ABB 1SBL371074R8300 Block Contactor - CE Certification

Part Number: 1SBL371074R8300
Manufacturer
ABB
Part number
1SBL371074R8300

Quick Summary

ABB 1SBL371074R8300 Block Contactor is designed to reliably switch 3-phase motors and power circuits up to 690 V AC. Manufacturers face challenges with coil voltage compatibility, mounting options, and access to CAD-ready data for fast panel builds. This device combines CE Declaration of Conformity, UL/CSA approvals, and RoHS/REACH compliance to support multinational installations across Europe and North America. With a compact footprint, screw-terminal access, and CAD data availability, it delivers faster installation, easier maintenance, and lower total cost of ownership for machine builders. Whether upgrading legacy equipment or integrating new lines, this ABB solution aligns with common industry standards while delivering reliable performance.

Product Information

Extended Description

1SBL371074R8300 ABB: AX50...AX80 contactors are mainly used for controlling 3-phase motors and power circuits up to 690 V AC. These contactors are of the block type design with: – 3 main poles – control circuit: AC operated – add-on auxiliary contact blocks (optional) for side mounting and a wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
1SBC100187L0203
Instructions and Manuals
AX 50~80A instructions
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
70 mm
Product Net Depth / Length
110 mm
Product Net Height
108 mm
Product Net Weight
1.01 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Rated Operational Voltage
Auxiliary Circuit 690 V | Main Circuit 690 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 125 A
Rated Operational Current AC-1 (Ie)
(220 / 240 V) 55 °C 95 A | (690 V) 40 °C 115 A | (690 V) 70 °C 80 A
Rated Operational Current AC-3 (Ie)
(415 V) 55 °C 65 A | (440 V) 55 °C 65 A | (500 V) 55 °C 55 A | (690 V) 55 °C 43 A | (380 / 400 V) 55 °C 65 A | (220 / 230 / 240 V) 55 °C 65 A
Rated Operational Power AC-3 (Pe)
(415 V) 37 kW | (440 V) 37 kW | (500 V) 37 kW | (690 V) 37 kW | (380 / 400 V) 30 kW | (220 / 230 / 240 V) 18.5 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 650 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 135 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 370 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1300 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 630 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
Rated Impulse Withstand Voltage (Uimp)
Auxiliary Circuit 6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-3) 600 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 48 V | 60 Hz 48 V
Power Loss
at Rated Operating Conditions AC-1 per Pole 6.5 W | at Rated Operating Conditions AC-3 per Pole 1.5 W
Operate Time
Between Coil De-energization and NC Contact Closing 7 ... 14 ms | Between Coil De-energization and NO Contact Opening 4 ... 11 ms | Between Coil Energization and NC Contact Opening 7 ... 22 ms | Between Coil Energization and NO Contact Closing 8 ... 27 ms
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Tightening Torque
Control Circuit 1 N·m | Main Circuit 4 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
General Use Rating UL/CSA
(600 V AC) 90 A
Horsepower Rating UL/CSA
(120 V AC) Single Phase 5 hp | (200 ... 208 V AC) Three Phase 20 hp | (220 ... 240 V AC) Three Phase 25 hp | (240 V AC) Single Phase 10 hp | (440 ... 480 V AC) Three Phase 60 hp | (550 ... 600 V AC) Three Phase 75 hp
Tightening Torque UL/CSA
Auxiliary Circuit 9 in·lb | Control Circuit 9 in·lb | Main Circuit 35 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 56 A | (200 ... 208 V AC) Three Phase 62.1 A | (220 ... 240 V AC) Three Phase 68 A | (240 V AC) Single Phase 50 A | (440 ... 480 V AC) Three Phase 77 A | (550 ... 600 V AC) Three Phase 77 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -25 ... 55 °C | Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C | Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
Maximum Operating Altitude Permissible
Without Derating 3000 m
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
CB Certificate
AX 50~80A CB certification
CCC Certificate
9AKK107492A7091
CCS Certificate
CCS Certificate of AFC09 ... AFC96 , AX09-AX370 contactors
CQC Certificate
CQC Certificate, Contactor, AX50, AX65, AX80, Made in China
Declaration of Conformity - CCC
CCC Declaration of Conformity, Contactor, AX50, AX65, AX80, Made in China
Declaration of Conformity - CE
EU Declaration of Conformity AX06, AX09, AX12, AX18, AX25, AX32, AX40, AX50, AX65, AX80 3-pole Contactors
UL Certificate
UL Certificate of Compliance – AX06, AX09, AX12, AX18, AX25
Package Level 1 Units
box 1 piece
Package Level 1 Width
102 mm
Package Level 1 Depth / Length
143 mm
Package Level 1 Height
152 mm
Package Level 1 Gross Weight
1.12 kg
Package Level 1 EAN
3471522405838
Package Level 2 Units
10 piece
Package Level 2 Width
240 mm
Package Level 2 Depth / Length
295 mm
Package Level 2 Height
145 mm
Package Level 2 Gross Weight
11.2 kg
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4755 >> Contactors
Feature: Three main poles with an AC-operated control circuit and a rated main circuit up to 690 V AC. Business Impact: Simplifies wiring, reduces relay stack height, and enables consistent starting of three-phase motors. Application: Ideal for conveyors, pumps, and fans in standard industrial drives. Feature: Compact footprint with 70 mm width, 110 mm depth, and 108 mm height. Business Impact: Saves panel space and enclosure costs, enabling tighter machine layouts. Application: Suitable for compact control panels in packaging lines and machine tools. Feature: Clear separation of coil and main circuits with screw terminals. Business Impact: Improves wiring reliability and enables straightforward maintenance with predictable torque values. Application: Mounting in standard enclosures where robust electrical connections are essential. Feature: 3 NO main contacts, 0 NC, and no auxiliary contacts by default. Business Impact: Reduces part count while delivering reliable main switching; easy to add auxiliary blocks later. Application: Configurable to support custom control logic. Feature: Rated Operational Current AC-1 and AC-3 across multiple voltages; P- and Icw values provide design flexibility. Business Impact: Supports a wide range of motor loads while ensuring safe short-time withstand performance. Application: Suitable for motor starters in mixed-voltage environments. Feature: IP20 coil terminals and IP10 main terminals. Business Impact: Safer wiring in standard rooms and easier maintenance during service campaigns. Application: Typical panel-building environments with standard protections. Feature: CAD data availability (2D/3D) for fast integration. Business Impact: Speeds up design, reduces CAD errors, and accelerates commissioning. Application: OEMs and integrators embedding the part into machine designs.

Get a Quick Quote for a ABB 1SBL371074R8300

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SBL371074R8300? Enquire Now

FAQs

Installation requires mounting the 3-pole block contacor in a standard panel, securing the device with the provided hardware, and wiring the main circuit to the screw terminals. Use a tightening torque of 4 N·m for the main circuit and 1 N·m for the control circuit. Ensure IP20 coil terminals and IP10 main terminals are properly protected within the enclosure.
Rated Operational Current AC-1 ranges up to 115 A at 690 V and 95 A at 220/240 V (40 °C). Rated Operational Current AC-3 includes 65 A at 415–690 V, with corresponding P_e values around 37 kW at several voltages. Short-time withstand and breaking capacities are specified (I_cw up to 1000 A for short times), supporting reliable motor starting.
Yes. The device is designed for 3-phase motor control up to 690 V AC, with main circuit ratings and protective interlocks suitable for high-voltage drive applications. It supports AC-1 and AC-3 operation modes, enabling both switching and starting of varied motor loads in compliant industrial environments.
The AX50–AX80 series provides CE Declaration of Conformity, UL/CSA approvals for North American installations, and RoHS/REACH compliance. Additional certifications include CCC, CQC, and related declarations to support manufacturing and procurement workflows in global supply chains.
The device offers low power loss per pole (6.5 W for AC-1 and 1.5 W for AC-3), which reduces energy consumption and heat in control panels. Its compact form, reliable mechanical life (up to high cycle counts), and CAD-ready data shorten installation time and support faster commissioning, improving machine uptime and total cost of ownership.