ABB AF65B-30-11-13 Contactor - IEC/EN 60947-4-1, UL 60335-2-40

Part Number: 1SBL387061R1311
Manufacturer
ABB
Part number
1SBL387061R1311

Quick Summary

ABB AF65B-30-11-13 Contactor provides robust motor control for 30 kW loads in industrial lines. Many panels suffer from voltage variation and energy waste; AF65B’s wide 100–250 V AC/DC coil range mitigates this. It complies with IEC/EN 60947-4-1 and UL 60335-2-40, and includes CE and UKCA declarations to support global deployment. This compact 3-pole design supports pre-mounted auxiliary contacts and easy extension with add-on contactor blocks, reducing panel footprint and simplifying installation. Engineered for reliability in unstable networks, it delivers consistent operation and energy efficiency, making it a favorable choice for OEMs and maintenance teams seeking durable motor control solutions in harsh environments.

Product Information

Extended Description

1SBL387061R1311 ABB: The AF65B-30-11-13 is a 3 pole - 690 V IEC or 600 UL contactor with pre-mounted auxiliary contacts and screw terminals, controlling motors up to 30 kW / 400 V AC (AC-3) or 50 hp / 480 V UL and switching power circuits up to 105 A (AC-1) or 90 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
Motor control and protection for Rolling stock application_PDF
Instructions and Manuals
Installation instructions AF(C)40(B)...96(B)-30 Contactors, CA4, CAL4, CAT4, CC4, LDC4 Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
67 mm
Product Net Depth / Length
111 mm
Product Net Height
125.5 mm
Product Net Weight
0.99 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
1
Number of Poles
3P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives.
Rated Operational Voltage
Auxiliary Circuit 690 V | Main Circuit 690 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 Hz | Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 105 A | acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 105 A | (690 V) 60 °C 90 A | (690 V) 70 °C 80 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 65 A | (440 V) 60 °C 65 A | (500 V) 60 °C 55 A | (690 V) 60 °C 39 A | (380 / 400 V) 60 °C 65 A | (220 / 230 / 240 V) 60 °C 65 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 65 A | (440 V) 60 °C 65 A | (500 V) 60 °C 55 A | (690 V) 60 °C 39 A | (380 / 400 V) 60 °C 65 A | (220 / 230 / 240 V) 60 °C 65 A
Rated Operational Current AC-15 (Ie)
(500 V) 2 A | (690 V) 2 A | (24 / 127 V) 6 A | (220 / 240 V) 4 A | (400 / 440 V) 3 A
Rated Operational Current DC-1 (Ie)
(110 V) 2 Poles in Series, 40 °C 105 A | (110 V) 2 Poles in Series, 60 °C 90 A | (110 V) 2 Poles in Series, 70 °C 80 A | (110 V) 3 Poles in Series, 40 °C 105 A | (110 V) 3 Poles in Series, 60 °C 90 A | (110 V) 3 Poles in Series, 70 °C 80 A | (220 V) 3 Poles in Series, 40 °C 105 A | (220 V) 3 Poles in Series, 60 °C 90 A | (220 V) 3 Poles in Series, 70 °C 80 A | (72 V) 1-Pole, 40 °C 105 A | (72 V) 1-Pole, 60 °C 90 A | (72 V) 1-Pole, 70 °C 80 A | (72 V) 2 Poles in Series, 40 °C 105 A | (72 V) 2 Poles in Series, 60 °C 90 A | (72 V) 2 Poles in Series, 70 °C 80 A | (72 V) 3 Poles in Series, 40 °C 105 A | (72 V) 3 Poles in Series, 60 °C 90 A | (72 V) 3 Poles in Series, 70 °C 80 A
Rated Operational Current DC-3 (Ie)
(110 V) 2 Poles in Series, 40 °C 105 A | (110 V) 2 Poles in Series, 60 °C 90 A | (110 V) 2 Poles in Series, 70 °C 80 A | (110 V) 3 Poles in Series, 40 °C 105 A | (110 V) 3 Poles in Series, 60 °C 90 A | (110 V) 3 Poles in Series, 70 °C 80 A | (220 V) 3 Poles in Series, 40 °C 105 A | (220 V) 3 Poles in Series, 60 °C 90 A | (220 V) 3 Poles in Series, 70 °C 80 A | (72 V) 1-Pole, 40 °C 105 A | (72 V) 1-Pole, 60 °C 90 A | (72 V) 1-Pole, 70 °C 80 A | (72 V) 2 Poles in Series, 40 °C 105 A | (72 V) 2 Poles in Series, 60 °C 90 A | (72 V) 2 Poles in Series, 70 °C 80 A | (72 V) 3 Poles in Series, 40 °C 105 A | (72 V) 3 Poles in Series, 60 °C 90 A | (72 V) 3 Poles in Series, 70 °C 80 A
Rated Operational Current DC-5 (Ie)
(110 V) 2 Poles in Series, 40 °C 105 A | (110 V) 2 Poles in Series, 60 °C 90 A | (110 V) 2 Poles in Series, 70 °C 80 A | (110 V) 3 Poles in Series, 40 °C 105 A | (110 V) 3 Poles in Series, 60 °C 90 A | (110 V) 3 Poles in Series, 70 °C 80 A | (220 V) 3 Poles in Series, 40 °C 105 A | (220 V) 3 Poles in Series, 60 °C 90 A | (220 V) 3 Poles in Series, 70 °C 80 A | (72 V) 1-Pole, 40 °C 105 A | (72 V) 1-Pole, 60 °C 90 A | (72 V) 1-Pole, 70 °C 80 A | (72 V) 2 Poles in Series, 40 °C 105 A | (72 V) 2 Poles in Series, 60 °C 90 A | (72 V) 2 Poles in Series, 70 °C 80 A | (72 V) 3 Poles in Series, 40 °C 105 A | (72 V) 3 Poles in Series, 60 °C 90 A | (72 V) 3 Poles in Series, 70 °C 80 A
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W | (48 V) 2.8 A / 134 W | (72 V) 1 A / 72 W | (110 V) 1.1 A / 121 W | (125 V) 0.55 A / 69 W | (220 V) 0.27 A / 60 W | (250 V) 0.27 A / 68 W | (400 V) 0.15 A / 60 W | (500 V) 0.13 A / 65 W | (600 V) 0.1 A / 60 W
Rated Operational Power AC-3 (Pe)
(400 V) 30 kW | (415 V) 37 kW | (440 V) 37 kW | (500 V) 37 kW | (690 V) 37 kW | (380 / 400 V) 30 kW | (220 / 230 / 240 V) 18.5 kW
Rated Operational Power AC-3e (Pe)
(415 V) 37 kW | (440 V) 37 kW | (500 V) 37 kW | (690 V) 37 kW | (380 / 400 V) 30 kW | (220 / 230 / 240 V) 18.5 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 600 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A | for 0.1 s 140 A | for 1 s 100 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 V | acc. to IEC 60947-5-1 690 V | acc. to UL/CSA 600 V
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-15) 1200 cycles per hour | (AC-2 / AC-4) 150 cycles per hour | (AC-3) 1200 cycles per hour | (DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 100 ... 250 V | 60 Hz 100 ... 250 V | DC Operation 100 ... 250 V
Coil Consumption
Average Holding Value 50 / 60 Hz 4 V·A | Average Holding Value DC 2 W
Power Loss
at Rated Operating Conditions AC-1 per Pole 7 W | at Rated Operating Conditions AC-3 per Pole 2.7 W
Operate Time
Between Coil De-energization and NC Contact Closing 19 ... 105 ms | Between Coil De-energization and NO Contact Opening 17 ... 100 ms | Between Coil Energization and NC Contact Opening 38 ... 95 ms | Between Coil Energization and NO Contact Closing 42 ... 100 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 4 ... 35 mm² | Flexible with Insulated Ferrule 1/2x 4 ... 35 mm² | Rigid Stranded 1/2x 6 ... 35 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Auxiliary Circuit 10 mm | Control Circuit 10 mm | Main Circuit 16 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Recommended Screw Driver
Pozidriv PZ
Tightening Torque
Auxiliary Circuit 1.2 N·m | Control Circuit 1.2 N·m | Main Circuit 4 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
Continuous Current Rating NEMA
0 A
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 90 A
Horsepower Rating UL/CSA
(120 V AC) Single Phase 5 hp | (200 ... 208 V AC) Three Phase 20 hp | (220 ... 240 V AC) Three Phase 25 hp | (240 V AC) Single Phase 15 hp | (440 ... 480 V AC) Three Phase 50 hp | (550 ... 600 V AC) Three Phase 60 hp
Connecting Capacity Main Circuit UL/CSA
Rigid Stranded 1/2x 10-2 AWG
Connecting Capacity Control Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG | Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSA
Auxiliary Circuit 11 in·lb | Control Circuit 11 in·lb | Main Circuit 35 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 56 A | (200 ... 208 V AC) Three Phase 62.1 A | (220 ... 240 V AC) Three Phase 68 A | (240 V AC) Single Phase 68 A | (440 ... 480 V AC) Three Phase 65 A | (550 ... 600 V AC) Three Phase 62 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -40 ... 70 °C | Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Shock and Vibration Withstand acc. to IEC 61373
Category 1, Class B
Pollution Degree
3
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
Yes
End Of Life Disassembling Instructions
End of life instruction AF(S)40/52/65/80/96(B)(RT) Contactors
Environmental Product Declaration - EPD
Environmental Product Declaration AF(S)40(B), AF(S)52(B), AF(S)65(B) (FR)
Sustainable Material Content in Packaging (wt. %)
FSC Recycled Paper - 94.6 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 28.2 %
A2L Certificate – UL
UL-US Certificate of Compliance AF40 ... AF96 3-pole contactors - UL 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers | UL-CA Certificate of Compliance AF40 ... AF96 3-pole contactors - CSA C22.2 No. 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers
CB Certificate
CB Certificate AF(S)40(B), (S)AF52(B), AF(S)65(B) 3 and 4-pole contactors
CCC Certificate
CQC Certificate, Contactor, AF*40-30-**-**, AF40-40-**-**, AF40-22-**-**, AF*52-30-**-**, AF52-40-**-**,AF*65-30-**-**, Made in France
Declaration of Conformity - CE
EU Declaration of Conformity AF09 ... AF38(Z)B..(K), AF40B ... AF96B 3 and 4-pole contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09 ... AF38(Z)B..(K), AF40B ... AF96B 3 and 4-pole contactors
UL Certificate
UL-US-L312527-1141-10303102-9 | UL-CA-L312527-4141-10303102-9
Package Level 1 Units
box 1 piece
Package Level 1 Width
150 mm
Package Level 1 Depth / Length
150 mm
Package Level 1 Height
97 mm
Package Level 1 Gross Weight
1.09 kg
Package Level 1 EAN
3471523025301
Package Level 2 Units
box 10 piece
Package Level 2 Width
250 mm
Package Level 2 Depth / Length
300 mm
Package Level 2 Height
300 mm
Package Level 2 Gross Weight
10.9 kg
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
Feature: Wide control voltage range of 100-250 V AC/DC with AF technology. Business Impact: Reduces wiring variants and control-signal mismatches, lowering commissioning time and field faults. Application: Ideal for mixed-voltage automation lines and machines where supply quality varies. Feature: Built-in surge protection and compact block design. Business Impact: Minimizes external protection needs and saves panel space, cutting installation costs. Application: Suitable for compact control panels in robotics and packaging lines. Feature: Pre-mounted auxiliary contacts (1 NO and 1 NC). Business Impact: Enables ready-made control feedback and safer interlocking without extra accessories. Application: Easily wired for starter circuits and safety interlocks in conveyors. Feature: Coil consumption and power loss optimized for efficiency. Business Impact: Lower energy use per operation reduces operating costs over the product life cycle. Application: High-duty cycle drives in HVAC and processing equipment. Feature: DIN rail mounting and versatile connections (TH35 options and screw terminations). Business Impact: Simplifies installation and maintenance with flexible mounting and a wide conductor range. Application: Suitable for panel builders and OEMs deploying in standard cabinet environments.

Get a Quick Quote for a ABB 1SBL387061R1311

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SBL387061R1311? Enquire Now

FAQs

Install the device on a TH35 DIN rail (TH35-15 or TH35-7.5). Use 2x M4 or 2x M6 screws for panel mounting if needed. Main circuit connections accept flexible ferrule 1/2x 4-35 mm², auxiliary 0.75-2.5 mm², and control 0.75-2.5 mm². Tightening torques are 4 N·m for main, 1.2 N·m for auxiliary and control circuits. Ensure coil voltage matches 100-250 V AC/DC and verify polarity where applicable.
Main circuit rated voltage is 690 V, with IEC/EN 60947-4-1 compliance and AC-1 Ie up to 105 A (60 °C) and 90 A (40 °C) or 80 A (70 °C). For AC-3, Ie values vary by voltage (e.g., 39 A at 690 V). The auxiliary circuit shares the 690 V rating, with one NO and one NC contact provided for control signaling and interlocking.
Yes. The AF65B-30-11-13 is a 3-pole 690 V contactor rated for high-power motor control up to 30 kW, with wide coil voltage compatibility and built-in surge protection. It supports standard IEC/UL/CSA certifications and can be extended with add-on auxiliary blocks, making it adaptable for rail rolling stock, conveyors, and general industrial drives.
The device aligns with IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40, UL/CSA listings, and CE/UKCA declarations. These certifications support regulatory compliance for electrical equipment across Europe, North America, and other markets, simplifying approvals, reducing risk during import/export, and ensuring safety and interoperability in panel assemblies.
The contactor’s low coil power (2 W DC holding; 4 V·A for 50/60 Hz) and integrated surge protection reduce energy consumption and need for external suppressors, lowering operating costs. Its compact, modular design and DIN rail mounting simplify installation and maintenance, cutting labor time during replacements or extensions and delivering a favorable total cost of ownership in automated systems.