ABB AF96-30-11-11 Contactor - 3P, 1000V IEC/UL

Part Number: 1SBL407001R1111
Manufacturer
ABB
Part number
1SBL407001R1111

Quick Summary

ABB AF96-30-11-11 Contactor enables reliable three-phase motor control for motors up to 45 kW in industrial equipment. In networks with voltage fluctuations, its wide control voltage range and built-in surge protection minimize panel energy waste and equipment wear. The device carries IEC/EN standards, UL/CSA listings, and CE/UKCA marks to support global compliance. With a compact AF block design and easy add-on auxiliary contacts, it scales for growing control needs while reducing panel space and maintenance costs. Coil options include 24-60 V AC, 20-60 V DC, and it offers robust performance across a wide temperature range, making it suitable for demanding industrial environments.

Product Information

Extended Description

1SBL407001R1111 ABB: The AF96-30-11-11 is a 3 pole - 1000 V IEC or 600 UL contactor with pre-mounted auxiliary contacts and screw terminals, controlling motors up to 45 kW / 400 V AC (AC-3) or 60 hp / 480 V UL and switching power circuits up to 130 A (AC-1) or 115 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (24-60 V 50/60 Hz and 20-60 V DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
1SBC100214C0202 - Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) - Edition 2024
Instructions and Manuals
Installation instructions AF(C)40(B)...96(B)-30 Contactors, CA4, CAL4, CAT4, CC4, LDC4 Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
82 mm
Product Net Depth / Length
116 mm
Product Net Height
125.5 mm
Product Net Weight
1.26 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
1
Number of Poles
3P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22
Rated Operational Voltage
Auxiliary Circuit 690 V | Main Circuit 1000 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 Hz | Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 130 A | acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 130 A | (690 V) 60 °C 105 A | (690 V) 70 °C 90 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 96 A | (440 V) 60 °C 96 A | (500 V) 60 °C 80 A | (690 V) 60 °C 57 A | (1000 V) 60 °C 30 A | (380 / 400 V) 60 °C 105 A | (220 / 230 / 240 V) 60 °C 105 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 96 A | (440 V) 60 °C 96 A | (500 V) 60 °C 80 A | (690 V) 60 °C 57 A | (380 / 400 V) 60 °C 105 A | (220 / 230 / 240 V) 60 °C 105 A
Rated Operational Current AC-15 (Ie)
(500 V) 2 A | (690 V) 2 A | (24 / 127 V) 6 A | (220 / 240 V) 4 A | (400 / 440 V) 3 A
Rated Operational Current DC-1 (Ie)
(110 V) 2 Poles in Series, 40 °C 130 A | (110 V) 2 Poles in Series, 60 °C 105 A | (110 V) 2 Poles in Series, 70 °C 90 A | (110 V) 3 Poles in Series, 40 °C 130 A | (110 V) 3 Poles in Series, 60 °C 105 A | (110 V) 3 Poles in Series, 70 °C 90 A | (220 V) 3 Poles in Series, 40 °C 125 A | (220 V) 3 Poles in Series, 60 °C 105 A | (220 V) 3 Poles in Series, 70 °C 90 A | (72 V) 1-Pole, 40 °C 130 A | (72 V) 1-Pole, 60 °C 105 A | (72 V) 1-Pole, 70 °C 90 A | (72 V) 2 Poles in Series, 40 °C 130 A | (72 V) 2 Poles in Series, 60 °C 105 A | (72 V) 2 Poles in Series, 70 °C 90 A | (72 V) 3 Poles in Series, 40 °C 130 A | (72 V) 3 Poles in Series, 60 °C 105 A | (72 V) 3 Poles in Series, 70 °C 90 A
Rated Operational Current DC-3 (Ie)
(110 V) 2 Poles in Series, 40 °C 130 A | (110 V) 2 Poles in Series, 60 °C 105 A | (110 V) 2 Poles in Series, 70 °C 90 A | (110 V) 3 Poles in Series, 40 °C 130 A | (110 V) 3 Poles in Series, 60 °C 105 A | (110 V) 3 Poles in Series, 70 °C 90 A | (220 V) 3 Poles in Series, 40 °C 130 A | (220 V) 3 Poles in Series, 60 °C 105 A | (220 V) 3 Poles in Series, 70 °C 90 A | (72 V) 1-Pole, 40 °C 130 A | (72 V) 1-Pole, 60 °C 105 A | (72 V) 1-Pole, 70 °C 90 A | (72 V) 2 Poles in Series, 40 °C 130 A | (72 V) 2 Poles in Series, 60 °C 105 A | (72 V) 2 Poles in Series, 70 °C 90 A | (72 V) 3 Poles in Series, 40 °C 130 A | (72 V) 3 Poles in Series, 60 °C 105 A | (72 V) 3 Poles in Series, 70 °C 90 A
Rated Operational Current DC-5 (Ie)
(110 V) 2 Poles in Series, 40 °C 130 A | (110 V) 2 Poles in Series, 60 °C 105 A | (110 V) 2 Poles in Series, 70 °C 90 A | (110 V) 3 Poles in Series, 40 °C 130 A | (110 V) 3 Poles in Series, 60 °C 105 A | (110 V) 3 Poles in Series, 70 °C 90 A | (220 V) 3 Poles in Series, 40 °C 130 A | (220 V) 3 Poles in Series, 60 °C 105 A | (220 V) 3 Poles in Series, 70 °C 90 A | (72 V) 1-Pole, 40 °C 130 A | (72 V) 1-Pole, 60 °C 105 A | (72 V) 1-Pole, 70 °C 90 A | (72 V) 2 Poles in Series, 40 °C 130 A | (72 V) 2 Poles in Series, 60 °C 105 A | (72 V) 2 Poles in Series, 70 °C 90 A | (72 V) 3 Poles in Series, 40 °C 130 A | (72 V) 3 Poles in Series, 60 °C 105 A | (72 V) 3 Poles in Series, 70 °C 90 A
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W | (48 V) 2.8 A / 134 W | (72 V) 1 A / 72 W | (110 V) 0.55 A / 60 W | (125 V) 0.55 A / 69 W | (220 V) 0.27 A / 60 W | (250 V) 0.27 A / 68 W | (400 V) 0.15 A / 60 W | (500 V) 0.13 A / 65 W | (600 V) 0.1 A / 60 W
Rated Operational Power AC-3 (Pe)
(415 V) 55 kW | (440 V) 55 kW | (500 V) 55 kW | (690 V) 55 kW | (1000 V) 40 kW | (380 / 400 V) 45 kW | (380 / 400 V) 55 kW | (220 / 230 / 240 V) 25 kW | (220 / 230 / 240 V) 30 kW
Rated Operational Power AC-3e (Pe)
(415 V) 55 kW | (440 V) 55 kW | (500 V) 55 kW | (690 V) 55 kW | (380 / 400 V) 45 kW | (380 / 400 V) 55 kW | (220 / 230 / 240 V) 25 kW | (220 / 230 / 240 V) 30 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 840 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 140 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 300 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1200 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 450 A | for 0.1 s 140 A | for 1 s 100 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1150 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 750 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 1000 V | acc. to IEC 60947-5-1 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
8 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-15) 1200 cycles per hour | (AC-2 / AC-4) 150 cycles per hour | (AC-3) 1200 cycles per hour | (DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 24 ... 60 V | 60 Hz 24 ... 60 V | DC Operation 20 ... 60 V
Coil Consumption
Average Holding Value 50 / 60 Hz 4 V·A | Average Holding Value 50 Hz 4 V·A | Average Holding Value 60 Hz 4 V·A | Average Holding Value DC 2 W | Average Holding Value, from Warm State 2 W
Power Loss
at 6 A per Pole 0.1 W | at Rated Operating Conditions AC-1 per Pole 8.2 W | at Rated Operating Conditions AC-3 per Pole 4.5 W
Operate Time
Between Coil De-energization and NC Contact Closing 19 ... 105 ms | Between Coil De-energization and NO Contact Opening 17 ... 100 ms | Between Coil Energization and NC Contact Opening 38 ... 95 ms | Between Coil Energization and NO Contact Closing 42 ... 100 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 6 ... 50 mm² | Flexible with Insulated Ferrule 1/2x 6 ... 50 mm² | Rigid Stranded 1x 6 ... 70 mm² | Rigid Stranded 2x 6 ... 50 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Rigid 1/2x 1 ... 2.5 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Auxiliary Circuit 10 mm | Control Circuit 10 mm | Main Circuit 17 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Recommended Screw Driver
Pozidriv PZ
Tightening Torque
Auxiliary Circuit 1.2 N·m | Control Circuit 1.2 N·m | Main Circuit 6 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 115 A
Horsepower Rating UL/CSA
(120 V AC) Single Phase 7-1/2 hp | (200 ... 208 V AC) Three Phase 30 hp | (220 ... 240 V AC) Three Phase 40 hp | (240 V AC) Single Phase 20 hp | (440 ... 480 V AC) Three Phase 75 hp | (550 ... 600 V AC) Three Phase 75 hp
Connecting Capacity Main Circuit UL/CSA
Rigid Stranded 1/2x 6-1 AWG
Tightening Torque UL/CSA
Auxiliary Circuit 11 in·lb | Control Circuit 11 in·lb | Main Circuit 53 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 80 A | (200 ... 208 V AC) Three Phase 92 A | (220 ... 240 V AC) Three Phase 80 A | (240 V AC) Single Phase 88 A | (440 ... 480 V AC) Three Phase 77 A | (550 ... 600 V AC) Three Phase 77 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -40 ... 70 °C | Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27
Closed, Shock Direction: A 25 g | Closed, Shock Direction: B1 25 g | Closed, Shock Direction: B2 15 g | Closed, Shock Direction: C1 25 g | Closed, Shock Direction: C2 25 g | Open, Shock Direction: B1 5 g
Resistance to Vibrations
3g Closed Position & 3g Open Position 5 ... 300 Hz
Pollution Degree
3
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
Yes
End Of Life Disassembling Instructions
End of life instruction AF(S)40/52/65/80/96(B)(RT) Contactors
Environmental Product Declaration - EPD
Environmental Product Declaration AF80, AF96 (CN) Contactors | Environmental Product Declaration AF(S)80(B), AF(S)96(B) (FR)
Sustainable Material Content in Packaging (wt. %)
FSC Recycled Paper - 94.6 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 28.2 %
A2L Certificate – UL
UL-US Certificate of Compliance AF40 ... AF96 3-pole contactors - UL 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers | UL-CA Certificate of Compliance AF40 ... AF96 3-pole contactors - CSA C22.2 No. 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers
ABS Certificate
ABS Certificate, AF(S)09 to AF(S)96 contactors, NF contactor relays and CA4, CC4, CAL4, CAT4 auxiliary contact blocks, TEF4 electronic timers
BV Certificate
BV_2634H36994B1
CB Certificate
CB Certificate AF(S)80(B), AF(S)96(B) 3 and 4-pole contactors
CCC Certificate
CQC Certificate, AC Contactor, AF(S)*80-30-**-**, AF80-40-**-**, AF80-22-**-**, AF(S)96-30-**-**, Made in France
Declaration of Conformity - CCC
CCC Declaration of Conformity, AC Contactor, AF*80-30-**-**, AF80-40-**-**, AF80-22-**-**, AF*96-30-**-**, Made in France
Declaration of Conformity - CE
EU Declaration of Conformity AF09... AF96-30-.., AF09...38(Z)-30..K 3-pole Contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09... AF96-30-.., AF09...38(Z)-30..K 3-pole Contactors
DNV Certificate
DNV Certificate AF(S)09...96 3-pole & AF09...80 4-pole contactors with screw, spring, push-in terminals
KC Certificate
KC Certificate AF80, AF96 3-pole Contactors
LR Certificate
LRS Certificate AF(S)09..(K) ... AF96 3 and 4-pole contactors and CA(L)4..(K), CAT4, CC4 auxiliary contact blocks
RINA Certificate
Rina Certificate for AF09...AF96 contactors, NF contactor relays and accessories, screw and spring terminals
RMRS Certificate
RMRS Certificate AF(S)09(S)...AF(S)38 3-pole and 4-pole, AF(S)40..96 3-pole contactors with screw, push-in and spring terminals
UL Certificate
UL-US-L312527-1141-10303102-9 | UL-CA-L312527-4141-10303102-9
UL Listing Card
UL_E312527
Package Level 1 Units
box 1 piece
Package Level 1 Width
150 mm
Package Level 1 Depth / Length
150 mm
Package Level 1 Height
103 mm
Package Level 1 Gross Weight
1.38 kg
Package Level 1 EAN
3471523133310
Package Level 2 Units
box 8 piece
Package Level 2 Width
250 mm
Package Level 2 Depth / Length
300 mm
Package Level 2 Height
300 mm
Package Level 2 Gross Weight
11.04 kg
Package Level 3 Units
192 piece
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
E-Number (Finland)
3707140
Feature: Wide control voltage range 24-60 Hz AC and 20-60 V DC; Business Impact: Allows stable operation across fluctuating supply voltages, reducing panel redesigns and energy waste; Application: Machine control panels in factories with variable mains. Application: Compatible with 24-60 V control circuits in modern automation setups. Feature: Built-in surge protection with AF technology; Business Impact: Enhances reliability and protects downstream electronics, lowering maintenance costs; Application: Motors and power circuits in packaging, material handling, and process lines. Feature: 3P main contacts plus 1 NO and 1 NC auxiliary contacts; Business Impact: Extends control logic without additional devices, saving panel space; Application: Sequence control for conveyors and pumps. Feature: Rated Operational Current AC-3 up to 96 A at 415–690 V; Business Impact: Supports high-power motors with compact sizing; Application: Heavy-duty drives in lift systems and large fans. Feature: Rated insulation voltage up to 1000 V and 690 V on auxiliary; Business Impact: Broad insulation margin improves safety and lifecycle; Application: Standards-compliant installations in mixed-voltage environments. Feature: DIN rail mounting TH35-15; Business Impact: Fast, secure installation with scalable accessory options; Application: Modern switchgear in control cabinets. Feature: Screw terminals with defined torque; Business Impact: Reliable, vibration-resistant connections that ease maintenance; Application: All main and auxiliary circuits. Feature: High mechanical switching frequency up to 3600 cycles/hour; Business Impact: Quick response for demanding start-stop sequences; Application: Conveyor drives and packaging lines. Feature: Compliance certifications including UL, CSA, CE, UKCA; Business Impact: Enables global deployment with reduced validation time; Application: Multinational equipment projects. Feature: Compact footprint with optional accessory blocks; Business Impact: Saves panel space and enables future expansion; Application: Retrofit projects in limited enclosures.

Get a Quick Quote for a ABB 1SBL407001R1111

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SBL407001R1111? Enquire Now

FAQs

The AF96-30-11-11 is designed for easy DIN rail mounting (TH35-15) and uses screw terminals for main, auxiliary, and control circuits. This combination supports fast, secure installation in standard control cabinets, minimizes wiring errors, and provides robust connections suitable for vibration-prone industrial environments.
Main circuit current ratings include up to 96 A AC-3 at 415–690 V and up to 130 A AC-1 at appropriate voltages, with a main circuit insulation up to 1000 V. Coil options cover 24–60 V AC/50/60 Hz and 20–60 V DC, enabling operation across fluctuating control voltages and improving panel energy efficiency.
Yes. It supports 3P motor control with high switching frequency capability and robust thermal performance. Its IP20 terminal protection, vibration tolerance, and wide ambient temperature range (-40 to 70 C with/without a thermal overload relay) make it well-suited for conveyors, pumps, and milling lines in industrial settings.
This contactor carries UL and CSA listings, CE and UKCA markings, and CCC/CQC declarations where applicable. These certifications validate safety, performance, and regulatory compliance for markets across North America and Europe, reducing validation time for international projects.
The built-in surge protection and wide control voltage range reduce nuisance trips and energy waste, while the compact block design and optional auxiliary contacts simplify future expansion. Over the life of a line, these features translate to lower maintenance costs, fewer spare parts, and a faster return on investment in automation upgrades.