ABB AF80B-22-00-13 Block Contactor - IEC 60947-4-1
Part Number: 1SBL397561R1300
Quick Summary
ABB AF80B-22-00-13 Block Contactor is a 4-pole motor switch designed for reliable control of 3-phase motors in industrial automation. Unstable control voltages and panel energy waste are common pain points this model helps mitigate with a wide control voltage range (100–250 V AC/DC). It carries IEC/EN 60947-4-1 and UL/CSA approvals, with CE conformance and built-in surge protection to simplify compliance and uptime. Its compact footprint, DIN rail mounting (TH35-15), and easy accessory integration support faster project commissioning while reducing panel space and installation costs. Designed to withstand demanding environments, it offers broad compatibility and a low total cost of ownership for modern control panels.
Product Information
Extended Description
1SBL397561R1300 ABB: The AF80B-22-00-13 is a 4 pole - 1000 V IEC or 600 UL contactor with screw terminals, controlling motors up to 37 kW / 400 V AC (AC-3) and switching power circuits up to 125 A (AC-1) or 105 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
Motor control and protection for Rolling stock application_PDF
Instructions and Manuals
Installation instructions AF(C)40(B)...80(B)-40/22 Contactors, CA4, CAL4, CAT4, CC4, LDC4 Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
90 mm
Product Net Depth / Length
116 mm
Product Net Height
125.5 mm
Product Net Weight
1.44 kg
Number of Main Contacts NO
2
Number of Main Contacts NC
2
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Number of Poles
4P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives.
Rated Operational Voltage
Main Circuit 1000 V
Rated Frequency (f)
Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 125 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 125 A | (690 V) 60 °C 105 A | (690 V) 70 °C 90 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 80 A | (440 V) 60 °C 80 A | (500 V) 60 °C 65 A | (690 V) 60 °C 49 A | (1000 V) 60 °C 25 A | (380 / 400 V) 60 °C 80 A | (220 / 230 / 240 V) 60 °C 80 A
Rated Operational Power AC-3 (Pe)
(415 V) 45 kW | (440 V) 45 kW | (500 V) 45 kW | (690 V) 45 kW | (1000 V) 35 kW | (380 / 400 V) 37 kW | (220 / 230 / 240 V) 22 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 780 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 140 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 300 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1200 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 450 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1150 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 750 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 1000 V | acc. to UL/CSA 600 V
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 100 ... 250 V | 60 Hz 100 ... 250 V | DC Operation 100 ... 250 V
Coil Consumption
Average Holding Value 50 / 60 Hz 4 V·A | Average Holding Value DC 2 W
Power Loss
at Rated Operating Conditions AC-1 per Pole 8 W | at Rated Operating Conditions AC-3 per Pole 3.2 W
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 6 ... 50 mm² | Flexible with Insulated Ferrule 1/2x 6 ... 50 mm² | Rigid Stranded 1x 6 ... 70 mm² | Rigid Stranded 2x 6 ... 50 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Auxiliary Circuit 0 mm | Control Circuit 10 mm | Main Circuit 17 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Recommended Screw Driver
Pozidriv PZ
Tightening Torque
Control Circuit 1.2 N·m | Main Circuit 6 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
Continuous Current Rating NEMA
0 A
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 105 A
Connecting Capacity Main Circuit UL/CSA
Rigid Stranded 1/2x 6-1 AWG
Connecting Capacity Control Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG | Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSA
Control Circuit 11 in·lb | Main Circuit 53 in·lb
Ambient Air Temperature
Close to Contactor for Storage -60 ... +80 °C | Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Shock and Vibration Withstand acc. to IEC 61373
Category 1, Class B
Pollution Degree
3
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
Yes
End Of Life Disassembling Instructions
End of life instruction AF(S)40/52/65/80/96(B)(RT) Contactors
Environmental Product Declaration - EPD
Environmental Product Declaration AF(S)80(B), AF(S)96(B) (FR)
Sustainable Material Content in Packaging (wt. %)
FSC Recycled Paper - 94.6 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 28.2 %
A2L Certificate – UL
UL-US Certificate of Compliance AF40 ... AF96 3-pole contactors - UL 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers | UL-CA Certificate of Compliance AF40 ... AF96 3-pole contactors - CSA C22.2 No. 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers
CB Certificate
CB Certificate AF(S)80(B), AF(S)96(B) 3 and 4-pole contactors
CCC Certificate
CQC Certificate, AC Contactor, AF(S)*80-30-**-**, AF80-40-**-**, AF80-22-**-**, AF(S)96-30-**-**, Made in France
Declaration of Conformity - CE
EU Declaration of Conformity AF09 ... AF38(Z)B..(K), AF40B ... AF96B 3 and 4-pole contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09 ... AF38(Z)B..(K), AF40B ... AF96B 3 and 4-pole contactors
UL Certificate
UL-US Certificate of Compliance AF40(B)...80(B) 4-pole contactors | UL-CA Certificate of Compliance AF40(B)...80(B) 4-pole contactors
Package Level 1 Units
box 1 piece
Package Level 1 Width
150 mm
Package Level 1 Depth / Length
150 mm
Package Level 1 Height
103 mm
Package Level 1 Gross Weight
1.57 kg
Package Level 1 EAN
3471523025479
Package Level 2 Units
box 8 piece
Package Level 2 Width
250 mm
Package Level 2 Depth / Length
300 mm
Package Level 2 Height
300 mm
Package Level 2 Gross Weight
12.56 kg
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
Feature wide control-voltage range (100–250 V AC/50/60 Hz and DC) → Business Impact reduces wiring complexity and voltage mismatch risk, boosting reliability in machines and panels → Application suitable for diverse machine controls and automation panels. Feature built-in surge protection with AF technology → Business Impact protects contacts from voltage spikes, lowers need for external protection devices, and extends component life → Application in conveyors, presses, and industrial drives with unstable supply. Feature four main contacts (2 NO + 2 NC) on a 4P block contactor with rated currents up to 125 A AC-1 and 80 A AC-3 at specified voltages → Business Impact supports high-load motor control with fewer devices and simpler schematics → Application for medium-power motors up to roughly 37 kW (AC-3) and 45 kW (AC-3 at higher voltages) in typical ABB panel designs. Feature compact DIN-rail mounting (TH35-15) and screw-terminal wiring → Business Impact enables quick, secure installation and straightforward maintenance → Application in standard control cabinets or machine panels with fast commissioning. Feature compatibility with add-on auxiliary contact blocks and a wide range of accessories → Business Impact scalable control logic and easier integration into existing control architectures → Application for expandability in automation projects and rolling stock motor protection. Feature precise dimensions and weight (90 mm width, 116 mm depth, 125.5 mm height, 1.44 kg) → Business Impact minimizes enclosure footprint and material costs while maintaining robust mechanical durability → Application in space-constrained panels and compact installations.
Get a Quick Quote for a ABB 1SBL397561R1300
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SBL397561R1300?
Enquire Now
FAQs
The AF80B-22-00-13 mounts on a TH35-15 DIN rail and uses screw terminals for both main and control circuits. Main circuit connections accept flexible with ferrule 1/2 x 6–50 mm² or rigid options, while control circuit accepts ferrule 0.75–2.5 mm² or solid/stranded 0.75–2.5 mm². For installation, you can secure with two M4 or two M6 screws diagonally. This combination simplifies panel wiring and ensures a stable, łat installation in standard control cabinets.
For AC-1 operation at 690 V, the contactor carries up to 125 A; at 60 °C, 105 A; and at 70 °C, 90 A. For AC-3 operation, ratings vary by voltage: at 415–440 V, 80 A; at 500 V, 65 A; at 690 V, 49 A. Power handling includes about 45 kW at several voltages (e.g., 415–690 V) and 37 kW at 380/400 V, aligning with typical motor-control requirements.
Yes, the AF80B-22-00-13 is designed for robust motor control with four poles and up to 125 A AC-1, 80 A AC-3 ratings, plus built-in surge protection. Its compact form factor and wide control-voltage tolerance help manage start transients in machines or rolling stock environments, while DIN-rail mounting facilitates integration into standard rolling stock or industrial control cabinets.
This contactor complies with IEC/EN 60947-4-1 and UL 60947-4-1/60947-1 family requirements, with CSA equivalents and CE declarations. It also carries relevant DoCs and UKCA/UL certificates for related configurations. For your exact application, confirm part-level compliance with ABB representatives to ensure alignment with regional regulations and installation standards.
The built-in surge protection reduces external components and maintenance, while the wide coil-voltage tolerance minimizes panel reconfiguration costs. Coil consumption is low (4 V·A holding; 2 W DC), supporting energy efficiency. With long mechanical life and straightforward accessory expansion, it lowers total cost of ownership and speeds up project delivery in automation projects.