ABB 1SBL361201R8500 Contactor - 4P 690V IEC/UL

Part Number: 1SBL361201R8500
Manufacturer
ABB
Part number
1SBL361201R8500

Quick Summary

ABB Contactor 1SBL361201R8500 is a four-pole AC switch designed for motor and power circuit control in industrial automation. This device helps reduce wiring complexity and space constraints with a compact block design and screw terminals. It complies with IEC/EN 60947-4-1, UL/CSA, and CE/UKCA declarations, supporting global installations and fast regulatory approvals. The coil accepts 380-400 V AC at 50 Hz or 400-415 V AC at 60 Hz, enabling flexible control from regional supplies, while the 690 V main circuit rating supports a wide power range. Together with reliable operating times and clear installation guidance, it offers predictable uptime and streamlined procurement for panel builders and OEMs.

Product Information

Extended Description

1SBL361201R8500 ABB: The AFC52-40-00-85 is a 4-pole (4 N.O) - 690 V IEC or 600 V UL contactor with Screw terminals, mainly controlling power circuits up to 100 A (IEC AC-1) or 80 A UL general use. Within the AF platform, AFC contactors offer an optimized operating time for AC controlled applications with electromagnetic coil (control voltage : 380 ... 400 V AC 50 Hz / 400 ... 415 V AC 60 Hz). AFC contactors have a block type design and can be easily extended with add-on auxiliary contact blocks and a wide range of additionnal accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
1SBC100219C0201 AFC contactors for AC control applications_Catalog PDF
Instructions and Manuals
Installation instructions AF(C)40(B)...80(B)-40/22 Contactors, CA4, CAL4, CAT4, CC4, LDC4 Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
Product Net Width
70 mm
Product Net Depth / Length
119.5 mm
Product Net Height
113.5 mm
Product Net Weight
1.18 kg
Number of Main Contacts NO
4
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Number of Poles
4P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60947-1, CSA C22.2 No. 60947-4-1
Rated Operational Voltage
Main Circuit 690 V
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 105 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 100 A | (690 V) 60 °C 80 A | (690 V) 70 °C 70 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 53 A | (440 V) 60 °C 53 A | (500 V) 60 °C 45 A | (690 V) 60 °C 35 A | (380 / 400 V) 60 °C 53 A | (220 / 230 / 240 V) 60 °C 53 A
Rated Operational Power AC-3 (Pe)
(415 V) 30 kW | (440 V) 30 kW | (500 V) 30 kW | (690 V) 30 kW | (380 / 400 V) 22 kW | (220 / 230 / 240 V) 15 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
Auxiliary Circuit 6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-2 / AC-4) 0 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 380 ... 400 V | 60 Hz 400 ... 415 V
Coil Consumption
Average Holding Value 50 / 60 Hz 20 V·A | Average Pull-in Value 50 Hz 150 V·A | Average Pull-in Value 60 Hz 151 V·A
Power Loss
at Rated Operating Conditions AC-1 per Pole 6.3 W | at Rated Operating Conditions AC-3 per Pole 1.7 W
Operate Time
Between Coil De-energization and NO Contact Opening 4 ... 14 ms | Between Coil Energization and NO Contact Closing 7 ... 21 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 4 ... 35 mm² | Flexible with Insulated Ferrule 1/2x 4 ... 35 mm² | Rigid 1/2x 6 ... 3 5 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Control Circuit 10 mm | Main Circuit 16 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Recommended Screw Driver
Main Circuit 6.5 | Main Circuit Slot | Control Circuit 5.5 | Control Circuit Slot
Tightening Torque
Control Circuit 1.2 N·m | Main Circuit 4 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 80 A
Tightening Torque UL/CSA
Control Circuit 11 in·lb | Main Circuit 35 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 3 A | (200 ... 208 V AC) Three Phase 15 A | (220 ... 240 V AC) Three Phase 20 A | (240 V AC) Single Phase 10 A | (440 ... 480 V AC) Three Phase 40 A | (550 ... 600 V AC) Three Phase 50 A
Ambient Air Temperature
Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C | Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Pollution Degree
3
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
BV Certificate
BV_2634H36994B1
CB Certificate
CB Certificate AFC40, AFC52, AFC65 3 or 4-pole contactors
CCC Certificate
CCC Declaration of Conformity, Contactor, AF(C)40, AF52(C), AF65(C),AFC78 Made in China
CQC Certificate
CQC Certificate, Contactor, AF40, AF52, AF65, AFC40, AFC52, AFC65, Made in China
Declaration of Conformity - CE
EU Declaration of Conformity AFC09 ... AFC80 4-pole Contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AFC09 ... AFC80 4-pole Contactors
DNV Certificate
DNV Certificate AFC09...96 3-pole & AFC09...80 4-pole contactors with screw, push-in terminals
RINA Certificate
Rina Certificate for AFC09...AFC96 3 pole and 4 pole contactors, NFC relays ,screw and spring terminals
UL Certificate
UL-CA Certificate of Compliance AFC40 ... AFC80 4-pole contactors | UL-US Certificate of Compliance AFC40 ... AFC80 4-pole contactors
Package Level 1 Units
box 1 piece
Package Level 1 Width
146.5 mm
Package Level 1 Depth / Length
96.5 mm
Package Level 1 Height
146.5 mm
Package Level 1 Gross Weight
1.3 kg
Package Level 1 EAN
3471523019324
Package Level 3 Units
192 piece
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4755 >> Contactors
Feature to benefit mapping begins with a robust four-pole NO configuration designed for AC-1 and AC-3 loads, delivering high surge tolerance and predictable switch performance; this improves system reliability and reduces unplanned downtime in motors and feeders. Application-wise, it supports control circuits up to 100 A at 690 V (IEC AC-1) or 80 A at higher ambient temperatures (IEC 690 V), enabling cost-effective, scalable motor control in packaging, material handling, and process lines. The coil options of 380-400 V 50 Hz and 400-415 V 60 Hz translate to universal applicability across European and North American sites, reducing control panel complexity and stock variety. Its block design accepts add-on auxiliary contact blocks and accessories, enabling seamless expansion as automation needs grow, while maintaining a compact footprint. The DIN-rail TH35-15 mounting and screw-terminal connectivity simplify installation, inspection, and field maintenance, shortening commissioning time and minimizing wiring errors. With IP ratings and robust insulation, the device supports safe operation inside control cabinets, lowering risk of incidental contact and improving maintainability. The device also delivers measurable efficiency gains through low coil power consumption and fast operate times, contributing to lower energy use and improved line efficiency over time.

Get a Quick Quote for a ABB 1SBL361201R8500

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SBL361201R8500? Enquire Now

FAQs

The 1SBL361201R8500 is designed for TH35-15 DIN rail mounting and uses screw terminals for the main circuit. Its compact 70 mm width and 119.5 mm depth fit neatly into standard control cabinets, while the screw terminals support flexible conductor cross-sections for quick, secure connections. This combination simplifies installation and future expansion.
Key ratings include a main circuit voltage up to 690 V and a rated operational current of 100 A (IEC AC-1) at 40 °C, with 80 A at 60 °C and 70 A at 70 °C. For AC-3 applications, it handles up to 53 A at 415–690 V. The coil control voltage is 380-400 V at 50 Hz or 400-415 V at 60 Hz, and it supports high short-time withstand currents for reliable fault handling.
Yes. With a 690 V main circuit rating and AC-3 rated current of up to 53 A at 60 °C, it is well-suited for motor control tasks in industrial lines. The device also provides fast operate times (4–14 ms release, 7–21 ms operate) and a high breaking capacity to handle startup surges, making it a reliable choice for pumps, conveyors, and fans.
The device complies with IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-1, UL 60947-4-1, CSA C22.2 standards, and European CE/UKCA declarations. Additional certificates referenced include BV, CB, CCC, and CQC, supporting compliance across global markets and facilitating regulatory approvals in manufacturing environments.
Maintenance benefits come from a robust block design, screw-terminal connections, and DIN-rail mounting which simplify field service and reduce downtime. Coil power consumption is modest (6.3 W per pole in AC-1, 1.7 W in AC-3), contributing to lower energy use. Combined with 4P reliability and compatibility with accessory blocks, you can expect longer intervals between replacements and a favorable total cost of ownership in high-volume panel builds.