ABB 1SBL397201R1111 Block Contactor - UL/CSA Listed
Part Number: 1SBL397201R1111
Quick Summary
Block Contactor ABB 1SBL397201R1111 is a four-pole starter for motor control in heavy-duty industrial panels. In plants with fluctuating voltages, inconsistent control signals can trigger nuisance trips; AF technology accepts 24–60 V AC/DC control and stabilizes operation. It carries IEC/EN 60947-1, IEC/EN 60947-4-1, and UL/CSA certifications, plus CE and UKCA declarations for global installations. This combination supports OEMs and panel builders seeking reliability, energy efficiency, and regulatory compliance across diverse markets. Designed for DIN rail mounting with screw terminals and add-on auxiliary blocks, it reduces wiring time and panel footprint. Businesses benefit from predictable lifecycle costs, lower energy consumption, and quicker compliance during audits.
Product Information
Extended Description
1SBL397201R1111 ABB: The AF80-40-11-11 is a 4 pole - 1000 V IEC or 600 UL contactor with pre-mounted auxiliary contacts and screw terminals, controlling motors up to 37 kW / 400 V AC (AC-3) and switching power circuits up to 125 A (AC-1) or 105 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (24-60 V 50/60 Hz and 20-60 V DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Instructions and Manuals
Installation instructions AF(C)40(B)...80(B)-40/22 Contactors, CA4, CAL4, CAT4, CC4, LDC4 Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
102 mm
Product Net Depth / Length
116 mm
Product Net Height
125.5 mm
Product Net Weight
1.53 kg
Number of Main Contacts NO
4
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
1
Number of Poles
4P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, IEC/EN 60947-5-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22
Rated Operational Voltage
Auxiliary Circuit 690 V | Main Circuit 1000 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 Hz | Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 125 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 125 A | (690 V) 60 °C 105 A | (690 V) 70 °C 90 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 80 A | (440 V) 60 °C 80 A | (500 V) 60 °C 65 A | (690 V) 60 °C 49 A | (1000 V) 60 °C 25 A | (380 / 400 V) 60 °C 80 A | (220 / 230 / 240 V) 60 °C 80 A
Rated Operational Current AC-15 (Ie)
(500 V) 2 A | (690 V) 2 A | (24 / 127 V) 6 A | (220 / 240 V) 4 A | (400 / 440 V) 3 A
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W | (48 V) 2.8 A / 134 W | (72 V) 1 A / 72 W | (110 V) 0.55 A / 60 W | (125 V) 0.55 A / 69 W | (220 V) 0.27 A / 60 W | (250 V) 0.27 A / 68 W | (400 V) 0.15 A / 60 W | (500 V) 0.13 A / 65 W | (600 V) 0.1 A / 60 W
Rated Operational Power AC-3 (Pe)
(415 V) 45 kW | (440 V) 45 kW | (500 V) 45 kW | (690 V) 45 kW | (1000 V) 35 kW | (380 / 400 V) 37 kW | (220 / 230 / 240 V) 22 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 780 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 140 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 300 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1200 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 450 A | for 0.1 s 140 A | for 1 s 100 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1150 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 750 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 1000 V | acc. to IEC 60947-5-1 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
8 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-15) 1200 cycles per hour | (DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 24 ... 60 V | 60 Hz 24 ... 60 V | DC Operation 20 ... 60 V
Power Loss
at 6 A per Pole 0.1 W | at Rated Operating Conditions AC-1 per Pole 8 W | at Rated Operating Conditions AC-3 per Pole 3.2 W
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 6 ... 50 mm² | Flexible with Insulated Ferrule 1/2x 6 ... 50 mm² | Rigid Stranded 1x 6 ... 70 mm² | Rigid Stranded 2x 6 ... 50 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Auxiliary Circuit 10 mm | Control Circuit 10 mm | Main Circuit 17 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Tightening Torque
Auxiliary Circuit 1.2 N·m | Control Circuit 1.2 N·m | Main Circuit 6 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 105 A
Connecting Capacity Main Circuit UL/CSA
Rigid Stranded 1/2x 6-1 AWG
Connecting Capacity Auxiliary Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG | Rigid Stranded 1/2x 18-14 AWG
Connecting Capacity Control Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG | Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSA
Auxiliary Circuit 11 in·lb | Control Circuit 11 in·lb | Main Circuit 53 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 7-1/2 A | (200 ... 208 V AC) Three Phase 25 A | (220 ... 240 V AC) Three Phase 30 A | (240 V AC) Single Phase 15 A | (440 ... 480 V AC) Three Phase 60 A | (550 ... 600 V AC) Three Phase 75 A
Ambient Air Temperature
Close to Contactor for Storage -60 ... +80 °C | Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Resistance to Vibrations
3g Closed Position & 2g Open Position 5 ... 300 Hz
Pollution Degree
3
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
Yes
End Of Life Disassembling Instructions
End of life instruction AF(S)40/52/65/80/96(B)(RT) Contactors
Environmental Product Declaration - EPD
Environmental Product Declaration AF80, AF96 (CN) Contactors | Environmental Product Declaration AF(S)80(B), AF(S)96(B) (FR)
Sustainable Material Content in Packaging (wt. %)
FSC Recycled Paper - 94.6 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 28.2 %
A2L Certificate – UL
UL-US Certificate of Compliance AF40 ... AF96 3-pole contactors - UL 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers | UL-CA Certificate of Compliance AF40 ... AF96 3-pole contactors - CSA C22.2 No. 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers
ABS Certificate
ABS Certificate, AF(S)09 to AF(S)96 contactors, NF contactor relays and CA4, CC4, CAL4, CAT4 auxiliary contact blocks, TEF4 electronic timers
BV Certificate
BV_2634H36994B1
CB Certificate
CB Certificate AF(S)80(B), AF(S)96(B) 3 and 4-pole contactors
CCC Certificate
CQC Certificate, AC Contactor, AF(S)*80-30-**-**, AF80-40-**-**, AF80-22-**-**, AF(S)96-30-**-**, Made in France
Declaration of Conformity - CCC
CCC Declaration of Conformity, AC Contactor, AF*80-30-**-**, AF80-40-**-**, AF80-22-**-**, AF*96-30-**-**, Made in France
Declaration of Conformity - CE
EU Declaration of Conformity AF09, AF16, AF26, AF38, AF40, AF52, AF80, 4-pole Contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09, AF16, AF26, AF38, AF40, AF52, AF80, 4-pole Contactors
UL Certificate
UL-US Certificate of Compliance AF40(B)...80(B) 4-pole contactors | UL-CA Certificate of Compliance AF40(B)...80(B) 4-pole contactors
UL Listing Card
UL_E312527
Package Level 1 Units
box 1 piece
Package Level 1 Width
144 mm
Package Level 1 Depth / Length
147 mm
Package Level 1 Height
109 mm
Package Level 1 Gross Weight
1.69 kg
Package Level 1 EAN
3471523135611
Package Level 2 Units
box 8 piece
Package Level 2 Width
250 mm
Package Level 2 Depth / Length
300 mm
Package Level 2 Height
300 mm
Package Level 2 Gross Weight
13.52 kg
Package Level 3 Units
192 piece
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
Feature AF technology with a wide control voltage range and built-in surge protection → Business Impact Reduces nuisance tripping and energy waste while delivering stable motor control; Application Ideal for plants with voltage fluctuations and variable demand. Feature Four main NO contacts plus one NO and one NC auxiliary contact → Business Impact Enables straightforward signaling and interlocking within motor control circuits; Application Simplifies wiring in conveyors and pump applications. Feature Rated operational current AC-1 up to 125 A at 690 V and AC-3 up to 80 A at 415–690 V → Business Impact Supports high-power motor loads up to 37 kW at 400 V, improving drive efficiency; Application Suitable for medium to large motors in manufacturing lines. Feature DIN rail mounting TH35-15 and screw-terminal connections → Business Impact Speeds installation and simplifies retrofits in existing panels; Application Ideal for OEM panels and retrofit projects where space is at a premium. Feature Built-in compliance with IEC/EN 60947-1, IEC/EN 60947-4-1, UL/CSA, CE, and UKCA → Business Impact Reduces certification effort and accelerates time-to-line for global deployments; Application Meets global safety and performance requirements for multi-region projects. Feature Robust environmental specs and RoHS/REACH/CMRT compliance → Business Impact Supports sustainability goals and regulatory readiness; Application Beneficial for long-term service life in harsh environments.
Get a Quick Quote for a ABB 1SBL397201R1111
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SBL397201R1111?
Enquire Now
FAQs
This ABB 1SBL397201R1111 uses TH35-15 DIN rail mounting for rapid installation. Connect main circuit cables to screw terminals rated for flexible or ferrule-ended conductors up to 50 mm², and attach the auxiliary circuit and control circuit conductors with the specified cross-sections. The unit supports 2x M4 or 2x M6 mounting screws for optional fixed mounting and features plug-in auxiliary contact blocks for signaling expansion. Follow the included torque specs to ensure reliable connections and maintain IP20/IP10 protection as noted in the datasheet.
For AC-1 operation at 690 V, Ie is 125 A (60 °C) and 105 A (60 °C) or 90 A (70 °C). For AC-3 operation, Ie is 80 A at 415–690 V, and the device offers DC-13 ratings across multiple voltages (e.g., 24 V up to 600 V) with corresponding current ratings. These figures align with typical motor starter requirements, enabling motors up to approximately 37 kW at 400 V in AC-3 service. Always verify exact derating for your operating temperature and supply.
Yes. The ABB 1SBL397201R1111 is specified for power applications up to about 37 kW at 400 V (AC-3 duty) and supports main circuit currents compatible with typical plant motors. With its four-pole configuration, integrated auxiliary contact, and AF technology, it provides reliable switching under normal and transient loads, making it well-suited for conveyors, pumps, and process equipment in industrial automation lines.
The device carries IEC/EN 60947-1, IEC/EN 60947-4-1, and IEC/EN 60947-5-1 standards, along with UL and CSA general-use approvals. It also includes CE and UKCA declarations for market access across Europe and the UK. UL listings and related certificates (UL 60335-2-40) ensure compliance for household and similar appliances, broadening applicability in diverse sectors and regions.
AF technology provides a wide control voltage range, reducing panel energy consumption and stabilizing operation in networks with voltage fluctuations. Built-in surge protection minimizes wear and nuisance trips, lowering maintenance needs and improving uptime. In practice, this translates to longer service intervals, reduced warranty events, and faster project ROI due to fewer panel rewiring requirements and quicker commissioning.