ABB AF80 block contactor is a robust 3-pole device for motor control in industrial panels. It handles motors up to 37 kW at 400 V AC (AC-3) and can be extended with auxiliary blocks for added control. The AF technology provides a wide control voltage range of 250–500 V AC or DC, reducing panel energy fluctuations and improving reliability in networks with voltage variation. Built-in surge protection enhances reliability in harsh environments, and the compact block design saves panel space. The device meets IEC/EN 60947-1 and 60947-4-1, UL 60335-2-40, and is CE marked and CSA listed, offering strong compliance for global installations. Compatible with TH35 DIN rail mounting and accessories, it delivers scalable motor protection for growing automation needs.

Product Information

Extended Description

1SBL397001R1422 ABB: The AF80-30-22-14 is a 3 pole - 1000 V IEC or 600 UL contactor with pre-mounted auxiliary contacts and screw terminals, controlling motors up to 37 kW / 400 V AC (AC-3) or 60 hp / 480 V UL and switching power circuits up to 125 A (AC-1) or 105 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (250-500 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
1SBC100214C0202 - Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) - Edition 2024
Instructions and Manuals
Installation instructions AF(C)40(B)...96(B)-30 Contactors, CA4, CAL4, CAT4, CC4, LDC4 Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
70 mm
Product Net Depth / Length
149 mm
Product Net Height
125.5 mm
Product Net Weight
1.22 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
2
Number of Auxiliary Contacts NC
2
Number of Poles
3P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22
Rated Operational Voltage
Auxiliary Circuit 690 V | Main Circuit 1000 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 Hz | Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 130 A | acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 125 A | (690 V) 60 °C 100 A | (690 V) 70 °C 85 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 80 A | (440 V) 60 °C 80 A | (500 V) 60 °C 65 A | (690 V) 60 °C 49 A | (1000 V) 60 °C 25 A | (380 / 400 V) 60 °C 80 A | (220 / 230 / 240 V) 60 °C 80 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 80 A | (440 V) 60 °C 80 A | (500 V) 60 °C 65 A | (690 V) 60 °C 49 A | (380 / 400 V) 60 °C 80 A | (220 / 230 / 240 V) 60 °C 80 A
Rated Operational Current AC-15 (Ie)
(500 V) 2 A | (690 V) 2 A | (24 / 127 V) 6 A | (220 / 240 V) 4 A | (400 / 440 V) 3 A
Rated Operational Current DC-1 (Ie)
(110 V) 2 Poles in Series, 40 °C 125 A | (110 V) 2 Poles in Series, 60 °C 100 A | (110 V) 2 Poles in Series, 70 °C 85 A | (110 V) 3 Poles in Series, 40 °C 125 A | (110 V) 3 Poles in Series, 60 °C 100 A | (110 V) 3 Poles in Series, 70 °C 85 A | (220 V) 3 Poles in Series, 40 °C 125 A | (220 V) 3 Poles in Series, 60 °C 100 A | (220 V) 3 Poles in Series, 70 °C 85 A | (72 V) 1-Pole, 40 °C 125 A | (72 V) 1-Pole, 60 °C 100 A | (72 V) 1-Pole, 70 °C 85 A | (72 V) 2 Poles in Series, 40 °C 125 A | (72 V) 2 Poles in Series, 60 °C 100 A | (72 V) 2 Poles in Series, 70 °C 85 A | (72 V) 3 Poles in Series, 40 °C 125 A | (72 V) 3 Poles in Series, 60 °C 100 A | (72 V) 3 Poles in Series, 70 °C 85 A
Rated Operational Current DC-3 (Ie)
(110 V) 2 Poles in Series, 40 °C 125 A | (110 V) 2 Poles in Series, 60 °C 100 A | (110 V) 2 Poles in Series, 70 °C 85 A | (110 V) 3 Poles in Series, 40 °C 125 A | (110 V) 3 Poles in Series, 60 °C 100 A | (110 V) 3 Poles in Series, 70 °C 85 A | (220 V) 3 Poles in Series, 40 °C 125 A | (220 V) 3 Poles in Series, 60 °C 100 A | (220 V) 3 Poles in Series, 70 °C 85 A | (72 V) 1-Pole, 40 °C 125 A | (72 V) 1-Pole, 60 °C 100 A | (72 V) 1-Pole, 70 °C 85 A | (72 V) 2 Poles in Series, 40 °C 125 A | (72 V) 2 Poles in Series, 60 °C 100 A | (72 V) 2 Poles in Series, 70 °C 85 A | (72 V) 3 Poles in Series, 40 °C 125 A | (72 V) 3 Poles in Series, 60 °C 100 A | (72 V) 3 Poles in Series, 70 °C 85 A
Rated Operational Current DC-5 (Ie)
(110 V) 2 Poles in Series, 40 °C 125 A | (110 V) 2 Poles in Series, 60 °C 100 A | (110 V) 2 Poles in Series, 70 °C 85 A | (110 V) 3 Poles in Series, 40 °C 125 A | (110 V) 3 Poles in Series, 60 °C 100 A | (110 V) 3 Poles in Series, 70 °C 85 A | (220 V) 3 Poles in Series, 40 °C 125 A | (220 V) 3 Poles in Series, 60 °C 100 A | (220 V) 3 Poles in Series, 70 °C 85 A | (72 V) 1-Pole, 40 °C 125 A | (72 V) 1-Pole, 60 °C 100 A | (72 V) 1-Pole, 70 °C 85 A | (72 V) 2 Poles in Series, 40 °C 125 A | (72 V) 2 Poles in Series, 60 °C 100 A | (72 V) 2 Poles in Series, 70 °C 85 A | (72 V) 3 Poles in Series, 40 °C 125 A | (72 V) 3 Poles in Series, 60 °C 100 A | (72 V) 3 Poles in Series, 70 °C 85 A
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W | (48 V) 2.8 A / 134 W | (72 V) 1 A / 72 W | (110 V) 0.55 A / 60 W | (125 V) 0.55 A / 69 W | (220 V) 0.27 A / 60 W | (250 V) 0.27 A / 68 W | (400 V) 0.15 A / 60 W | (500 V) 0.13 A / 65 W | (600 V) 0.1 A / 60 W
Rated Operational Power AC-3 (Pe)
(400 V) 37 kW | (415 V) 45 kW | (440 V) 45 kW | (500 V) 45 kW | (690 V) 45 kW | (1000 V) 35 kW | (380 / 400 V) 37 kW | (220 / 230 / 240 V) 22 kW
Rated Operational Power AC-3e (Pe)
(415 V) 45 kW | (440 V) 45 kW | (500 V) 45 kW | (690 V) 45 kW | (380 / 400 V) 37 kW | (220 / 230 / 240 V) 22 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 780 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 140 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 300 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1200 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 450 A | for 0.1 s 140 A | for 1 s 100 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1150 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 750 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 1000 V | acc. to IEC 60947-5-1 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
8 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-15) 1200 cycles per hour | (AC-2 / AC-4) 150 cycles per hour | (AC-3) 1200 cycles per hour | (DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 250 ... 500 V | 60 Hz 250 ... 500 V | DC Operation 250 ... 500 V
Power Loss
at 6 A per Pole 0.1 W | at Rated Operating Conditions AC-1 per Pole 7.6 W | at Rated Operating Conditions AC-3 per Pole 3 W
Operate Time
Between Coil De-energization and NC Contact Closing 19 ... 105 ms | Between Coil De-energization and NO Contact Opening 17 ... 100 ms | Between Coil Energization and NC Contact Opening 38 ... 95 ms | Between Coil Energization and NO Contact Closing 42 ... 100 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 6 ... 50 mm² | Flexible with Insulated Ferrule 1/2x 6 ... 50 mm² | Rigid Stranded 1x 6 ... 70 mm² | Rigid Stranded 2x 6 ... 50 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Rigid 1/2x 1 ... 2.5 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Auxiliary Circuit 10 mm | Control Circuit 10 mm | Main Circuit 17 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Tightening Torque
Auxiliary Circuit 1.2 N·m | Control Circuit 1.2 N·m | Main Circuit 6 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
NEMA Size
3
Continuous Current Rating NEMA
90 A
Horsepower Rating NEMA
(200 V AC) Three Phase 25 Hp | (230 V AC) Three Phase 30 Hp | (460 V AC) Three Phase 50 Hp | (575 V AC) Three Phase 50 Hp
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 105 A
Horsepower Rating UL/CSA
(120 V AC) Single Phase 7-1/2 hp | (200 ... 208 V AC) Three Phase 25 hp | (220 ... 240 V AC) Three Phase 30 hp | (240 V AC) Single Phase 15 hp | (440 ... 480 V AC) Three Phase 60 hp | (550 ... 600 V AC) Three Phase 75 hp
Connecting Capacity Main Circuit UL/CSA
Rigid Stranded 1/2x 6-1 AWG
Tightening Torque UL/CSA
Auxiliary Circuit 11 in·lb | Control Circuit 11 in·lb | Main Circuit 53 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 80 A | (200 ... 208 V AC) Three Phase 78.2 A | (220 ... 240 V AC) Three Phase 80 A | (240 V AC) Single Phase 68 A | (440 ... 480 V AC) Three Phase 77 A | (550 ... 600 V AC) Three Phase 77 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -40 ... 70 °C | Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27
Closed, Shock Direction: A 25 g | Closed, Shock Direction: B1 25 g | Closed, Shock Direction: B2 15 g | Closed, Shock Direction: C1 25 g | Closed, Shock Direction: C2 25 g | Open, Shock Direction: B1 5 g
Resistance to Vibrations
3g Closed Position & 3g Open Position 5 ... 300 Hz
Pollution Degree
3
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
Yes
End Of Life Disassembling Instructions
End of life instruction AF(S)40/52/65/80/96(B)(RT) Contactors
Environmental Product Declaration - EPD
Environmental Product Declaration AF(S)80(B), AF(S)96(B) (FR)
Sustainable Material Content in Packaging (wt. %)
FSC Recycled Paper - 94.6 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 28.2 %
A2L Certificate – UL
UL-US Certificate of Compliance AF40 ... AF96 3-pole contactors - UL 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers | UL-CA Certificate of Compliance AF40 ... AF96 3-pole contactors - CSA C22.2 No. 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers
ABS Certificate
ABS Certificate, AF(S)09 to AF(S)96 contactors, NF contactor relays and CA4, CC4, CAL4, CAT4 auxiliary contact blocks, TEF4 electronic timers
BV Certificate
BV_2634H36994B1
CB Certificate
CB Certificate AF(S)80(B), AF(S)96(B) 3 and 4-pole contactors
CCC Certificate
CQC Certificate, AC Contactor, AF(S)*80-30-**-**, AF80-40-**-**, AF80-22-**-**, AF(S)96-30-**-**, Made in France
Declaration of Conformity - CCC
CCC Declaration of Conformity, AC Contactor, AF*80-30-**-**, AF80-40-**-**, AF80-22-**-**, AF*96-30-**-**, Made in France
Declaration of Conformity - CE
EU Declaration of Conformity AF09... AF96-30-.., AF09...38(Z)-30..K 3-pole Contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09... AF96-30-.., AF09...38(Z)-30..K 3-pole Contactors
DNV Certificate
DNV Certificate AF(S)09...96 3-pole & AF09...80 4-pole contactors with screw, spring, push-in terminals
KC Certificate
KC Certificate AF80, AF96 3-pole Contactors
LR Certificate
LRS Certificate AF(S)09..(K) ... AF96 3 and 4-pole contactors and CA(L)4..(K), CAT4, CC4 auxiliary contact blocks
RINA Certificate
Rina Certificate for AF09...AF96 contactors, NF contactor relays and accessories, screw and spring terminals
RMRS Certificate
RMRS Certificate AF(S)09(S)...AF(S)38 3-pole and 4-pole, AF(S)40..96 3-pole contactors with screw, push-in and spring terminals
UL Certificate
UL-US-L312527-1141-10303102-9 | UL-CA-L312527-4141-10303102-9
UL Listing Card
UL_E312527
Package Level 1 Units
box 1 piece
Package Level 1 Width
180 mm
Package Level 1 Depth / Length
150 mm
Package Level 1 Height
102 mm
Package Level 1 Gross Weight
1.36 kg
Package Level 1 EAN
3471523133143
Package Level 2 Units
box 6 piece
Package Level 2 Width
250 mm
Package Level 2 Depth / Length
300 mm
Package Level 2 Height
300 mm
Package Level 2 Gross Weight
8.16 kg
Package Level 3 Units
144 piece
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
E-Number (Finland)
3707133
Feature: Three-pole AF80 block contactor with pre-mounted auxiliary contacts and screw terminals. Business Impact: Simplifies wiring and reduces panel depth while delivering reliable control for motors up to 37 kW at 400 V AC (AC-3). Application: Suitable for compact control panels in packaging lines and conveyors. Feature: Wide control voltage range of 250–500 V AC/DC. Business Impact: Enables robust operation across unstable networks and voltage fluctuations, cutting nuisance trips and downtime. Application: Ideal for installations near varying supply sources or long cable runs. Feature: Built-in surge protection and compact block design. Business Impact: Increases device resilience and panel density, lowering total cost of ownership. Application: Critical in harsh industrial environments and space-constrained control cabinets. Feature: 3 main NO contacts and 2 auxiliary NO/2 NC contacts. Business Impact: Expands control logic without additional relays, enabling more sophisticated interlock schemes and safe interlocking in automation lines. Application: Commonly used in motor protection and control circuits with auxiliary feedback. Feature: DIN rail mounting TH35-15 and screw-terminal connections. Business Impact: Eases installation and maintenance, reducing commissioning time and field wiring errors. Application: Suitable for standard panel builds and retrofit projects with existing TH35 rails. Feature: Rated AC-3 power handling and low coil power loss (3 W per pole). Business Impact: Improves energy efficiency in control circuits and supports higher duty cycles. Application: High-usage applications such as conveyors and fans in process lines.

Get a Quick Quote for a ABB 1SBL397001R1422

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SBL397001R1422? Enquire Now

FAQs

Yes. The AF80 is designed for mounting on TH35-15 DIN rails, which is the standard 35 x 15 mm profile. It can also be installed using 2 x M4 or 2 x M6 screws placed diagonally. This symmetry simplifies integration into existing control cabinets and minimizes space requirements while maintaining secure mechanical mounting.
The coil operates across a wide 250–500 V range for both AC and DC control. The device features 3 main NO contacts and 2 auxiliary contacts (NO), plus 2 NC auxiliary contacts. Main circuit voltage is up to 1000 V, with AC-3 power handling up to 37 kW at 400 V and up to 45 kW at higher voltages, supporting reliable motor starting in diverse industrial settings.
Yes. With AC-3 rating up to 45 kW at 690 V and 37 kW at 400 V, the AF80-30-22-14 is well-suited for motor starting and stopping in conveyors and similar line equipment. Its built-in surge protection and compact block design reduce wiring, improve reliability, and simplify integration into automated conveyor systems.
This contactor is aligned with IEC/EN 60947-1 and 60947-4-1, UL 60335-2-40, and CSA standards. It is CE marked and supports global installation requirements, providing traceable compliance for safety and performance in industrial installations.
Low coil power loss (3 W per pole for AC-3) reduces energy in control paths, while the ability to add auxiliary contact blocks supports scalable control logic without new modules. DIN-rail mounting and screw-terminal connections speed up commissioning. Durable construction and wide voltage tolerance improve uptime and reduce total cost of ownership over the device life cycle.