ABB 1SBL367201R1400 Contactor - IEC 690V UL Listed
Part Number: 1SBL367201R1400
Quick Summary
ABB AF52-4-pole Contactor is designed to reliably switch motors up to 22 kW at 400 V AC in industrial panels. In harsh networks with voltage fluctuations, it helps reduce energy waste and ensures dependable operation. The device meets IEC/EN 60947-1 and 60947-4-1, UL 60335-2-40, and CSA safety approvals, with built-in surge protection and a compact block design. Its wide control-voltage range—250 to 500 V AC or DC—plus screw-terminal connections and DIN-rail mounting simplify field installation and spare-part planning. These features support improved panel productivity and lower lifecycle costs for OEMs and panel builders.
Product Information
Extended Description
1SBL367201R1400 ABB: The AF52-40-00-14 is a 4 pole - 690 V IEC or 600 UL contactor with screw terminals, controlling motors up to 22 kW / 400 V AC (AC-3) and switching power circuits up to 100 A (AC-1) or 80 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (250-500 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Data Sheet, Technical Information
1SBC100214C0202 - Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) - Edition 2024
Instructions and Manuals
Installation instructions AF(C)40(B)...80(B)-40/22 Contactors, CA4, CAL4, CAT4, CC4, LDC4 Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
70 mm
Product Net Depth / Length
113.5 mm
Product Net Height
125.5 mm
Product Net Weight
1.16 kg
Number of Main Contacts NO
4
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Number of Poles
4P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22
Rated Operational Voltage
Main Circuit 690 V
Rated Frequency (f)
Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 105 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 100 A | (690 V) 60 °C 80 A | (690 V) 70 °C 70 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 53 A | (440 V) 60 °C 53 A | (500 V) 60 °C 45 A | (690 V) 60 °C 35 A | (380 / 400 V) 60 °C 53 A | (220 / 230 / 240 V) 60 °C 53 A
Rated Operational Power AC-3 (Pe)
(415 V) 30 kW | (440 V) 30 kW | (500 V) 30 kW | (690 V) 30 kW | (380 / 400 V) 22 kW | (220 / 230 / 240 V) 15 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 600 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 250 ... 500 V | 60 Hz 250 ... 500 V | DC Operation 250 ... 500 V
Coil Consumption
Average Holding Value 50 / 60 Hz 4 V·A | Average Holding Value 50 Hz 4 V·A | Average Holding Value 60 Hz 4 V·A | Average Holding Value DC 2 W | Average Holding Value, from Warm State 2 W
Power Loss
at Rated Operating Conditions AC-1 per Pole 6.3 W | at Rated Operating Conditions AC-3 per Pole 1.7 W
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 4 ... 35 mm² | Flexible with Insulated Ferrule 1/2x 4 ... 35 mm² | Rigid Stranded 1/2x 6 ... 35 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Control Circuit 10 mm | Main Circuit 16 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Recommended Screw Driver
Pozidriv PZ
Tightening Torque
Control Circuit 1.2 N·m | Main Circuit 4 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 80 A
Connecting Capacity Main Circuit UL/CSA
Rigid Stranded 1/2x 10-2 AWG
Connecting Capacity Control Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG | Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSA
Control Circuit 11 in·lb | Main Circuit 35 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 3 A | (200 ... 208 V AC) Three Phase 15 A | (220 ... 240 V AC) Three Phase 20 A | (240 V AC) Single Phase 10 A | (440 ... 480 V AC) Three Phase 40 A | (550 ... 600 V AC) Three Phase 50 A
Ambient Air Temperature
Close to Contactor for Storage -60 ... +80 °C | Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Resistance to Vibrations
3g Closed Position & 2g Open Position 5 ... 300 Hz
Pollution Degree
3
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
2583f20a-3a69-458c-a294-1229532242dc China (CN)
Simplified SCIP
cc72ba67-82bf-46a6-b83d-0a89993a38b7 Belgium (BE) | 81effc56-5d27-45b1-b19a-ae780e4f4ce1 Germany (DE) | 63478c82-7455-4738-ae30-6abb1fff45a7 Poland (PL) | dfca3aac-3e63-4058-b5d6-2965f740909f France (FR) | f0b1cde7-53e0-46f6-981a-c5c4236266db Germany (DE) | f9953735-b9b5-4394-9641-882ced4cc563 Sweden (SE) | 89bd7731-23f1-4814-a3dd-c263b1161f46 France (FR) | 8fa41811-4e87-433f-abd6-b3a918fd3154 Netherlands (NL) | 8eb0194f-c306-42a1-a411-30e7fdd45cb8 Poland (PL) | 525f10aa-8db7-4277-8abf-bc522c28643a Poland (PL) | 0ff44a3b-67fc-4919-9362-3acd4f53a48d Finland (FI) | 3a98df60-af7c-4032-b8e8-532f8a91a514 Estonia (EE) | cc2688ca-7c1a-45f5-b227-6af7c2403a25 Hungary (HU) | ba87b5c7-dd13-4ca8-81f3-a0b7a2b32533 Hungary (HU) | 7110b2af-7a12-44a7-8a46-7bee8ecc1525 Norway (NO) | da1fcb55-8841-4507-b673-a81956f730a6 Germany (DE) | 98a68093-f269-446b-b358-959923497da8 Germany (DE) | 89bd6f91-d8bb-47e4-935b-78d3d6b4a3c6 Sweden (SE) | c7ada52d-0680-42f3-8e3d-c305f171d3a0 Croatia (HR) | f5fef54d-e7ea-47c3-970b-8b73a044fcb1 Germany (DE) | 650fa59b-cdc0-4319-ba2b-8412c3f89ebd Greece (GR) | d4d06f62-22a0-40bb-9103-c1ce2e42f9ed Bulgaria (BG) | 126d2505-708f-46ee-a250-53c92a07b905 Portugal (PT) | 6df2d604-34c9-4cb8-a873-bbf04ea38027 Belgium (BE) | 2a8ccc3e-86c9-49a6-b9c5-6a3db824ad25 Czech Republic (CZ) | e91ae8ae-0486-4042-afdf-75d718333fc6 Spain (ES) | 80fbaa6a-1e4f-4cd0-9cb7-d677ffe0e574 Denmark (DK)
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
Yes
End Of Life Disassembling Instructions
End of life instruction AF(S)40/52/65/80/96(B)(RT) Contactors
Environmental Product Declaration - EPD
Environmental Product Declaration AF40, AF52, AF65 (CN) | Environmental Product Declaration AF(S)40(B), AF(S)52(B), AF(S)65(B) (FR)
Sustainable Material Content in Packaging (wt. %)
FSC Recycled Paper - 94.6 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 28.2 %
A2L Certificate – UL
UL-US Certificate of Compliance AF40 ... AF96 3-pole contactors - UL 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers | UL-CA Certificate of Compliance AF40 ... AF96 3-pole contactors - CSA C22.2 No. 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers
ABS Certificate
ABS Certificate, AF(S)09 to AF(S)96 contactors, NF contactor relays and CA4, CC4, CAL4, CAT4 auxiliary contact blocks, TEF4 electronic timers
BV Certificate
BV_2634H36994B1
CB Certificate
CB Certificate AF(S)40(B), (S)AF52(B), AF(S)65(B) 3 and 4-pole contactors
CCC Certificate
CQC Certificate, Contactor, AF*40-30-**-**, AF40-40-**-**, AF40-22-**-**, AF*52-30-**-**, AF52-40-**-**,AF*65-30-**-**, Made in France
CQC Certificate
CQC Certificate, Contactor, AF*40-30-**-**, AF40-40-**-**, AF40-22-**-**, AF*52-30-**-**, AF52-40-**-**,AF*65-30-**-**, Made in France
Declaration of Conformity - CCC
CCC Declaration of Conformity, Contactor, AF*40-30-**-**, AF40-40-**-**, AF40-22-**-**, AF*52-30-**-**, AF52-40-**-**,AF*65-30-**-**, Made in France
Declaration of Conformity - CE
EU Declaration of Conformity AF09, AF16, AF26, AF38, AF40, AF52, AF80, 4-pole Contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09, AF16, AF26, AF38, AF40, AF52, AF80, 4-pole Contactors
DNV Certificate
DNV Certificate AF(S)09...96 3-pole & AF09...80 4-pole contactors with screw, spring, push-in terminals
KC Certificate
KC Certificate AF52 4-pole Contactors
LR Certificate
LRS Certificate AF(S)09..(K) ... AF96 3 and 4-pole contactors and CA(L)4..(K), CAT4, CC4 auxiliary contact blocks
RMRS Certificate
RMRS Certificate AF09(S)...AF38 3-pole and 4-pole, AF40..96 3-pole contactors, screw and spring terminals
UL Certificate
UL-US Certificate of Compliance AF40(B)...80(B) 4-pole contactors | UL-CA Certificate of Compliance AF40(B)...80(B) 4-pole contactors
UL Listing Card
UL_E312527
Package Level 1 Units
box 1 piece
Package Level 1 Width
150 mm
Package Level 1 Depth / Length
150 mm
Package Level 1 Height
103 mm
Package Level 1 Gross Weight
1.27 kg
Package Level 1 EAN
3471523133648
Package Level 2 Units
box 8 piece
Package Level 2 Width
250 mm
Package Level 2 Depth / Length
300 mm
Package Level 2 Height
300 mm
Package Level 2 Gross Weight
10.16 kg
Package Level 3 Units
192 piece
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
E-Number (Finland)
3707263
E-Number (Sweden)
3210312
Feature: 4-pole main circuit rated for up to 690 V with 100 A AC-1 (40 °C), 80 A at 60 °C, and 70 A at 70 °C, plus 53 A AC-3 at 415 V various voltages. Business Impact: Enables reliable motor control for high-demand loads (24/7 operation) while preserving protection margins and energy efficiency. Application: Suitable for AC-3 motor control in conveyors, pumps, and HVAC applications with tight space constraints. Feature: AF technology with a broad control circuit range of 250–500 V AC/50/60 Hz and DC operation. Business Impact: Reduces panel complexity and energy waste by tolerating large control voltage variations, lowering wiring and transformer requirements. Application: Ideal for installations in unstable power networks or where supply fluctuations are common. Feature: Built-in surge protection enhances equipment longevity. Business Impact: Shields downstream electronics and contactor life from voltage spikes, reducing maintenance costs and unplanned downtime. Application: Critical in metalworking, packaging lines, and process controls with motor starts. Feature: Block design with easy extension via add-on auxiliary contact blocks. Business Impact: Scales from basic motor switching to complex control schemes without replacing hardware, lowering TCO. Application: OEMs can future-proof panels as control logic evolves. Feature: Compact DIN-rail mounting (TH35-15) and screw-terminals for main and control circuits. Business Impact: Accelerates installation, simplifies field wiring, and improves serviceability. Application: Ideal for standard panels in machine builders and retrofit projects. Feature: Low coil energy and efficient power loss profile (4 VA holding for 50/60 Hz; 2 W DC; 6.3 W per pole AC-1; 1.7 W per pole AC-3). Business Impact: Reduces energy draw and heat within control cabinets, contributing to safer enclosures and longer component life. Application: Suitable for automation layouts with energy budgets and thermal constraints.
Get a Quick Quote for a ABB 1SBL367201R1400
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SBL367201R1400?
Enquire Now
FAQs
Install on a TH35-15 DIN rail or secure with two diagonally placed screws (M4 or M6). Main circuit terminals accept flexible ferrule 1/2x 4-35 mm2 or rigid 1/2x 6-35 mm2; control circuit accepts 0.75-2.5 mm2 conductors. Wire stripping lengths are 16 mm for the main and 10 mm for the control circuit. Ensure IP20 coil terminals and IP10 main terminals are properly protected in the enclosure.
Main circuit rated at up to 690 V with AC-1 current rating of 100 A at 40 °C (80 A at 60 °C, 70 A at 70 °C). AC-3 rated current is 53 A across nominal voltages such as 415–500 V, with a maximum switching capacity suitable for demanding motor starts. Coil rated for 250–500 V control voltage, including DC operation, supporting a wide control range.
Yes. AF52 type uses AF technology with a wide control voltage range of 250–500 V AC/50/60 Hz and DC, helping to tolerate voltage fluctuations. The device also integrates surge protection to safeguard the circuit, reducing nuisance trips and protecting the motor and controller electronics in unstable networks.
The product aligns with IEC/EN 60947-1 and 60947-4-1, UL 60335-2-40, and CSA safety standards, with corresponding UL/CSA listings and CE marking. It also supports material and environmental declarations, RoHS/REACH compliance, and relevant safety certifications for panel builders and OEMs.
With built-in surge protection and extendable auxiliary contacts, you can upgrade control logic without replacing the base unit, reducing downtime and parts costs. Moderate coil consumption (4 VA at 50/60 Hz; 2 W DC) lowers energy draw in control cabinets. The contactor supports frequent switching (600 cycles/hour AC-1), aligning with typical production line cycles for predictable maintenance planning.