ABB 1SBL371074R3611 Block Contactor - UL/CE Certified

Part Number: 1SBL371074R3611
Manufacturer
ABB
Part number
1SBL371074R3611

Quick Summary

Block Contactor ABB 1SBL371074R3611 provides reliable motor control for 3-phase systems up to 690 V. This solution helps you simplify panel design while delivering consistent switching performance. Engineers often face mounting variability, limited auxiliary contact options, and longer downtime due to incompatible accessories. The AX50–AX80 family offers 3 main poles, AC-operated control, and optional add-on auxiliary blocks for side mounting, plus a broad range of compatible accessories. This model carries CE and UL certifications, along with RoHS and REACH declarations to support global deployment. By combining compact dimensions with robust ratings and standard screw terminals, it delivers lower installed cost, easier maintenance, and faster time-to-value for your automation projects.

Product Information

Extended Description

1SBL371074R3611 ABB: AX50...AX80 contactors are mainly used for controlling 3-phase motors and power circuits up to 690 V AC. These contactors are of the block type design with: – 3 main poles – control circuit: AC operated – add-on auxiliary contact blocks (optional) for side mounting and a wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
1SBC100187L0203
Instructions and Manuals
AX 50~80A instructions
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
82 mm
Product Net Depth / Length
110 mm
Product Net Height
108 mm
Product Net Weight
1.05 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
1
Rated Operational Voltage
Auxiliary Circuit 690 V | Main Circuit 690 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 125 A
Rated Operational Current AC-1 (Ie)
(220 / 240 V) 55 °C 95 A | (690 V) 40 °C 115 A | (690 V) 70 °C 80 A
Rated Operational Current AC-3 (Ie)
(415 V) 55 °C 65 A | (440 V) 55 °C 65 A | (500 V) 55 °C 55 A | (690 V) 55 °C 43 A | (380 / 400 V) 55 °C 65 A | (220 / 230 / 240 V) 55 °C 65 A
Rated Operational Power AC-3 (Pe)
(415 V) 37 kW | (440 V) 37 kW | (500 V) 37 kW | (690 V) 37 kW | (380 / 400 V) 30 kW | (220 / 230 / 240 V) 18.5 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 650 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 135 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 370 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1300 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 630 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
Rated Impulse Withstand Voltage (Uimp)
Auxiliary Circuit 6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-3) 600 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 190 V | 60 Hz 220 V
Power Loss
at Rated Operating Conditions AC-1 per Pole 6.5 W | at Rated Operating Conditions AC-3 per Pole 1.5 W
Operate Time
Between Coil De-energization and NC Contact Closing 7 ... 14 ms | Between Coil De-energization and NO Contact Opening 4 ... 11 ms | Between Coil Energization and NC Contact Opening 7 ... 22 ms | Between Coil Energization and NO Contact Closing 8 ... 27 ms
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Tightening Torque
Control Circuit 1 N·m | Main Circuit 4 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
General Use Rating UL/CSA
(600 V AC) 90 A
Horsepower Rating UL/CSA
(120 V AC) Single Phase 5 hp | (200 ... 208 V AC) Three Phase 20 hp | (220 ... 240 V AC) Three Phase 25 hp | (240 V AC) Single Phase 10 hp | (440 ... 480 V AC) Three Phase 60 hp | (550 ... 600 V AC) Three Phase 75 hp
Tightening Torque UL/CSA
Auxiliary Circuit 9 in·lb | Control Circuit 9 in·lb | Main Circuit 35 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 56 A | (200 ... 208 V AC) Three Phase 62.1 A | (220 ... 240 V AC) Three Phase 68 A | (240 V AC) Single Phase 50 A | (440 ... 480 V AC) Three Phase 77 A | (550 ... 600 V AC) Three Phase 77 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -25 ... 55 °C | Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C | Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
Maximum Operating Altitude Permissible
Without Derating 3000 m
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
CB Certificate
AX 50~80A CB certification
CCC Certificate
9AKK107492A7091
CCS Certificate
CCS Certificate of AFC09 ... AFC96 , AX09-AX370 contactors
CQC Certificate
CQC Certificate, Contactor, AX50, AX65, AX80, Made in China
Declaration of Conformity - CCC
CCC Declaration of Conformity, Contactor, AX50, AX65, AX80, Made in China
Declaration of Conformity - CE
EU Declaration of Conformity AX06, AX09, AX12, AX18, AX25, AX32, AX40, AX50, AX65, AX80 3-pole Contactors
UL Certificate
UL Certificate of Compliance – AX06, AX09, AX12, AX18, AX25
Package Level 1 Units
box 1 piece
Package Level 1 Width
102 mm
Package Level 1 Depth / Length
143 mm
Package Level 1 Height
152 mm
Package Level 1 Gross Weight
1.16 kg
Package Level 1 EAN
3471522406361
Package Level 2 Units
10 piece
Package Level 2 Width
240 mm
Package Level 2 Depth / Length
295 mm
Package Level 2 Height
145 mm
Package Level 2 Gross Weight
11.6 kg
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4755 >> Contactors
Three main NO contacts and a compact block design deliver dependable switching for 3-phase motors up to 690 V. This compact form factor reduces panel footprint and simplifies wiring, enabling tighter, more reliable installations in control cabinets. Ideal for conveyors, pumps, fans and other high-demand loads in manufacturing lines.High-performance ratings provide clear business value: rated operational current AC-3 up to 65 A at 415–690 V, I_th up to 125 A, and protection voltages up to 690 V. Short-time withstand capabilities and maximum breaking capacity of 1300 A enable safe, controlled switching under fault conditions. This translates to lower downtime and safer startup in critical processes.Control and installation convenience drive faster project delivery: coil options at 190 V / 220 V (50/60 Hz), screw terminals, and IP20 coil terminals with IP10 main terminals. Optional add-on auxiliary contact blocks support side mounting and expansion without rework. CAD data and 2D/3D files simplify integration with your design tools.Reliability and compliance underpin long-term value: RoHS and REACH declarations, CE and UL certifications, and CB/CCC listings support global regulatory requirements. With a weight of 1.05 kg and dimensions near 82 × 110 × 108 mm, the unit fits compact panels while maintaining robust performance for years of service.

Get a Quick Quote for a ABB 1SBL371074R3611

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SBL371074R3611? Enquire Now

FAQs

The unit measures 82 mm wide, 110 mm deep, and 108 mm high, with screw terminals on both coil (IP20) and main (IP10) circuits. It supports add-on auxiliary contact blocks for side mounting and is compatible with the AX50–AX80 family. Ensure panel space allows for the 1.05 kg unit and provide proper clearance for thermal dissipation.
Rated operational current AC-3 varies by voltage: up to 65 A at 415–440 V, 55 A at 500 V, and 43 A at 690 V (55 °C ambient). Conventional free-air thermal current Θ = 40 °C yields about 125 A. Short-time withstand and breaking capacity support safe fault handling during motor starting and stopping.
Yes. With three main NO contacts and a dedicated auxiliary contact, the device is designed for three-phase motor control up to 690 V. Its compact footprint and robust AC-3 ratings make it well-suited for conveyors, pumps, fans and other constantly switched loads in process lines.
The model carries CE and UL certifications, along with RoHS and REACH declarations. It is compatible with CB and CCC documentation, providing regulatory support for global manufacturing sites and export markets.
Competitive running power loss per pole (6.5 W AC-1, 1.5 W AC-3) and a mechanical life of up to 3600 cycles support reliability and uptime. The compact form factor reduces panel space, easing maintenance and replacement in lean automation architectures while enabling faster project delivery.