ABB 1SBL911074R2610 Block Contactor - 690 V CE

Part Number: 1SBL911074R2610
Manufacturer
ABB
Part number
1SBL911074R2610

Quick Summary

ABB 1SBL911074R2610 Block Contactor is a three‑pole AC contactor designed to control 3‑phase motors and power circuits up to 690 V AC. This unit addresses common field challenges such as panel space, heat, and regulatory compliance with a compact footprint and robust construction. It carries CE and UL/CCC declarations, plus RoHS compliance, ensuring safe, compliant operation in industrial environments. A built‑in auxiliary NO contact simplifies control wiring and interlocking, reducing component count and installation time. Low coil power loss supports energy efficiency and thermal reliability, while a 0.8 W per pole AC‑1 / 0.1 W AC‑3 rating keeps heat under control. Compatible AX series accessories enable quick installation and scalable control.

Product Information

Extended Description

1SBL911074R2610 ABB: AX09...AX25 contactors are mainly used for controlling 3-phase motors and power circuits up to 690 V AC. These contactors are of the block type design with: – 3 main poles and 1 built-in auxiliary contact – control circuit: AC operated – add-on auxiliary contact blocks for front or side mounting and a wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
1SBC100187L0203
Instructions and Manuals
AX 06~40A instructions
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
44 mm
Product Net Depth / Length
74 mm
Product Net Height
74 mm
Product Net Weight
0.326 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
0
Rated Operational Voltage
Auxiliary Circuit 690 V | Main Circuit 690 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 26 A | acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)
(220 / 240 V) 55 °C 22 A | (690 V) 40 °C 25 A | (690 V) 70 °C 18 A
Rated Operational Current AC-3 (Ie)
(415 V) 55 °C 12 A | (440 V) 55 °C 9 A | (500 V) 55 °C 9 A | (690 V) 55 °C 7 A | (380 / 400 V) 55 °C 12 A | (220 / 230 / 240 V) 55 °C 12 A
Rated Operational Current AC-15 (Ie)
(690 V) 2 A | (24 / 127 V) 6 A | (220 / 240 V) 4 A | (380 / 400 V) 3 A | (400 / 440 V) 2 A
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W | (110 V) 1.1 A / 121 W | (125 V) 1.1 A / 138 W | (220 V) 0.55 A / 121 W | (250 V) 0.55 A / 138 W | (400 V) 2.8 A / 134 W | (500 V) 2 A / 144 W
Rated Operational Power AC-3 (Pe)
(415 V) 5.5 kW | (440 V) 4 kW | (500 V) 5.5 kW | (690 V) 5.5 kW | (380 / 400 V) 5.5 kW | (220 / 230 / 240 V) 3 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 120 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 26 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 55 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 280 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 70 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 90 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
Rated Impulse Withstand Voltage (Uimp)
Auxiliary Circuit 6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-15) 1200 cycles per hour | (AC-3) 1200 cycles per hour | (DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 105 V | 60 Hz 110 ... 127 V
Power Loss
at Rated Operating Conditions AC-1 per Pole 0.8 W | at Rated Operating Conditions AC-3 per Pole 0.1 W
Operate Time
Between Coil De-energization and NC Contact Closing 9 ... 16 ms | Between Coil De-energization and NO Contact Opening 4 ... 11 ms | Between Coil Energization and NC Contact Opening 7 ... 21 ms | Between Coil Energization and NO Contact Closing 10 ... 26 ms
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
Tightening Torque
Auxiliary Circuit 1 N·m | Control Circuit 1 N·m | Main Circuit 1 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
General Use Rating UL/CSA
(600 V AC) 25 A
Horsepower Rating UL/CSA
(120 V AC) Single Phase 3/4 hp | (200 ... 208 V AC) Three Phase 3 hp | (220 ... 240 V AC) Three Phase 3 hp | (240 V AC) Single Phase 2 hp | (440 ... 480 V AC) Three Phase 7.5 hp | (550 ... 600 V AC) Three Phase 10 hp
Tightening Torque UL/CSA
Auxiliary Circuit 9 in·lb | Control Circuit 9 in·lb | Main Circuit 9 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 13.8 A | (200 ... 208 V AC) Three Phase 11 A | (220 ... 240 V AC) Three Phase 9.6 A | (240 V AC) Single Phase 12 A | (440 ... 480 V AC) Three Phase 11 A | (550 ... 600 V AC) Three Phase 11 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -25 ... 55 °C | Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C | Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
Maximum Operating Altitude Permissible
Without Derating 3000 m
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
CB Certificate
AX 06~25A CB certification
CCC Certificate
9AKK107492A7089
CCS Certificate
CCS Certificate of AFC09 ... AFC96 , AX09-AX370 contactors
CQC Certificate
CQC Certificate, Contactor, AX06, AX09, AX12, AX18, AX25, Made in China
Declaration of Conformity - CCC
CCC Declaration of Conformity, Contactor, AX06, AX09, AX12, AX18, AX25, Made in China
Declaration of Conformity - CE
EU Declaration of Conformity AX06, AX09, AX12, AX18, AX25, AX32, AX40, AX50, AX65, AX80 3-pole Contactors
UL Certificate
UL Certificate of Compliance – AX06, AX09, AX12, AX18, AX25
Package Level 1 Units
box 1 piece
Package Level 1 Width
48 mm
Package Level 1 Depth / Length
78 mm
Package Level 1 Height
79 mm
Package Level 1 Gross Weight
0.34 kg
Package Level 1 EAN
3471522393265
Package Level 2 Units
30 piece
Package Level 2 Width
240 mm
Package Level 2 Depth / Length
295 mm
Package Level 2 Height
145 mm
Package Level 2 Gross Weight
10.2 kg
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4755 >> Contactors
Feature → Business Impact → Application: The block design provides three main normally open contacts and a built‑in auxiliary NO contact, enabling straightforward motor start/stop and auxiliary signaling in a single device. This reduces wiring complexity and panel density, which lowers assembly time and potential fault points on manufacturing lines. Typical applications include fans, pumps, and conveyor systems in industrial plants. Feature → Business Impact → Application: Control circuit is AC operated with 50 Hz 105 V or 60 Hz 110–127 V, matching common control voltages and simplifying integration with existing control circuits. Application in standard control panels and automation architectures is streamlined. Feature → Business Impact → Application: Power loss per pole 0.8 W (AC‑1) and 0.1 W (AC‑3) reduces heat and supports energy efficiency, improving overall machine bottom line. Used in continuous duty scenarios where cooling and energy cost matter. Feature → Business Impact → Application: Rated insulation voltage 690 V, impulse withstand 6 kV, and mechanical switching frequency up to 3600 cycles per hour provide robust performance under demanding loads. Ideal for frequent cycling in conveyors, presses, and pumps. Feature → Business Impact → Application: IP20 protection with screw terminals, compact 44 mm width, 74 mm depth, and 74 mm height, plus 0.326 kg weight, enables easy field installation and compatibility with standard DIN rail panels. Add-on auxiliary contact blocks for front or side mounting support customization and accessibility in control schemes.

Get a Quick Quote for a ABB 1SBL911074R2610

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SBL911074R2610? Enquire Now

FAQs

This block contactor uses three normally open main contacts plus one NO auxiliary contact, with an AC control coil at 50 Hz 105 V or 60 Hz 110–127 V. It features screw terminals and IP20 protection, making it compatible with standard control panel wiring and common control relays. Its compact footprint (44 mm wide) helps fit tight enclosures and simplifies panel layouts while maintaining regulatory compliance with CE and UL declarations.
In AC‑3 service, the contactor supports 9–12 A depending on voltage and temperature, with a low per‑pole power loss of 0.1 W, aiding thermal management during frequent switching. Maximum mechanical switching frequency is 3600 cycles per hour, and the unit provides 690 V insulation with a 6 kV impulse withstand for reliable protection against transients typical in motor drive environments.
Yes. The device is designed for 690 V systems and up to 25 A Ie in AC‑3 configurations, with IP20 protection for coil terminals and robust thermal performance (Ith 26 A open contactor). Its compact 44 mm width, 74 mm depth, and 74 mm height fit dense installations, while accessory add‑on blocks enable front or side mounting to suit specific machine layouts.
The product carries CE declarations and UL certification; it also aligns with CCC, RoHS, and REACH declarations for multi‑region compliance. This combination supports global deployment in regulated environments and reduces the risk of non‑compliant components in supply chains and end‑products.
Low coil power loss (0.8 W per pole for AC‑1, 0.1 W for AC‑3) reduces heat generation and energy usage, improving system efficiency and cooling requirements. The integrated auxiliary contact reduces wiring and component counts, cutting installation time and spare parts inventory. Durable construction and compliance certifications also minimize maintenance downtime and regulatory risk over the machine lifecycle.