ABB AF52B-30-11-14 Block Contactor - 690V AF Technology
Part Number: 1SBL367061R1411
Quick Summary
ABB AF52B-30-11-14 Block Contactor is a 3-pole motor control device designed for demanding industrial panels. In practice, voltage variations can trigger nuisance trips and energy waste, complicating panel design and maintenance. The AF technology delivers a wide control voltage range of 250–500 V at 50/60 Hz and even supports DC operation, helping you maintain reliable operation in unstable networks. Built-in surge protection and a compact block design enable easy expansion with auxiliary contact blocks for scalable automation. With IEC/EN 60947-4-1 and UL 60335-2-40 certifications and CE/UKCA declarations, it aligns with global safety standards while supporting energy-efficient control strategies. This combination delivers tangible business value for OEMs, panel builders, and service teams seeking robust performance and simplified integration.
Product Information
Extended Description
1SBL367061R1411 ABB: The AF52B-30-11-14 is a 3 pole - 690 V IEC or 600 UL contactor with pre-mounted auxiliary contacts and screw terminals, controlling motors up to 22 kW / 400 V AC (AC-3) or 40 hp / 480 V UL and switching power circuits up to 100 A (AC-1) or 80 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (250-500 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
Motor control and protection for Rolling stock application_PDF
Instructions and Manuals
Installation instructions AF(C)40(B)...96(B)-30 Contactors, CA4, CAL4, CAT4, CC4, LDC4 Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
67 mm
Product Net Depth / Length
111 mm
Product Net Height
125.5 mm
Product Net Weight
0.99 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
1
Number of Poles
3P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives.
Rated Operational Voltage
Auxiliary Circuit 690 V | Main Circuit 690 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 Hz | Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 105 A | acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 100 A | (690 V) 60 °C 80 A | (690 V) 70 °C 70 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 53 A | (440 V) 60 °C 53 A | (500 V) 60 °C 45 A | (690 V) 60 °C 35 A | (380 / 400 V) 60 °C 53 A | (220 / 230 / 240 V) 60 °C 53 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 53 A | (440 V) 60 °C 53 A | (500 V) 60 °C 45 A | (690 V) 60 °C 35 A | (380 / 400 V) 60 °C 53 A | (220 / 230 / 240 V) 60 °C 53 A
Rated Operational Current AC-15 (Ie)
(500 V) 2 A | (690 V) 2 A | (24 / 127 V) 6 A | (220 / 240 V) 4 A | (400 / 440 V) 3 A
Rated Operational Current DC-1 (Ie)
(110 V) 2 Poles in Series, 40 °C 100 A | (110 V) 2 Poles in Series, 60 °C 80 A | (110 V) 2 Poles in Series, 70 °C 70 A | (110 V) 3 Poles in Series, 40 °C 100 A | (110 V) 3 Poles in Series, 60 °C 80 A | (110 V) 3 Poles in Series, 70 °C 70 A | (220 V) 3 Poles in Series, 40 °C 100 A | (220 V) 3 Poles in Series, 60 °C 80 A | (220 V) 3 Poles in Series, 70 °C 70 A | (72 V) 1-Pole, 40 °C 100 A | (72 V) 1-Pole, 60 °C 80 A | (72 V) 1-Pole, 70 °C 70 A | (72 V) 2 Poles in Series, 40 °C 100 A | (72 V) 2 Poles in Series, 60 °C 80 A | (72 V) 2 Poles in Series, 70 °C 70 A | (72 V) 3 Poles in Series, 40 °C 100 A | (72 V) 3 Poles in Series, 60 °C 80 A | (72 V) 3 Poles in Series, 70 °C 70 A
Rated Operational Current DC-3 (Ie)
(110 V) 2 Poles in Series, 40 °C 100 A | (110 V) 2 Poles in Series, 60 °C 80 A | (110 V) 2 Poles in Series, 70 °C 70 A | (110 V) 3 Poles in Series, 40 °C 100 A | (110 V) 3 Poles in Series, 60 °C 80 A | (110 V) 3 Poles in Series, 70 °C 70 A | (220 V) 3 Poles in Series, 40 °C 100 A | (220 V) 3 Poles in Series, 60 °C 80 A | (220 V) 3 Poles in Series, 70 °C 70 A | (72 V) 1-Pole, 40 °C 100 A | (72 V) 1-Pole, 60 °C 80 A | (72 V) 1-Pole, 70 °C 70 A | (72 V) 2 Poles in Series, 40 °C 100 A | (72 V) 2 Poles in Series, 60 °C 80 A | (72 V) 2 Poles in Series, 70 °C 70 A | (72 V) 3 Poles in Series, 40 °C 100 A | (72 V) 3 Poles in Series, 60 °C 80 A | (72 V) 3 Poles in Series, 70 °C 70 A
Rated Operational Current DC-5 (Ie)
(110 V) 2 Poles in Series, 40 °C 100 A | (110 V) 2 Poles in Series, 60 °C 80 A | (110 V) 2 Poles in Series, 70 °C 70 A | (110 V) 3 Poles in Series, 40 °C 100 A | (110 V) 3 Poles in Series, 60 °C 80 A | (110 V) 3 Poles in Series, 70 °C 70 A | (220 V) 3 Poles in Series, 40 °C 100 A | (220 V) 3 Poles in Series, 60 °C 80 A | (220 V) 3 Poles in Series, 70 °C 70 A | (72 V) 1-Pole, 40 °C 100 A | (72 V) 1-Pole, 60 °C 80 A | (72 V) 1-Pole, 70 °C 70 A | (72 V) 2 Poles in Series, 40 °C 100 A | (72 V) 2 Poles in Series, 60 °C 80 A | (72 V) 2 Poles in Series, 70 °C 70 A | (72 V) 3 Poles in Series, 40 °C 100 A | (72 V) 3 Poles in Series, 60 °C 80 A | (72 V) 3 Poles in Series, 70 °C 70 A
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W | (48 V) 2.8 A / 134 W | (72 V) 1 A / 72 W | (110 V) 0.55 A / 60 W | (125 V) 0.55 A / 69 W | (220 V) 0.27 A / 60 W | (250 V) 0.27 A / 68 W | (400 V) 0.15 A / 60 W | (500 V) 0.13 A / 65 W | (600 V) 0.1 A / 60 W
Rated Operational Power AC-3 (Pe)
(400 V) 22 kW | (415 V) 30 kW | (440 V) 30 kW | (500 V) 30 kW | (690 V) 30 kW | (380 / 400 V) 22 kW | (220 / 230 / 240 V) 15 kW
Rated Operational Power AC-3e (Pe)
(415 V) 30 kW | (440 V) 30 kW | (500 V) 30 kW | (690 V) 30 kW | (380 / 400 V) 22 kW | (220 / 230 / 240 V) 15 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 600 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A | for 0.1 s 140 A | for 1 s 100 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 V | acc. to IEC 60947-5-1 690 V | acc. to UL/CSA 600 V
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-15) 1200 cycles per hour | (AC-2 / AC-4) 150 cycles per hour | (AC-3) 1200 cycles per hour | (DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 250 ... 500 V | 60 Hz 250 ... 500 V | DC Operation 250 ... 500 V
Coil Consumption
Average Holding Value 50 / 60 Hz 4 V·A | Average Holding Value DC 2 W
Power Loss
at Rated Operating Conditions AC-1 per Pole 6.3 W | at Rated Operating Conditions AC-3 per Pole 1.7 W
Operate Time
Between Coil De-energization and NC Contact Closing 19 ... 105 ms | Between Coil De-energization and NO Contact Opening 17 ... 100 ms | Between Coil Energization and NC Contact Opening 38 ... 95 ms | Between Coil Energization and NO Contact Closing 42 ... 100 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 4 ... 35 mm² | Flexible with Insulated Ferrule 1/2x 4 ... 35 mm² | Rigid Stranded 1/2x 6 ... 35 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Auxiliary Circuit 10 mm | Control Circuit 10 mm | Main Circuit 16 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Recommended Screw Driver
Pozidriv PZ
Tightening Torque
Auxiliary Circuit 1.2 N·m | Control Circuit 1.2 N·m | Main Circuit 4 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
Continuous Current Rating NEMA
0 A
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 80 A
Horsepower Rating UL/CSA
(120 V AC) Single Phase 3 hp | (200 ... 208 V AC) Three Phase 15 hp | (220 ... 240 V AC) Three Phase 20 hp | (240 V AC) Single Phase 10 hp | (440 ... 480 V AC) Three Phase 40 hp | (550 ... 600 V AC) Three Phase 50 hp
Connecting Capacity Main Circuit UL/CSA
Rigid Stranded 1/2x 10-2 AWG
Connecting Capacity Control Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG | Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSA
Auxiliary Circuit 11 in·lb | Control Circuit 11 in·lb | Main Circuit 35 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 34 A | (200 ... 208 V AC) Three Phase 48.3 A | (220 ... 240 V AC) Three Phase 54 A | (240 V AC) Single Phase 50 A | (440 ... 480 V AC) Three Phase 52 A | (550 ... 600 V AC) Three Phase 52 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -40 ... 70 °C | Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Shock and Vibration Withstand acc. to IEC 61373
Category 1, Class B
Pollution Degree
3
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
Yes
End Of Life Disassembling Instructions
End of life instruction AF(S)40/52/65/80/96(B)(RT) Contactors
Environmental Product Declaration - EPD
Environmental Product Declaration AF(S)40(B), AF(S)52(B), AF(S)65(B) (FR)
Sustainable Material Content in Packaging (wt. %)
FSC Recycled Paper - 94.6 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 28.2 %
A2L Certificate – UL
UL-US Certificate of Compliance AF40 ... AF96 3-pole contactors - UL 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers | UL-CA Certificate of Compliance AF40 ... AF96 3-pole contactors - CSA C22.2 No. 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers
CB Certificate
CB Certificate AF(S)40(B), (S)AF52(B), AF(S)65(B) 3 and 4-pole contactors
CCC Certificate
CQC Certificate, Contactor, AF*40-30-**-**, AF40-40-**-**, AF40-22-**-**, AF*52-30-**-**, AF52-40-**-**,AF*65-30-**-**, Made in France
Declaration of Conformity - CE
EU Declaration of Conformity AF09 ... AF38(Z)B..(K), AF40B ... AF96B 3 and 4-pole contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09 ... AF38(Z)B..(K), AF40B ... AF96B 3 and 4-pole contactors
UL Certificate
UL-US-L312527-1141-10303102-9 | UL-CA-L312527-4141-10303102-9
Package Level 1 Units
box 1 piece
Package Level 1 Width
150 mm
Package Level 1 Depth / Length
150 mm
Package Level 1 Height
97 mm
Package Level 1 Gross Weight
1.09 kg
Package Level 1 EAN
3471523025035
Package Level 2 Units
box 10 piece
Package Level 2 Width
250 mm
Package Level 2 Depth / Length
300 mm
Package Level 2 Height
300 mm
Package Level 2 Gross Weight
10.9 kg
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
Feature → Business Impact → Application: AF52B-30-11-14 uses AF technology to tolerate wide control voltage variations (250–500 V) with DC support, reducing panel energy consumption and preventing misoperation in fluctuating networks. This translates to fewer trips and improved uptime in motor control applications up to 30 kW at higher voltages, making it ideal for conveyors, pumps, and fans. Feature → Business Impact → Application: Built-in surge protection and a compact block design minimize external protection components and panel footprint, lowering installation time and wiring complexity in compact control cabinets. Feature → Business Impact → Application: The 3P main contacts with 1 NO and 1 NC auxiliary pair enable direct signaling and circuit monitoring, while add-on auxiliary blocks allow scalable control without reworking cabinets. Feature → Business Impact → Application: DIN rail mounting TH35-15/TH35-7.5 and screw-fit options simplify retrofits and new builds, ensuring quick, secure installation in standard panels. Feature → Business Impact → Application: Wide certification coverage (IEC/EN 60947-1, IEC/EN 60947-4-1, UL/CSA references) reduces compliance risk in global deployments, supporting CE/UKCA declarations and cross-border sourcing. Feature → Business Impact → Application: Coils with low consumption (4 V·A holding at 50/60 Hz; 2 W DC) reduce heat and power draw in control circuits, improving overall energy efficiency and reliability in energy-conscious facilities.
Get a Quick Quote for a ABB 1SBL367061R1411
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SBL367061R1411?
Enquire Now
FAQs
The AF52B-30-11-14 supports DIN rail mounting on TH35-15 or TH35-7.5 rails and can be mounted with two M4 or M6 screws diagonally if preferred. Main circuit terminals are screw-type with 50/60 Hz control and 690 V main ratings, while auxiliary terminals use IP20 protection. Flexible ferrule or rigid conductor connections are supported for 4–35 mm² main conductors and 0.75–2.5 mm² auxiliary conductors.
The device features 3 main NO contacts and 1 auxiliary NO plus 1 auxiliary NC contact. Rated operational current for AC-3 is up to 53 A at 415–690 V, with AC-1 up to 100 A at 690 V. Coil voltage tolerance is 250–500 V for AC and DC operation, and the unit includes built-in surge protection for robust switching of motor loads.
Yes. It is designed for AC-3 and AC-1 operations up to 690 V, with ratings such as 30 kW at various voltages, and a wide control voltage tolerance that helps manage network fluctuations. It is suitable for pumps, fans, conveyors, and other motor-driven equipment in harsh or unstable electrical environments.
The AF52B-30-11-14 complies with IEC/EN 60947-1 and 60947-4-1, UL 60335-2-40 family, and CSA equivalents, with CE and UKCA declarations available. These certifications support global deployments and supplier qualification, reducing regulatory risk in multinational projects.
AF technology provides a wide control voltage range and built-in surge protection, reducing panel components and energy waste. The coil consumption is low (4 V·A at 50/60 Hz or 2 W DC), which lowers heat in enclosures and extends service life. The modular design also simplifies maintenance and future expansions, delivering lower total cost of ownership.