ABB 1SBL397001R1211 Block Contactor - IEC/UL Certifications
Part Number: 1SBL397001R1211
Quick Summary
ABB 1SBL397001R1211 is a 3-pole block contactor that controls motors up to 37 kW at 400 V AC. Its wide coil control range 48-130 V AC/DC helps maintain reliable operation even with voltage fluctuations and unstable mains. It carries IEC/EN 60947-1 and 60947-4-1 compliance along with UL 60335-2-40 and other global listings for safety and motor-control applications. This combination supports fast commissioning, straightforward expansion with add-on auxiliary blocks, and dependable performance in challenging industrial environments. Designed for DIN rail mounting and screw terminal connections, it also features built-in surge protection to simplify panel design and reduce component count. With multiple current ratings for AC-1, AC-3, and DC-13 families, you can standardize spare parts across diversified equipment.
Product Information
Extended Description
1SBL397001R1211 ABB: The AF80-30-11-12 is a 3 pole - 1000 V IEC or 600 UL contactor with pre-mounted auxiliary contacts and screw terminals, controlling motors up to 37 kW / 400 V AC (AC-3) or 60 hp / 480 V UL and switching power circuits up to 125 A (AC-1) or 105 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (48-130 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
1SBC100214C0202 - Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) - Edition 2024
Instructions and Manuals
Installation instructions AF(C)40(B)...96(B)-30 Contactors, CA4, CAL4, CAT4, CC4, LDC4 Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
82 mm
Product Net Depth / Length
116 mm
Product Net Height
125.5 mm
Product Net Weight
1.26 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
1
Number of Poles
3P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22
Rated Operational Voltage
Auxiliary Circuit 690 V | Main Circuit 1000 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 Hz | Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 130 A | acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 125 A | (690 V) 60 °C 100 A | (690 V) 70 °C 85 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 80 A | (440 V) 60 °C 80 A | (500 V) 60 °C 65 A | (690 V) 60 °C 49 A | (1000 V) 60 °C 25 A | (380 / 400 V) 60 °C 80 A | (220 / 230 / 240 V) 60 °C 80 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 80 A | (440 V) 60 °C 80 A | (500 V) 60 °C 65 A | (690 V) 60 °C 49 A | (380 / 400 V) 60 °C 80 A | (220 / 230 / 240 V) 60 °C 80 A
Rated Operational Current AC-15 (Ie)
(500 V) 2 A | (690 V) 2 A | (24 / 127 V) 6 A | (220 / 240 V) 4 A | (400 / 440 V) 3 A
Rated Operational Current DC-1 (Ie)
(110 V) 2 Poles in Series, 40 °C 125 A | (110 V) 2 Poles in Series, 60 °C 100 A | (110 V) 2 Poles in Series, 70 °C 85 A | (110 V) 3 Poles in Series, 40 °C 125 A | (110 V) 3 Poles in Series, 60 °C 100 A | (110 V) 3 Poles in Series, 70 °C 85 A | (220 V) 3 Poles in Series, 40 °C 125 A | (220 V) 3 Poles in Series, 60 °C 100 A | (220 V) 3 Poles in Series, 70 °C 85 A | (72 V) 1-Pole, 40 °C 125 A | (72 V) 1-Pole, 60 °C 100 A | (72 V) 1-Pole, 70 °C 85 A | (72 V) 2 Poles in Series, 40 °C 125 A | (72 V) 2 Poles in Series, 60 °C 100 A | (72 V) 2 Poles in Series, 70 °C 85 A | (72 V) 3 Poles in Series, 40 °C 125 A | (72 V) 3 Poles in Series, 60 °C 100 A | (72 V) 3 Poles in Series, 70 °C 85 A
Rated Operational Current DC-3 (Ie)
(110 V) 2 Poles in Series, 40 °C 125 A | (110 V) 2 Poles in Series, 60 °C 100 A | (110 V) 2 Poles in Series, 70 °C 85 A | (110 V) 3 Poles in Series, 40 °C 125 A | (110 V) 3 Poles in Series, 60 °C 100 A | (110 V) 3 Poles in Series, 70 °C 85 A | (220 V) 3 Poles in Series, 40 °C 125 A | (220 V) 3 Poles in Series, 60 °C 100 A | (220 V) 3 Poles in Series, 70 °C 85 A | (72 V) 1-Pole, 40 °C 125 A | (72 V) 1-Pole, 60 °C 100 A | (72 V) 1-Pole, 70 °C 85 A | (72 V) 2 Poles in Series, 40 °C 125 A | (72 V) 2 Poles in Series, 60 °C 100 A | (72 V) 2 Poles in Series, 70 °C 85 A | (72 V) 3 Poles in Series, 40 °C 125 A | (72 V) 3 Poles in Series, 60 °C 100 A | (72 V) 3 Poles in Series, 70 °C 85 A
Rated Operational Current DC-5 (Ie)
(110 V) 2 Poles in Series, 40 °C 125 A | (110 V) 2 Poles in Series, 60 °C 100 A | (110 V) 2 Poles in Series, 70 °C 85 A | (110 V) 3 Poles in Series, 40 °C 125 A | (110 V) 3 Poles in Series, 60 °C 100 A | (110 V) 3 Poles in Series, 70 °C 85 A | (220 V) 3 Poles in Series, 40 °C 125 A | (220 V) 3 Poles in Series, 60 °C 100 A | (220 V) 3 Poles in Series, 70 °C 85 A | (72 V) 1-Pole, 40 °C 125 A | (72 V) 1-Pole, 60 °C 100 A | (72 V) 1-Pole, 70 °C 85 A | (72 V) 2 Poles in Series, 40 °C 125 A | (72 V) 2 Poles in Series, 60 °C 100 A | (72 V) 2 Poles in Series, 70 °C 85 A | (72 V) 3 Poles in Series, 40 °C 125 A | (72 V) 3 Poles in Series, 60 °C 100 A | (72 V) 3 Poles in Series, 70 °C 85 A
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W | (48 V) 2.8 A / 134 W | (72 V) 1 A / 72 W | (110 V) 0.55 A / 60 W | (125 V) 0.55 A / 69 W | (220 V) 0.27 A / 60 W | (250 V) 0.27 A / 68 W | (400 V) 0.15 A / 60 W | (500 V) 0.13 A / 65 W | (600 V) 0.1 A / 60 W
Rated Operational Power AC-3 (Pe)
(400 V) 37 kW | (415 V) 45 kW | (440 V) 45 kW | (500 V) 45 kW | (690 V) 45 kW | (1000 V) 35 kW | (380 / 400 V) 37 kW | (220 / 230 / 240 V) 22 kW
Rated Operational Power AC-3e (Pe)
(415 V) 45 kW | (440 V) 45 kW | (500 V) 45 kW | (690 V) 45 kW | (380 / 400 V) 37 kW | (220 / 230 / 240 V) 22 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 780 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 140 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 300 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1200 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 450 A | for 0.1 s 140 A | for 1 s 100 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1150 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 750 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 1000 V | acc. to IEC 60947-5-1 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
8 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-15) 1200 cycles per hour | (AC-2 / AC-4) 150 cycles per hour | (AC-3) 1200 cycles per hour | (DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 48 ... 130 V | 60 Hz 48 ... 130 V | DC Operation 48 ... 130 V
Coil Consumption
Average Holding Value 50 / 60 Hz 4 V·A | Average Holding Value 50 Hz 4 V·A | Average Holding Value 60 Hz 4 V·A | Average Holding Value DC 2 W | Average Holding Value, from Warm State 2 W
Power Loss
at 6 A per Pole 0.1 W | at Rated Operating Conditions AC-1 per Pole 7.6 W | at Rated Operating Conditions AC-3 per Pole 3 W
Operate Time
Between Coil De-energization and NC Contact Closing 19 ... 105 ms | Between Coil De-energization and NO Contact Opening 17 ... 100 ms | Between Coil Energization and NC Contact Opening 38 ... 95 ms | Between Coil Energization and NO Contact Closing 42 ... 100 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 6 ... 50 mm² | Flexible with Insulated Ferrule 1/2x 6 ... 50 mm² | Rigid Stranded 1x 6 ... 70 mm² | Rigid Stranded 2x 6 ... 50 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Rigid 1/2x 1 ... 2.5 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Auxiliary Circuit 10 mm | Control Circuit 10 mm | Main Circuit 17 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Recommended Screw Driver
Pozidriv PZ
Tightening Torque
Auxiliary Circuit 1.2 N·m | Control Circuit 1.2 N·m | Main Circuit 6 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
NEMA Size
3
Continuous Current Rating NEMA
90 A
Horsepower Rating NEMA
(200 V AC) Three Phase 25 Hp | (230 V AC) Three Phase 30 Hp | (460 V AC) Three Phase 50 Hp | (575 V AC) Three Phase 50 Hp
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 105 A
Horsepower Rating UL/CSA
(120 V AC) Single Phase 7-1/2 hp | (200 ... 208 V AC) Three Phase 25 hp | (220 ... 240 V AC) Three Phase 30 hp | (240 V AC) Single Phase 15 hp | (440 ... 480 V AC) Three Phase 60 hp | (550 ... 600 V AC) Three Phase 75 hp
Connecting Capacity Main Circuit UL/CSA
Rigid Stranded 1/2x 6-1 AWG
Tightening Torque UL/CSA
Auxiliary Circuit 11 in·lb | Control Circuit 11 in·lb | Main Circuit 53 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 80 A | (200 ... 208 V AC) Three Phase 78.2 A | (220 ... 240 V AC) Three Phase 80 A | (240 V AC) Single Phase 68 A | (440 ... 480 V AC) Three Phase 77 A | (550 ... 600 V AC) Three Phase 77 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -40 ... 70 °C | Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27
Closed, Shock Direction: A 25 g | Closed, Shock Direction: B1 25 g | Closed, Shock Direction: B2 15 g | Closed, Shock Direction: C1 25 g | Closed, Shock Direction: C2 25 g | Open, Shock Direction: B1 5 g
Resistance to Vibrations
3g Closed Position & 3g Open Position 5 ... 300 Hz
Pollution Degree
3
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
3a800c77-0458-49d3-963d-df785c3a3f08 China (CN)
Simplified SCIP
be996b07-c79a-4149-8e54-23702cfd40eb Denmark (DK) | 95b7037d-7ef2-4a2e-8709-2afbe2f32ae8 Czech Republic (CZ) | c2126788-8dce-453e-9fce-5090d25347c7 Belgium (BE) | 07b00c91-988c-4e62-999e-3c97f71236d7 Spain (ES) | 84b17106-9db3-4aea-bd10-8da03f7030b7 Germany (DE) | 5eb9ab55-d7c5-40a6-a177-871e5696c199 Croatia (HR) | fa2ee5d3-43a6-463c-8f35-50ab3d10278c Poland (PL) | 2b752fe7-7467-4f68-8c8a-b0fdc66087ac Germany (DE) | 5fe87ffc-559d-469e-a012-efc3e7badadf Sweden (SE) | e47b6a12-c461-48f2-b89e-5b64e4203a52 Germany (DE) | 62900f66-64ab-4d56-84a5-16de35ed5f1d France (FR) | bc862988-a746-40a2-94d9-43056d5f0555 Sweden (SE) | 701e6c80-f017-4fa5-9a74-eb952a164b89 France (FR) | b4bc8d61-3a52-408a-9807-7c6504c39557 Germany (DE) | 37bbfc8f-1b2f-4821-b8fb-a8dd0a08413a Poland (PL) | 48d151df-e35e-49a9-8cd1-841157f15f6e Poland (PL) | c26f31f6-9e4b-4901-9965-7024dd8d9c21 Finland (FI) | 172ded13-ad73-4598-9d6a-3fa1777f8695 Belgium (BE) | 2b74d152-2715-4877-963d-8c7e0482e30d Greece (GR) | 0e41c800-6e98-438f-9499-54dcc0390403 Portugal (PT) | 64b7d3ee-94e2-428e-b175-af1a2962ff0d Germany (DE) | 5f1dbb6c-3f34-468e-b10c-79aa2acacd30 Netherlands (NL) | 7189510a-75e5-4d90-bfdc-572e479598f0 Hungary (HU) | 75daa2ac-a6ef-465d-99b6-074f2a3e9565 Norway (NO) | f49a7da8-b38a-4335-91e6-610601cc7a53 Hungary (HU) | ea096171-8054-44cc-b321-2c9ecc300364 Estonia (EE) | 1c6cd2d2-9845-443d-aa11-79ad43c0503f Bulgaria (BG)
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
Yes
End Of Life Disassembling Instructions
End of life instruction AF(S)40/52/65/80/96(B)(RT) Contactors
Environmental Product Declaration - EPD
Environmental Product Declaration AF80, AF96 (CN) Contactors | Environmental Product Declaration AF(S)80(B), AF(S)96(B) (FR)
Sustainable Material Content in Packaging (wt. %)
FSC Recycled Paper - 94.6 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 28.2 %
A2L Certificate – UL
UL-US Certificate of Compliance AF40 ... AF96 3-pole contactors - UL 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers | UL-CA Certificate of Compliance AF40 ... AF96 3-pole contactors - CSA C22.2 No. 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers
ABS Certificate
ABS Certificate, AF(S)09 to AF(S)96 contactors, NF contactor relays and CA4, CC4, CAL4, CAT4 auxiliary contact blocks, TEF4 electronic timers
BV Certificate
BV_2634H36994B1
CB Certificate
CB Certificate AF(S)80(B), AF(S)96(B) 3 and 4-pole contactors
CCC Certificate
CQC Certificate, AC Contactor, AF(S)*80-30-**-**, AF80-40-**-**, AF80-22-**-**, AF(S)96-30-**-**, Made in France
Declaration of Conformity - CCC
CCC Declaration of Conformity, AC Contactor, AF*80-30-**-**, AF80-40-**-**, AF80-22-**-**, AF*96-30-**-**, Made in France
Declaration of Conformity - CE
EU Declaration of Conformity AF09... AF96-30-.., AF09...38(Z)-30..K 3-pole Contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09... AF96-30-.., AF09...38(Z)-30..K 3-pole Contactors
DNV Certificate
DNV Certificate AF(S)09...96 3-pole & AF09...80 4-pole contactors with screw, spring, push-in terminals
KC Certificate
KC Certificate AF80, AF96 3-pole Contactors
LR Certificate
LRS Certificate AF(S)09..(K) ... AF96 3 and 4-pole contactors and CA(L)4..(K), CAT4, CC4 auxiliary contact blocks
RINA Certificate
Rina Certificate for AF09...AF96 contactors, NF contactor relays and accessories, screw and spring terminals
RMRS Certificate
RMRS Certificate AF(S)09(S)...AF(S)38 3-pole and 4-pole, AF(S)40..96 3-pole contactors with screw, push-in and spring terminals
UL Certificate
UL-US-L312527-1141-10303102-9 | UL-CA-L312527-4141-10303102-9
UL Listing Card
UL_E312527
Package Level 1 Units
box 1 piece
Package Level 1 Width
150 mm
Package Level 1 Depth / Length
150 mm
Package Level 1 Height
103 mm
Package Level 1 Gross Weight
1.38 kg
Package Level 1 EAN
3471523133020
Package Level 2 Units
box 8 piece
Package Level 2 Width
250 mm
Package Level 2 Depth / Length
300 mm
Package Level 2 Height
300 mm
Package Level 2 Gross Weight
11.04 kg
Package Level 3 Units
192 piece
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
E-Number (Finland)
3707126
Feature: AF technology delivers a broad control voltage range that supports 48–130 V AC or DC coils. Business Impact: this tolerance minimizes nuisance tripping and reduces energy consumption by stabilizing coil operation in fluctuating networks. Application: ideal for motor protection and control in HVAC, pumps, and process conveyors where power quality varies. | Feature: Built-in surge protection and a compact block design. Business Impact: enhances reliability and saves panel space, reducing parts count and maintenance complexity. Application: easy integration into compact electrical cabinets and retrofit projects with limited clearance. | Feature: Pre-mounted auxiliary contacts NO/NC and screw terminals. Business Impact: simplifies wiring schemes and improves maintainability; enables quick field changes without replacing the base unit. Application: auxiliary signaling for motor control circuits and interlocking in safety circuits. | Feature: 3-pole main contact arrangement with high AC-3 and DC-13 ratings. Business Impact: supports motor loads across a wide voltage range, enabling standardization of drive components. Application: control of pumps, fans, compressors in industrial machines. | Feature: DIN rail mounting TH35-15 and flexible connecting options. Business Impact: straightforward installation and scalable wiring; supports easy retrofits and service upgrades. Application: panel builders and OEMs seeking modular, maintainable motor protection and control solutions. | Feature: Wide compatibility with 1/2x 6–50 mm² main conductors and 0.75–2.5 mm² auxiliary/control conductors. Business Impact: accelerates wiring design and reduces termination times. Application: versatile for diverse machine builds, from packaging lines to water pumps.
Get a Quick Quote for a ABB 1SBL397001R1211
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SBL397001R1211?
Enquire Now
FAQs
The device is designed for DIN rail mounting (TH35-15) and screw mounting with 2x M4 or 2x M6 screws. Main circuit uses screw terminals with flexible or rigid conductors, and the auxiliary/control circuits use screw terminals or ferrule connections. This combination simplifies installation and enables quick field wiring changes.
Yes. The block contactor is rated for AC-3 across voltages up to 690 V, with AC-3 power ratings up to 45 kW at 415–690 V (and 37 kW at 400 V in some configurations). It supports motor control for pumps, conveyors, and fans within those ratings.
It complies with IEC/EN 60947-1 and 60947-4-1, UL 60335-2-40, UL/CSA listings, CCC/UKCA/CE marks, and multiple regional certifications, ensuring safe operation in global motor-protection and control applications.
The coil supports a wide control voltage of 48–130 V for AC and DC operation, enabling reliable operation despite mains variations. Coil current characteristics include low holding power (4 V·A at 50/60 Hz) and a minimum inrush for fast engagement.
Operating temperature ranges from -40 to 70 °C, with an altitude rating up to 3000 m without derating. Terminals feature IP20/IP10 protection depending on circuit, and the product has a robust IP-related and shock/vibration spec suitable for industrial environments.