuits or implementing interlock schemes. Feature → Business Impact → Application: Compliance and protection through IEC/EN 60947-1, 60947-4-1 and UL/CSA listings; IP20 coil terminals and IP10 main terminals support safe operation in common industrial environments. Application: machines deployed globally with strict regulatory requirements. Feature → Business Impact → Application: Rated operational currents and high breaking capacity provide reliability in motor control and power distribution, reducing downtime and extending service intervals. Application: critical power switching in pumps, compressors, and assembly lines.
Get a Quick Quote for a ABB 1SBL361201R8100
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SBL361201R8100?
Enquire Now
FAQs
This 4-pole block contactor is designed for TH35-15 DIN rails. To install, snap the device into the rail, ensure the mounting is level, and connect main conductors to the 70 mm wide, screw-terminal block. Secure control wiring to the 24 V coil terminals and verify that the rail has proper clearance for heat dissipation and mechanical movement.
The coil is 24 V AC (50/60 Hz). The main circuit is rated up to 690 V, with 4 NO contacts (4P). In IEC AC-1 service it supports up to 100 A at 690 V, and it also provides UL/CSA compatibility with related ratings for standard control applications.
Yes. With 4 NO main contacts and a 690 V main circuit rating, it is appropriate for AC-1 duty in motors and general power circuits. Its 4-pole configuration and compatibility with auxiliary contact blocks enable various interlocking and sequencing schemes common in conveyors, pumps, and air handling units.
The device complies with IEC/EN 60947-1 and 60947-4-1, UL 60947-1 and 60947-4-1, CSA equivalents, and CE declarations. It also carries RoHS/WEEE compliance and related declarations, ensuring broad regulatory acceptance across Europe, North America, and other regions.
Key factors include screw-terminal connections for secure wiring, compact DIN-rail mounting for efficient panel layouts, and accessory compatibility for scalable control. Tightening torques are 4 N·m on the main circuit and 1.2 N·m on the control circuit; keep coil cleanliness and ambient temperatures within rated ranges to minimize unexpected coil failures.