ABB AF96B-30-11-14 3-Pole Block Contactor - IEC/UL
Part Number: 1SBL407061R1411
Quick Summary
ABB AF96B-30-11-14 is a 3-pole block contactor for reliable motor control in industrial drives. When control voltages swing or networks fluctuate, panel reliability and energy use can suffer. It meets IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-1/4-1 and CSA C22.2 with railway and vibration standards. Its compact AF technology reduces panel energy consumption, while expanding with add-on auxiliary blocks. Designed for DIN rail mounting TH35-15 and screw mounting, it simplifies panel layout and secure connections. With wide control voltage tolerance 250-500 V AC/50/60 Hz and DC operation, it accommodates large voltage variations. Built-in surge protection and robust mains and auxiliary contact ratings support demanding applications across varied voltage systems. The ABB EcoSolutions approach adds value through sustainability and lifecycle considerations.
Product Information
Extended Description
1SBL407061R1411 ABB: The AF96B-30-11-14 is a 3 pole - 1000 V IEC or 600 UL contactor with pre-mounted auxiliary contacts and screw terminals, controlling motors up to 45 kW / 400 V AC (AC-3) or 60 hp / 480 V UL and switching power circuits up to 130 A (AC-1) or 115 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (250-500 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
Motor control and protection for Rolling stock application_PDF
Instructions and Manuals
Installation instructions AF(C)40(B)...96(B)-30 Contactors, CA4, CAL4, CAT4, CC4, LDC4 Accessories
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
82 mm
Product Net Depth / Length
116 mm
Product Net Height
125.5 mm
Product Net Weight
1.21 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
1
Number of Poles
3P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives.
Rated Operational Voltage
Auxiliary Circuit 690 V | Main Circuit 1000 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 Hz | Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 130 A | acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 130 A | (690 V) 60 °C 105 A | (690 V) 70 °C 90 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 96 A | (440 V) 60 °C 96 A | (500 V) 60 °C 80 A | (690 V) 60 °C 57 A | (1000 V) 60 °C 30 A | (380 / 400 V) 60 °C 105 A | (220 / 230 / 240 V) 60 °C 105 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 96 A | (440 V) 60 °C 96 A | (500 V) 60 °C 80 A | (690 V) 60 °C 57 A | (380 / 400 V) 60 °C 105 A | (220 / 230 / 240 V) 60 °C 105 A
Rated Operational Current AC-15 (Ie)
(500 V) 2 A | (690 V) 2 A | (24 / 127 V) 6 A | (220 / 240 V) 4 A | (400 / 440 V) 3 A
Rated Operational Current DC-1 (Ie)
(110 V) 2 Poles in Series, 40 °C 130 A | (110 V) 2 Poles in Series, 60 °C 105 A | (110 V) 2 Poles in Series, 70 °C 90 A | (110 V) 3 Poles in Series, 40 °C 130 A | (110 V) 3 Poles in Series, 60 °C 105 A | (110 V) 3 Poles in Series, 70 °C 90 A | (220 V) 3 Poles in Series, 40 °C 125 A | (220 V) 3 Poles in Series, 60 °C 105 A | (220 V) 3 Poles in Series, 70 °C 90 A | (72 V) 1-Pole, 40 °C 130 A | (72 V) 1-Pole, 60 °C 105 A | (72 V) 1-Pole, 70 °C 90 A | (72 V) 2 Poles in Series, 40 °C 130 A | (72 V) 2 Poles in Series, 60 °C 105 A | (72 V) 2 Poles in Series, 70 °C 90 A | (72 V) 3 Poles in Series, 40 °C 130 A | (72 V) 3 Poles in Series, 60 °C 105 A | (72 V) 3 Poles in Series, 70 °C 90 A
Rated Operational Current DC-3 (Ie)
(110 V) 2 Poles in Series, 40 °C 130 A | (110 V) 2 Poles in Series, 60 °C 105 A | (110 V) 2 Poles in Series, 70 °C 90 A | (110 V) 3 Poles in Series, 40 °C 130 A | (110 V) 3 Poles in Series, 60 °C 105 A | (110 V) 3 Poles in Series, 70 °C 90 A | (220 V) 3 Poles in Series, 40 °C 130 A | (220 V) 3 Poles in Series, 60 °C 105 A | (220 V) 3 Poles in Series, 70 °C 90 A | (72 V) 1-Pole, 40 °C 130 A | (72 V) 1-Pole, 60 °C 105 A | (72 V) 1-Pole, 70 °C 90 A | (72 V) 2 Poles in Series, 40 °C 130 A | (72 V) 2 Poles in Series, 60 °C 105 A | (72 V) 2 Poles in Series, 70 °C 90 A | (72 V) 3 Poles in Series, 40 °C 130 A | (72 V) 3 Poles in Series, 60 °C 105 A | (72 V) 3 Poles in Series, 70 °C 90 A
Rated Operational Current DC-5 (Ie)
(110 V) 2 Poles in Series, 40 °C 130 A | (110 V) 2 Poles in Series, 60 °C 105 A | (110 V) 2 Poles in Series, 70 °C 90 A | (110 V) 3 Poles in Series, 40 °C 130 A | (110 V) 3 Poles in Series, 60 °C 105 A | (110 V) 3 Poles in Series, 70 °C 90 A | (220 V) 3 Poles in Series, 40 °C 130 A | (220 V) 3 Poles in Series, 60 °C 105 A | (220 V) 3 Poles in Series, 70 °C 90 A | (72 V) 1-Pole, 40 °C 130 A | (72 V) 1-Pole, 60 °C 105 A | (72 V) 1-Pole, 70 °C 90 A | (72 V) 2 Poles in Series, 40 °C 130 A | (72 V) 2 Poles in Series, 60 °C 105 A | (72 V) 2 Poles in Series, 70 °C 90 A | (72 V) 3 Poles in Series, 40 °C 130 A | (72 V) 3 Poles in Series, 60 °C 105 A | (72 V) 3 Poles in Series, 70 °C 90 A
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W | (48 V) 2.8 A / 134 W | (72 V) 1 A / 72 W | (110 V) 1.1 A / 121 W | (125 V) 0.55 A / 69 W | (220 V) 0.27 A / 60 W | (250 V) 0.27 A / 68 W | (400 V) 0.15 A / 60 W | (500 V) 0.13 A / 65 W | (600 V) 0.1 A / 60 W
Rated Operational Power AC-3 (Pe)
(415 V) 55 kW | (440 V) 55 kW | (500 V) 55 kW | (690 V) 55 kW | (1000 V) 40 kW | (380 / 400 V) 100 kW | (380 / 400 V) 45 kW | (380 / 400 V) 55 kW | (220 / 230 / 240 V) 55 kW | (220 / 230 / 240 V) 25 kW | (220 / 230 / 240 V) 30 kW
Rated Operational Power AC-3e (Pe)
(415 V) 55 kW | (440 V) 55 kW | (500 V) 55 kW | (690 V) 55 kW | (380 / 400 V) 45 kW | (380 / 400 V) 55 kW | (220 / 230 / 240 V) 25 kW | (220 / 230 / 240 V) 30 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 840 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 140 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 300 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1200 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 450 A | for 0.1 s 140 A | for 1 s 100 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1150 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 750 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 1000 V | acc. to IEC 60947-5-1 690 V | acc. to UL/CSA 600 V
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-15) 1200 cycles per hour | (AC-2 / AC-4) 150 cycles per hour | (AC-3) 1200 cycles per hour | (DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 250 ... 500 V | 60 Hz 250 ... 500 V | DC Operation 250 ... 500 V
Coil Consumption
Average Holding Value 50 / 60 Hz 4 V·A | Average Holding Value DC 2 W
Power Loss
at Rated Operating Conditions AC-1 per Pole 8.2 W | at Rated Operating Conditions AC-3 per Pole 4.5 W
Operate Time
Between Coil De-energization and NC Contact Closing 19 ... 105 ms | Between Coil De-energization and NO Contact Opening 17 ... 100 ms | Between Coil Energization and NC Contact Opening 38 ... 95 ms | Between Coil Energization and NO Contact Closing 42 ... 100 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 6 ... 50 mm² | Flexible with Insulated Ferrule 1/2x 6 ... 50 mm² | Rigid Stranded 1x 6 ... 70 mm² | Rigid Stranded 2x 6 ... 50 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Auxiliary Circuit 10 mm | Control Circuit 10 mm | Main Circuit 17 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Recommended Screw Driver
Pozidriv PZ
Tightening Torque
Auxiliary Circuit 1.2 N·m | Control Circuit 1.2 N·m | Main Circuit 6 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
Continuous Current Rating NEMA
0 A
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 115 A
Horsepower Rating UL/CSA
(120 V AC) Single Phase 7-1/2 hp | (200 ... 208 V AC) Three Phase 30 hp | (220 ... 240 V AC) Three Phase 40 hp | (240 V AC) Single Phase 20 hp | (440 ... 480 V AC) Three Phase 75 hp | (550 ... 600 V AC) Three Phase 75 hp
Connecting Capacity Main Circuit UL/CSA
Rigid Stranded 1/2x 6-1 AWG
Connecting Capacity Control Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG | Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSA
Auxiliary Circuit 11 in·lb | Control Circuit 11 in·lb | Main Circuit 53 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 80 A | (200 ... 208 V AC) Three Phase 92 A | (220 ... 240 V AC) Three Phase 80 A | (240 V AC) Single Phase 88 A | (440 ... 480 V AC) Three Phase 77 A | (550 ... 600 V AC) Three Phase 77 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -40 ... 70 °C | Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Shock and Vibration Withstand acc. to IEC 61373
Category 1, Class B
Pollution Degree
3
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
Yes
End Of Life Disassembling Instructions
End of life instruction AF(S)40/52/65/80/96(B)(RT) Contactors
Environmental Product Declaration - EPD
Environmental Product Declaration AF(S)80(B), AF(S)96(B) (FR)
Sustainable Material Content in Packaging (wt. %)
FSC Recycled Paper - 94.6 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 28.2 %
A2L Certificate – UL
UL-US Certificate of Compliance AF40 ... AF96 3-pole contactors - UL 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers | UL-CA Certificate of Compliance AF40 ... AF96 3-pole contactors - CSA C22.2 No. 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers
CB Certificate
CB Certificate AF(S)80(B), AF(S)96(B) 3 and 4-pole contactors
CCC Certificate
CQC Certificate, AC Contactor, AF(S)*80-30-**-**, AF80-40-**-**, AF80-22-**-**, AF(S)96-30-**-**, Made in France
Declaration of Conformity - CE
EU Declaration of Conformity AF09 ... AF38(Z)B..(K), AF40B ... AF96B 3 and 4-pole contactors
Declaration of Conformity - UKCA
UK Declaration of Conformity AF09 ... AF38(Z)B..(K), AF40B ... AF96B 3 and 4-pole contactors
UL Certificate
UL-US-L312527-1141-10303102-9 | UL-CA-L312527-4141-10303102-9
Package Level 1 Units
box 1 piece
Package Level 1 Width
150 mm
Package Level 1 Depth / Length
150 mm
Package Level 1 Height
103 mm
Package Level 1 Gross Weight
1.33 kg
Package Level 1 EAN
3471523025561
Package Level 2 Units
box 8 piece
Package Level 2 Width
250 mm
Package Level 2 Depth / Length
300 mm
Package Level 2 Height
300 mm
Package Level 2 Gross Weight
10.64 kg
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
Feature: AF technology with a wide control voltage range of 250-500 V 50/60 Hz and DC operation. Business Impact: Enables reliable operation across fluctuating networks, reducing nuisance tripping and unused panel energy. Application: Ideal for control circuits in conveyors, pumps, and machine tools where supply stability varies. Feature: Pre-mounted auxiliary contacts (NO and NC). Business Impact: Cuts wiring complexity and simplifies interlock logic, reducing installation time and potential wiring errors. Application: Suitable for starter circuits and local interlocks in automated lines. Feature: 3-pole design with up to 1000 V insulation and current ratings up to 130 A AC-1 and 96 A AC-3 (depending on voltage). Business Impact: Supports motor loads up to high kW ranges while maintaining safe switching in AC-3/AC-1 applications. Application: Primary motor control in packaging, plastics, and material handling. Feature: Built-in surge protection and compact block design. Business Impact: Protects coils and power circuits from transients, extending device life and reducing maintenance. Application: Harsh industrial environments with switching transients. Feature: Extendability with add-on auxiliary contact blocks and compatibility with AF accessories. Business Impact: Scales with evolving control schemes without full replacement, lowering lifecycle costs. Application: Modular automation setups and retrofit projects. Feature: DIN rail mounting TH35-15 and screw mounting (2x M4/M6). Business Impact: Fast, secure installation with flexible mounting options, reducing panel footprint. Application: Control cabinets in OEM and panel-building environments. Feature: RoHS/REACH compliance and sustainable packaging content. Business Impact: Supports regulatory compliance and corporate sustainability targets while maintaining performance. Application: Design for green manufacturing and long-term compliance in global plants.
Get a Quick Quote for a ABB 1SBL407061R1411
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SBL407061R1411?
Enquire Now
FAQs
The AF96B-30-11-14 supports TH35-15 DIN rail mounting and can also be screwed to a panel using two M4 or M6 fasteners placed diagonally. When wiring, use the main circuit terminals for 1/2 x 6 to 50 mm2 flexible or rigid conductors and connect the auxiliary and control circuits within the specified ferrule or solid wire ranges. Ensure tightening torques: main circuit 6 N·m and auxiliary/control circuits 1.2 N·m.
For AC-1, Ie is up to 130 A at 690 V (60 °C). For AC-3e and AC-3 at common industrial voltages, Ie values range from 96 A (415–440–500 V, 60 °C) down to 57 A (690 V). At 380/400 V, AC-3 ratings reach around 105 A. These values support motor starting and running duties in standard drive applications.
Yes. The AF96B series carries standards including IEC/EN 60947-1 and 60947-4-1, UL/CSA compliance, EN 50155, and IEC 61373 for vibration, which makes it suitable for rolling stock and other vibration-intensive environments when paired with appropriate accessories.
The product carries CE and UKCA declarations, UL and CSA certificates, CB certificates, and RoHS/REACH declarations. It also aligns with WEEE guidance for B2B applications and provides DoC references for Conformity, enabling straightforward regulatory compliance across markets.
Coil consumption is 4 VA at 50/60 Hz or 2 W DC, with 8.2 W (AC-1) and 4.5 W (AC-3) per pole power loss, contributing to predictable thermal behavior. Its extendable design and integrated surge protection reduce wiring, spare-part costs, and downtime, delivering a favorable total-cost-of-ownership in steady-state motor control applications.