ABB 1SBL407061R1211 Block Contactor - AF Tech 48-130 V
Part Number: 1SBL407061R1211
Quick Summary
The ABB AF contactor 1SBL407061R1211 is a three-pole block contactor with AF technology designed to control motors in industrial automation and rolling stock applications. It addresses voltage variability and energy waste by offering a wide control voltage range of 48-130 V AC/DC and built-in surge protection, reducing panel energy consumption and nuisance trips. Certified to IEC/EN 60947-1 and 60947-4-1, with UL/CSA approvals and EN 50155 applicability for railway environments, it helps maintain regulatory compliance across regions. With easy DIN rail mounting, add-on auxiliary blocks, and a compact footprint, it supports scalable automation while delivering reliable motor control and protection. This combination delivers efficiency, reliability, and a lower total cost of ownership for modern control panels.
Product Information
Extended Description
1SBL407061R1211 ABB: The AF96B-30-11-12 is a 3 pole - 1000 V IEC or 600 UL contactor with pre-mounted auxiliary contacts and screw terminals, controlling motors up to 45 kW / 400 V AC (AC-3) or 60 hp / 480 V UL and switching power circuits up to 130 A (AC-1) or 115 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (48-130 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
Motor control and protection for Rolling stock application_PDF
Instructions and Manuals
Installation instructions AF(C)40(B)...96(B)-30 Contactors, CA4, CAL4, CAT4, CC4, LDC4 Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
82 mm
Product Net Depth / Length
116 mm
Product Net Height
125.5 mm
Product Net Weight
1.26 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
1
Number of Poles
3P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives.
Rated Operational Voltage
Auxiliary Circuit 690 V | Main Circuit 1000 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 Hz | Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 130 A | acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 130 A | (690 V) 60 °C 105 A | (690 V) 70 °C 90 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 96 A | (440 V) 60 °C 96 A | (500 V) 60 °C 80 A | (690 V) 60 °C 57 A | (1000 V) 60 °C 30 A | (380 / 400 V) 60 °C 105 A | (220 / 230 / 240 V) 60 °C 105 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 96 A | (440 V) 60 °C 96 A | (500 V) 60 °C 80 A | (690 V) 60 °C 57 A | (380 / 400 V) 60 °C 105 A | (220 / 230 / 240 V) 60 °C 105 A
Rated Operational Current AC-15 (Ie)
(500 V) 2 A | (690 V) 2 A | (24 / 127 V) 6 A | (220 / 240 V) 4 A | (400 / 440 V) 3 A
Rated Operational Current DC-1 (Ie)
(110 V) 2 Poles in Series, 40 °C 130 A | (110 V) 2 Poles in Series, 60 °C 105 A | (110 V) 2 Poles in Series, 70 °C 90 A | (110 V) 3 Poles in Series, 40 °C 130 A | (110 V) 3 Poles in Series, 60 °C 105 A | (110 V) 3 Poles in Series, 70 °C 90 A | (220 V) 3 Poles in Series, 40 °C 125 A | (220 V) 3 Poles in Series, 60 °C 105 A | (220 V) 3 Poles in Series, 70 °C 90 A | (72 V) 1-Pole, 40 °C 130 A | (72 V) 1-Pole, 60 °C 105 A | (72 V) 1-Pole, 70 °C 90 A | (72 V) 2 Poles in Series, 40 °C 130 A | (72 V) 2 Poles in Series, 60 °C 105 A | (72 V) 2 Poles in Series, 70 °C 90 A | (72 V) 3 Poles in Series, 40 °C 130 A | (72 V) 3 Poles in Series, 60 °C 105 A | (72 V) 3 Poles in Series, 70 °C 90 A
Rated Operational Current DC-3 (Ie)
(110 V) 2 Poles in Series, 40 °C 130 A | (110 V) 2 Poles in Series, 60 °C 105 A | (110 V) 2 Poles in Series, 70 °C 90 A | (110 V) 3 Poles in Series, 40 °C 130 A | (110 V) 3 Poles in Series, 60 °C 105 A | (110 V) 3 Poles in Series, 70 °C 90 A | (220 V) 3 Poles in Series, 40 °C 130 A | (220 V) 3 Poles in Series, 60 °C 105 A | (220 V) 3 Poles in Series, 70 °C 90 A | (72 V) 1-Pole, 40 °C 130 A | (72 V) 1-Pole, 60 °C 105 A | (72 V) 1-Pole, 70 °C 90 A | (72 V) 2 Poles in Series, 40 °C 130 A | (72 V) 2 Poles in Series, 60 °C 105 A | (72 V) 2 Poles in Series, 70 °C 90 A | (72 V) 3 Poles in Series, 40 °C 130 A | (72 V) 3 Poles in Series, 60 °C 105 A | (72 V) 3 Poles in Series, 70 °C 90 A
Rated Operational Current DC-5 (Ie)
(110 V) 2 Poles in Series, 40 °C 130 A | (110 V) 2 Poles in Series, 60 °C 105 A | (110 V) 2 Poles in Series, 70 °C 90 A | (110 V) 3 Poles in Series, 40 °C 130 A | (110 V) 3 Poles in Series, 60 °C 105 A | (110 V) 3 Poles in Series, 70 °C 90 A | (220 V) 3 Poles in Series, 40 °C 130 A | (220 V) 3 Poles in Series, 60 °C 105 A | (220 V) 3 Poles in Series, 70 °C 90 A | (72 V) 1-Pole, 40 °C 130 A | (72 V) 1-Pole, 60 °C 105 A | (72 V) 1-Pole, 70 °C 90 A | (72 V) 2 Poles in Series, 40 °C 130 A | (72 V) 2 Poles in Series, 60 °C 105 A | (72 V) 2 Poles in Series, 70 °C 90 A | (72 V) 3 Poles in Series, 40 °C 130 A | (72 V) 3 Poles in Series, 60 °C 105 A | (72 V) 3 Poles in Series, 70 °C 90 A
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W | (48 V) 2.8 A / 134 W | (72 V) 1 A / 72 W | (110 V) 1.1 A / 121 W | (125 V) 0.55 A / 69 W | (220 V) 0.27 A / 60 W | (250 V) 0.27 A / 68 W | (400 V) 0.15 A / 60 W | (500 V) 0.13 A / 65 W | (600 V) 0.1 A / 60 W
Rated Operational Power AC-3 (Pe)
(415 V) 55 kW | (440 V) 55 kW | (500 V) 55 kW | (690 V) 55 kW | (1000 V) 40 kW | (380 / 400 V) 100 kW | (380 / 400 V) 45 kW | (380 / 400 V) 55 kW | (220 / 230 / 240 V) 55 kW | (220 / 230 / 240 V) 25 kW | (220 / 230 / 240 V) 30 kW
Rated Operational Power AC-3e (Pe)
(415 V) 55 kW | (440 V) 55 kW | (500 V) 55 kW | (690 V) 55 kW | (380 / 400 V) 45 kW | (380 / 400 V) 55 kW | (220 / 230 / 240 V) 25 kW | (220 / 230 / 240 V) 30 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 840 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 140 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 300 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1200 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 450 A | for 0.1 s 140 A | for 1 s 100 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1150 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 750 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 1000 V | acc. to IEC 60947-5-1 690 V | acc. to UL/CSA 600 V
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-15) 1200 cycles per hour | (AC-2 / AC-4) 150 cycles per hour | (AC-3) 1200 cycles per hour | (DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 48 ... 130 V | 60 Hz 48 ... 130 V | DC Operation 48 ... 130 V
Coil Consumption
Average Holding Value 50 / 60 Hz 4 V·A | Average Holding Value DC 2 W
Power Loss
at Rated Operating Conditions AC-1 per Pole 8.2 W | at Rated Operating Conditions AC-3 per Pole 4.5 W
Operate Time
Between Coil De-energization and NC Contact Closing 19 ... 105 ms | Between Coil De-energization and NO Contact Opening 17 ... 100 ms | Between Coil Energization and NC Contact Opening 38 ... 95 ms | Between Coil Energization and NO Contact Closing 42 ... 100 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 6 ... 50 mm² | Flexible with Insulated Ferrule 1/2x 6 ... 50 mm² | Rigid Stranded 1x 6 ... 70 mm² | Rigid Stranded 2x 6 ... 50 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Auxiliary Circuit 10 mm | Control Circuit 10 mm | Main Circuit 17 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Recommended Screw Driver
Pozidriv PZ
Tightening Torque
Auxiliary Circuit 1.2 N·m | Control Circuit 1.2 N·m | Main Circuit 6 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
Continuous Current Rating NEMA
0 A
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 115 A
Horsepower Rating UL/CSA
(120 V AC) Single Phase 7-1/2 hp | (200 ... 208 V AC) Three Phase 30 hp | (220 ... 240 V AC) Three Phase 40 hp | (240 V AC) Single Phase 20 hp | (440 ... 480 V AC) Three Phase 75 hp | (550 ... 600 V AC) Three Phase 75 hp
Connecting Capacity Main Circuit UL/CSA
Rigid Stranded 1/2x 6-1 AWG
Connecting Capacity Control Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG | Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSA
Auxiliary Circuit 11 in·lb | Control Circuit 11 in·lb | Main Circuit 53 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 80 A | (200 ... 208 V AC) Three Phase 92 A | (220 ... 240 V AC) Three Phase 80 A | (240 V AC) Single Phase 88 A | (440 ... 480 V AC) Three Phase 77 A | (550 ... 600 V AC) Three Phase 77 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -40 ... 70 °C | Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Shock and Vibration Withstand acc. to IEC 61373
Category 1, Class B
Pollution Degree
3
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
Yes
End Of Life Disassembling Instructions
End of life instruction AF(S)40/52/65/80/96(B)(RT) Contactors
Environmental Product Declaration - EPD
Environmental Product Declaration AF(S)80(B), AF(S)96(B) (FR)
Sustainable Material Content in Packaging (wt. %)
FSC Recycled Paper - 94.6 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 28.2 %
A2L Certificate – UL
UL-US Certificate of Compliance AF40 ... AF96 3-pole contactors - UL 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers | UL-CA Certificate of Compliance AF40 ... AF96 3-pole contactors - CSA C22.2 No. 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers
CB Certificate
CB Certificate AF(S)80(B), AF(S)96(B) 3 and 4-pole contactors
CCC Certificate
CQC Certificate, AC Contactor, AF(S)*80-30-**-**, AF80-40-**-**, AF80-22-**-**, AF(S)96-30-**-**, Made in France
Declaration of Conformity - CE
EU Declaration of Conformity AF09 ... AF38(Z)B..(K), AF40B ... AF96B 3 and 4-pole contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09 ... AF38(Z)B..(K), AF40B ... AF96B 3 and 4-pole contactors
UL Certificate
UL-US-L312527-1141-10303102-9 | UL-CA-L312527-4141-10303102-9
Package Level 1 Units
box 1 piece
Package Level 1 Width
150 mm
Package Level 1 Depth / Length
150 mm
Package Level 1 Height
103 mm
Package Level 1 Gross Weight
1.38 kg
Package Level 1 EAN
3471523025523
Package Level 2 Units
box 8 piece
Package Level 2 Width
250 mm
Package Level 2 Depth / Length
300 mm
Package Level 2 Height
300 mm
Package Level 2 Gross Weight
11.04 kg
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
Feature AF technology provides a wide control voltage range of 48-130 V and a robust coil design that tolerates voltage variations, delivering consistent operation. Business Impact This reduces misoperation and energy waste in panels subject to fluctuations, improving overall system reliability and cutting energy costs. Application Ideal for drives and motor control circuits where supply variability is common, including HVAC and rolling stock systems. Feature Built-in surge protection enhances durability by safeguarding contacts and control circuits from transient spikes. Business Impact This minimizes nuisance tripping and extends equipment life, lowering maintenance and replacement costs. Application Suitable for high-reliability industrial environments with demanding surge profiles. Feature Three main NO contacts and one auxiliary NO plus one NC contact offer extended control capability. Business Impact Enables local interlocking and status signaling without adding separate devices, reducing panel size and wiring complexity. Application Useful in legacy and new automation panels needing compact control with expanded signaling. Feature DIN rail mounting TH35-15 simplifies installation and retrofit. Business Impact Speeds up installation, reduces field wiring errors, and supports modular enclosures. Application Widely adopted in panel builders for quick deployment. Feature Compact footprint (82 mm W × 116 mm D × 125.5 mm H) and 1.26 kg weight deliver space-saving motor control. Business Impact Frees panel space for other devices and reduces shipping and handling costs. Application Suitable for compact panels in tight spaces. Feature Low coil power consumption (4 V·A holding, 2 W DC operation) lowers standby energy use. Business Impact Cuts operating costs over the life of the device and reduces thermal load in control panels. Application Improves energy efficiency in continuously energized control circuits.
Get a Quick Quote for a ABB 1SBL407061R1211
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SBL407061R1211?
Enquire Now
FAQs
Install the device on a TH35-15 DIN rail per IEC 60715, ensuring the relay is oriented for proper coil access. Use screw terminals for main circuit connections and flexible or rigid conductors as specified (1/2x 6-50 mm² for main, 0.75-2.5 mm² for auxiliary, 0.75-2.5 mm² for control). Torque values are 6 N·m on main terminals and 1.2 N·m on auxiliary and control terminals. Allow 10 mm wire stripping length for proper lug engagement.
The device is a 3-pole block contactor with main circuit rated up to 1000 V and auxiliary circuit up to 690 V. It supports 50/60 Hz operation, with AC-3 ratings down to 55 kW at higher voltages and up to 30 A at 1000 V. Coil range is 48-130 V AC or DC, and it includes 1 NO and 1 NC auxiliary contacts for signaling and interlocking.
Yes, it is suitable for rolling stock where EN 50155 applicable parts apply, and it meets multiple standards such as IEC/EN 60947-1 and 60947-4-1, UL 60947-1/4-1, and CSA equivalents. It also provides cross‑references to railway-specific components and comes with DoC/Ce UKCA documentation to support regulatory compliance in diverse markets.
It carries UL/CSA listings, CE and UKCA declarations, CB certification for AF80‑96 series, CCC in certain regions, RoHS and REACH declarations, and WEEE B2B categorization. Compliance is complemented by EN 50155 applicability for railway environments and EN 61373 vibration testing where applicable, ensuring suitability for demanding industrial and transportation applications.
The wide 48-130 V control range reduces control voltage mismatch and energy consumption, while built-in surge protection lowers failure rates in harsh networks. Its compact DIN rail design and add-on auxiliary blocks cut installation costs and panel space. Lower coil power (4 VA holding, 2 W DC) translates to ongoing energy savings and reduced cooling requirements, improving total cost of ownership.