ABB 1SBL367001R1200 Block Contactor - AF technology

Part Number: 1SBL367001R1200
Manufacturer
ABB
Part number
1SBL367001R1200

Quick Summary

ABB 1SBL367001R1200 block contactor is a 3-pole device designed to control motors up to 22 kW at 400 V AC. In many facilities, control voltage fluctuations cause nuisance trips and wasted energy; this AF technology tolerates wide ranges, reducing downtime and improving reliability. It carries IEC/EN 60947-1, IEC/EN 60947-4-1 and UL 60335-2-40 certifications, with CE/UKCA marks to support global deployment. Engineered for DIN rail mounting and easy accessory integration, it delivers compact, economical control without compromising available protection or performance, helping you lower panel energy consumption while maintaining robust motor protection and control capabilities.

Product Information

Extended Description

1SBL367001R1200 ABB: The AF52-30-00-12 is a 3 pole - 690 V IEC or 600 UL contactor with screw terminals, controlling motors up to 22 kW / 400 V AC (AC-3) or 40 hp / 480 V UL and switching power circuits up to 100 A (AC-1) or 80 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (48-130 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Data Sheet, Technical Information
1SBC100214C0202 - Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) - Edition 2024
Instructions and Manuals
Installation instructions AF(C)40(B)...96(B)-30 Contactors, CA4, CAL4, CAT4, CC4, LDC4 Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
55 mm
Product Net Depth / Length
111 mm
Product Net Height
125.5 mm
Product Net Weight
0.97 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Number of Poles
3P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22
Rated Operational Voltage
Main Circuit 690 V
Rated Frequency (f)
Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 105 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 100 A | (690 V) 60 °C 80 A | (690 V) 70 °C 70 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 53 A | (440 V) 60 °C 53 A | (500 V) 60 °C 45 A | (690 V) 60 °C 35 A | (380 / 400 V) 60 °C 53 A | (220 / 230 / 240 V) 60 °C 53 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 53 A | (440 V) 60 °C 53 A | (500 V) 60 °C 45 A | (690 V) 60 °C 35 A | (380 / 400 V) 60 °C 53 A | (220 / 230 / 240 V) 60 °C 53 A
Rated Operational Current DC-1 (Ie)
(110 V) 2 Poles in Series, 40 °C 100 A | (110 V) 2 Poles in Series, 60 °C 80 A | (110 V) 2 Poles in Series, 70 °C 70 A | (110 V) 3 Poles in Series, 40 °C 100 A | (110 V) 3 Poles in Series, 60 °C 80 A | (110 V) 3 Poles in Series, 70 °C 70 A | (220 V) 3 Poles in Series, 40 °C 100 A | (220 V) 3 Poles in Series, 60 °C 80 A | (220 V) 3 Poles in Series, 70 °C 70 A | (72 V) 1-Pole, 40 °C 100 A | (72 V) 1-Pole, 60 °C 80 A | (72 V) 1-Pole, 70 °C 70 A | (72 V) 2 Poles in Series, 40 °C 100 A | (72 V) 2 Poles in Series, 60 °C 80 A | (72 V) 2 Poles in Series, 70 °C 70 A | (72 V) 3 Poles in Series, 40 °C 100 A | (72 V) 3 Poles in Series, 60 °C 80 A | (72 V) 3 Poles in Series, 70 °C 70 A
Rated Operational Current DC-3 (Ie)
(110 V) 2 Poles in Series, 40 °C 100 A | (110 V) 2 Poles in Series, 60 °C 80 A | (110 V) 2 Poles in Series, 70 °C 70 A | (110 V) 3 Poles in Series, 40 °C 100 A | (110 V) 3 Poles in Series, 60 °C 80 A | (110 V) 3 Poles in Series, 70 °C 70 A | (220 V) 3 Poles in Series, 40 °C 100 A | (220 V) 3 Poles in Series, 60 °C 80 A | (220 V) 3 Poles in Series, 70 °C 70 A | (72 V) 1-Pole, 40 °C 100 A | (72 V) 1-Pole, 60 °C 80 A | (72 V) 1-Pole, 70 °C 70 A | (72 V) 2 Poles in Series, 40 °C 100 A | (72 V) 2 Poles in Series, 60 °C 80 A | (72 V) 2 Poles in Series, 70 °C 70 A | (72 V) 3 Poles in Series, 40 °C 100 A | (72 V) 3 Poles in Series, 60 °C 80 A | (72 V) 3 Poles in Series, 70 °C 70 A
Rated Operational Current DC-5 (Ie)
(110 V) 2 Poles in Series, 40 °C 100 A | (110 V) 2 Poles in Series, 60 °C 80 A | (110 V) 2 Poles in Series, 70 °C 70 A | (110 V) 3 Poles in Series, 40 °C 100 A | (110 V) 3 Poles in Series, 60 °C 80 A | (110 V) 3 Poles in Series, 70 °C 70 A | (220 V) 3 Poles in Series, 40 °C 100 A | (220 V) 3 Poles in Series, 60 °C 80 A | (220 V) 3 Poles in Series, 70 °C 70 A | (72 V) 1-Pole, 40 °C 100 A | (72 V) 1-Pole, 60 °C 80 A | (72 V) 1-Pole, 70 °C 70 A | (72 V) 2 Poles in Series, 40 °C 100 A | (72 V) 2 Poles in Series, 60 °C 80 A | (72 V) 2 Poles in Series, 70 °C 70 A | (72 V) 3 Poles in Series, 40 °C 100 A | (72 V) 3 Poles in Series, 60 °C 80 A | (72 V) 3 Poles in Series, 70 °C 70 A
Rated Operational Power AC-3 (Pe)
(400 V) 22 kW | (415 V) 30 kW | (440 V) 30 kW | (500 V) 30 kW | (690 V) 30 kW | (380 / 400 V) 22 kW | (220 / 230 / 240 V) 15 kW
Rated Operational Power AC-3e (Pe)
(415 V) 30 kW | (440 V) 30 kW | (500 V) 30 kW | (690 V) 30 kW | (380 / 400 V) 22 kW | (220 / 230 / 240 V) 15 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 600 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-2 / AC-4) 150 cycles per hour | (AC-3) 1200 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 48 ... 130 V | 60 Hz 48 ... 130 V | DC Operation 48 ... 130 V
Coil Consumption
Average Holding Value 50 / 60 Hz 4 V·A | Average Holding Value 50 Hz 4 V·A | Average Holding Value 60 Hz 4 V·A | Average Holding Value DC 2 W | Average Holding Value, from Warm State 2 W
Power Loss
at Rated Operating Conditions AC-1 per Pole 6.3 W | at Rated Operating Conditions AC-3 per Pole 1.7 W
Operate Time
Between Coil De-energization and NC Contact Closing 19 ... 105 ms | Between Coil De-energization and NO Contact Opening 17 ... 100 ms | Between Coil Energization and NC Contact Opening 38 ... 95 ms | Between Coil Energization and NO Contact Closing 42 ... 100 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 4 ... 35 mm² | Flexible with Insulated Ferrule 1/2x 4 ... 35 mm² | Rigid Stranded 1/2x 6 ... 35 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Control Circuit 10 mm | Main Circuit 16 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Recommended Screw Driver
Pozidriv PZ
Tightening Torque
Control Circuit 1.2 N·m | Main Circuit 4 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 80 A
Horsepower Rating UL/CSA
(120 V AC) Single Phase 3 hp | (200 ... 208 V AC) Three Phase 15 hp | (220 ... 240 V AC) Three Phase 20 hp | (240 V AC) Single Phase 10 hp | (440 ... 480 V AC) Three Phase 40 hp | (550 ... 600 V AC) Three Phase 50 hp
Connecting Capacity Main Circuit UL/CSA
Rigid Stranded 1/2x 10-2 AWG
Connecting Capacity Control Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG | Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSA
Control Circuit 11 in·lb | Main Circuit 35 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 34 A | (200 ... 208 V AC) Three Phase 48.3 A | (220 ... 240 V AC) Three Phase 54 A | (240 V AC) Single Phase 50 A | (440 ... 480 V AC) Three Phase 52 A | (550 ... 600 V AC) Three Phase 52 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -40 ... 70 °C | Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27
Closed, Shock Direction: A 25 g | Closed, Shock Direction: B1 25 g | Closed, Shock Direction: B2 15 g | Closed, Shock Direction: C1 25 g | Closed, Shock Direction: C2 25 g | Open, Shock Direction: B1 5 g
Resistance to Vibrations
3g Closed Position & 3g Open Position 5 ... 300 Hz
Pollution Degree
3
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
a0ddca38-6029-4f22-9951-33f3ec52d24a China (CN)
Simplified SCIP
6523aad5-6974-4186-aa93-8c7c43868aee France (FR) | 498c97b2-8b1d-4e45-9206-d3aad8734ab1 France (FR) | 4f440295-11a5-4750-99b6-e92ef98722d0 Sweden (SE) | d84a4ea7-aeb7-4a94-8297-c3c961a96a6c Germany (DE) | 87e0a32c-6bc8-49ca-9a07-d224c5c634d4 Czech Republic (CZ) | be79f394-6ec8-4b6f-918d-28b669fff0ad Croatia (HR) | 9cbda79d-4cb7-4ae3-9ecd-3bce9f6adf9f Belgium (BE) | 0c94aa8f-4341-4322-a336-892bb3949b3f Poland (PL) | 5222371e-bcaa-4e66-aa9a-02498b8dccd3 Poland (PL) | d19dfb3b-c2e1-431a-966e-4b0b1731b7fd Netherlands (NL) | 64b6d6a2-52f7-4470-a51c-4f4aecce6aa6 Norway (NO) | ded76c65-3ee8-4b22-ba6e-5b28c957e5ae Hungary (HU) | 5c229a40-6af1-442f-b1da-caef7dd5831a Hungary (HU) | fe87ab77-18e2-4b5e-aa52-5c3726486955 Finland (FI) | 86d41e44-8aad-40f4-a0bf-fcd35e65e467 Portugal (PT) | daf0e20c-3a90-4715-b620-38565dd20710 Germany (DE) | db31f3c4-63fb-4851-afe5-dda190c2729f Greece (GR) | 19e77f1b-2ade-43b7-a8c6-21caa26a5c50 Denmark (DK) | 8fbcbf46-5e4c-43be-aeef-69844d795bbb Belgium (BE) | 359e8284-de14-4b28-b30c-0972e19dedbf Bulgaria (BG) | a2674756-bbe2-4e95-b937-0d387a969d83 Spain (ES) | b253e501-a743-4b1f-8a8f-ba1ef4fed15c Estonia (EE) | f2a622af-4fec-48ed-983d-01236652234b Sweden (SE) | 4a0ad2ee-825f-4e0e-9d07-3c5a5b7c5e74 Germany (DE) | e14192a1-036f-4791-a880-ba406cfba6ea Germany (DE) | f96af997-2547-4f42-9042-0d52013d45ae Poland (PL) | f5da29a1-4139-4a93-8d54-cf1023f98f55 Germany (DE)
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
Yes
End Of Life Disassembling Instructions
End of life instruction AF(S)40/52/65/80/96(B)(RT) Contactors
Environmental Product Declaration - EPD
Environmental Product Declaration AF40, AF52, AF65 (CN) | Environmental Product Declaration AF(S)40(B), AF(S)52(B), AF(S)65(B) (FR)
Sustainable Material Content in Packaging (wt. %)
FSC Recycled Paper - 94.6 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 28.2 %
A2L Certificate – UL
UL-US Certificate of Compliance AF40 ... AF96 3-pole contactors - UL 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers | UL-CA Certificate of Compliance AF40 ... AF96 3-pole contactors - CSA C22.2 No. 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers
ABS Certificate
ABS Certificate, AF(S)09 to AF(S)96 contactors, NF contactor relays and CA4, CC4, CAL4, CAT4 auxiliary contact blocks, TEF4 electronic timers
BV Certificate
BV_2634H36994B1
CB Certificate
CB Certificate AF(S)40(B), (S)AF52(B), AF(S)65(B) 3 and 4-pole contactors
CCC Certificate
CQC Certificate, Contactor, AF*40-30-**-**, AF40-40-**-**, AF40-22-**-**, AF*52-30-**-**, AF52-40-**-**,AF*65-30-**-**, Made in France
CQC Certificate
CQC Certificate, Contactor, AF*40-30-**-**, AF40-40-**-**, AF40-22-**-**, AF*52-30-**-**, AF52-40-**-**,AF*65-30-**-**, Made in France | CQC Certificate, Contactor, AF40, AF52, AF65, AFC40, AFC52, AFC65, Made in China
Declaration of Conformity - CCC
CCC Declaration of Conformity, Contactor, AF*40-30-**-**, AF40-40-**-**, AF40-22-**-**, AF*52-30-**-**, AF52-40-**-**,AF*65-30-**-**, Made in France | CCC Declaration of Conformity, Contactor, AF(C)40, AF52(C), AF65(C),AFC78 Made in China
Declaration of Conformity - CE
EU Declaration of Conformity AF09... AF96-30-.., AF09...38(Z)-30..K 3-pole Contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09... AF96-30-.., AF09...38(Z)-30..K 3-pole Contactors
DNV Certificate
DNV Certificate AF(S)09...96 3-pole & AF09...80 4-pole contactors with screw, spring, push-in terminals
KC Certificate
KC Certificate AF52 3-pole Contactors
LR Certificate
LRS Certificate AF(S)09..(K) ... AF96 3 and 4-pole contactors and CA(L)4..(K), CAT4, CC4 auxiliary contact blocks
RINA Certificate
Rina Certificate for AF09...AF96 contactors, NF contactor relays and accessories, screw and spring terminals
RMRS Certificate
RMRS Certificate AF(S)09(S)...AF(S)38 3-pole and 4-pole, AF(S)40..96 3-pole contactors with screw, push-in and spring terminals
UL Certificate
UL-US-L312527-1141-10303102-9 | UL-CA-L312527-4141-10303102-9
UL Listing Card
UL_E312527
Package Level 1 Units
box 1 piece
Package Level 1 Width
150 mm
Package Level 1 Depth / Length
150 mm
Package Level 1 Height
97 mm
Package Level 1 Gross Weight
1.07 kg
Package Level 1 EAN
3471523132320
Package Level 2 Units
box 10 piece
Package Level 2 Width
250 mm
Package Level 2 Depth / Length
300 mm
Package Level 2 Height
300 mm
Package Level 2 Gross Weight
10.7 kg
Package Level 3 Units
240 piece
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
E-Number (Finland)
3707015
E-Number (Sweden)
3210038
Feature → Business Impact → Application: AF technology enables operation over a wide coil range of 48–130 V AC/50/60 Hz and DC, reducing control circuit energy waste and improving reliability in networks with voltage variation. This translates to fewer trips and smoother motor starting in automotive, metals, or packaging lines where supply quality varies. Application: use in main circuits up to 690 V where tight control tolerance is essential. Feature → Application → Benefit: Built-in surge protection and compact block design reduce panel space and simplify wiring, supporting faster panel builds and easier retrofits in new and existing lines. Impact: lower installation time, reduced wiring errors, and improved long-term reliability. Feature → Benefit → Application: 3P, screw-terminal block with TH35-compatible DIN rail mounting and options for add-on auxiliary contact blocks. This enables quick, scalable installations across machine cells and line upgrades, minimizing downtime during expansion. Feature → Application → Benefit: Wide compatibility with accessories including LZGH2 A2L contactor relays and a broad range of certifications ensures global compliance and easier cross-border deployment in manufacturing environments. Feature → Benefit → Application: Rated power and current across AC-1, AC-3, and DC-1/3 with detailed I_e ratings (AC-3 up to 53 A at 690 V, AC-1 up to 100 A) support precise motor sizing, reducing over-specification and cost. In practice this means you can select a single device for multiple motor ratings, simplifying spares and maintenance. Feature → Application → Benefit: Energy efficiency and reduced TCO thanks to measured coil consumption and optimized operating power (4 VA hold, 2 W DC hold) and low loss per pole, providing leaner panel design and lower heat generation on enclosed control panels. Feature → Benefit → Application: Comprehensive environmental and safety compliance (IP20 coil, IP10 main, RoHS/REACH, and global certificates) deliver confidence for use in harsh industrial environments and ensure regulatory alignment across plants in different regions.

Get a Quick Quote for a ABB 1SBL367001R1200

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SBL367001R1200? Enquire Now

FAQs

The device is designed for TH35-15 or TH35-7.5 DIN rails, allowing quick snap-in mounting. It uses screw terminals for the main circuit and control circuit connections, with recommended tightening torques 4 N·m (main) and 1.2 N·m (control). Ensure proper clearance and heat dissipation in the enclosure and verify coil voltage is within 48–130 V range.
Rated for main circuit voltages up to 690 V and control circuit voltage 48–130 V (AC 50/60 Hz or DC). In AC-3 configuration it handles up to 53 A at 690 V and up to 30 kW depending on voltage; in AC-1 configurations it handles up to 100 A. This covers motors up to about 22 kW at 400 V and various three-phase configurations.
Yes. It carries IEC/EN 60947-1 and 60947-4-1 standards, UL 60335-2-40, CSA equivalents, and CE/UKCA markings. It’s designed for global deployment, meeting both North American and European safety and performance requirements, with additional certificates such as UL/CSA and DNV as applicable for specific configurations.
It integrates surge protection, a compact block design for easy extension with auxiliary contacts, and robust insulation ratings. Coil terminals are IP20 and main terminals IP10, with a 6 kV impulse withstand voltage and predictable operate times (coil energization and de-energization delays). This combination supports reliable operation in fluctuating power environments.
The block design supports adding auxiliary contact blocks and other accessories, enabling scalable upgrades without replacing the base device. The DIN rail mounting and standardized terminals simplify field maintenance, while the device’s low coil energy and compact form reduce heat and lifecycle costs in maintenance cycles.