ABB 1SBL911074R8101 Contactor - UL 600V 25A, Industrial

Part Number: 1SBL911074R8101
Manufacturer
ABB
Part number
1SBL911074R8101

Quick Summary

ABB 1SBL911074R8101 Contactor is a 3-pole AC motor control device designed for reliable operation in industrial automation. It targets panel builders and maintenance engineers seeking compact, robust switchgear for 3‑phase motors up to 690 V AC. A common pain point is balancing space, thermal load, and certification requirements; this model delivers a compact 44 mm width with integrated 3 NO main contacts and 1 NC auxiliary contact, reducing panel depth and wiring complexity. The product is certified for UL/CSA and CE with RoHS compliance, and its IP20 rated terminals support safe, maintenance-friendly installations. With 24 V coil control and fast operate times, it supports efficient motor start sequences and predictable switch gear behavior.

Product Information

Extended Description

1SBL911074R8101 ABB: AX09...AX25 contactors are mainly used for controlling 3-phase motors and power circuits up to 690 V AC. These contactors are of the block type design with: – 3 main poles and 1 built-in auxiliary contact – control circuit: AC operated – add-on auxiliary contact blocks for front or side mounting and a wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
1SBC100187L0203
Instructions and Manuals
AX 06~40A instructions
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
44 mm
Product Net Depth / Length
74 mm
Product Net Height
74 mm
Product Net Weight
0.326 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
1
Rated Operational Voltage
Auxiliary Circuit 690 V | Main Circuit 690 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 26 A | acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)
(220 / 240 V) 55 °C 22 A | (690 V) 40 °C 25 A | (690 V) 70 °C 18 A
Rated Operational Current AC-3 (Ie)
(415 V) 55 °C 12 A | (440 V) 55 °C 9 A | (500 V) 55 °C 9 A | (690 V) 55 °C 7 A | (380 / 400 V) 55 °C 12 A | (220 / 230 / 240 V) 55 °C 12 A
Rated Operational Current AC-15 (Ie)
(500 V) NC 2 | (500 V) 2 A | (690 V) 2 A | (24 / 127 V) 6 A | (220 / 240 V) 4 A | (380 / 400 V) 3 A | (400 / 440 V) 2 A
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W | (110 V) 1.1 A / 121 W | (125 V) 1.1 A / 138 W | (220 V) 0.55 A / 121 W | (250 V) 0.55 A / 138 W | (400 V) 2.8 A / 134 W | (500 V) 2 A / 144 W
Rated Operational Power AC-3 (Pe)
(415 V) 5.5 kW | (440 V) 4 kW | (500 V) 5.5 kW | (690 V) 5.5 kW | (380 / 400 V) 5.5 kW | (220 / 230 / 240 V) 3 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 120 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 26 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 55 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 280 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 70 A | for 0.1 s 140 A | for 1 s 100 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 90 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
Rated Impulse Withstand Voltage (Uimp)
Auxiliary Circuit 6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-15) 1200 cycles per hour | (AC-3) 1200 cycles per hour | (DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 24 V | 60 Hz 24 V
Power Loss
at Rated Operating Conditions AC-1 per Pole 0.8 W | at Rated Operating Conditions AC-3 per Pole 0.1 W
Operate Time
Between Coil De-energization and NC Contact Closing 9 ... 16 ms | Between Coil De-energization and NO Contact Opening 4 ... 11 ms | Between Coil Energization and NC Contact Opening 7 ... 21 ms | Between Coil Energization and NO Contact Closing 10 ... 26 ms
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Tightening Torque
Auxiliary Circuit 1 N·m | Control Circuit 1 N·m | Main Circuit 1 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
General Use Rating UL/CSA
(600 V AC) 25 A
Horsepower Rating UL/CSA
(120 V AC) Single Phase 3/4 hp | (200 ... 208 V AC) Three Phase 3 hp | (220 ... 240 V AC) Three Phase 3 hp | (240 V AC) Single Phase 2 hp | (440 ... 480 V AC) Three Phase 7.5 hp | (550 ... 600 V AC) Three Phase 10 hp
Tightening Torque UL/CSA
Auxiliary Circuit 9 in·lb | Control Circuit 9 in·lb | Main Circuit 9 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 13.8 A | (200 ... 208 V AC) Three Phase 11 A | (220 ... 240 V AC) Three Phase 9.6 A | (240 V AC) Single Phase 12 A | (440 ... 480 V AC) Three Phase 11 A | (550 ... 600 V AC) Three Phase 11 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -25 ... 55 °C | Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C | Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
Maximum Operating Altitude Permissible
Without Derating 3000 m
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
CB Certificate
AX 06~25A CB certification
CCC Certificate
9AKK107492A7089
CCS Certificate
CCS Certificate of AFC09 ... AFC96 , AX09-AX370 contactors
CQC Certificate
CQC Certificate, Contactor, AX06, AX09, AX12, AX18, AX25, Made in China
Declaration of Conformity - CCC
CCC Declaration of Conformity, Contactor, AX06, AX09, AX12, AX18, AX25, Made in China
Declaration of Conformity - CE
EU Declaration of Conformity AX06, AX09, AX12, AX18, AX25, AX32, AX40, AX50, AX65, AX80 3-pole Contactors
UL Certificate
UL Certificate of Compliance – AX06, AX09, AX12, AX18, AX25
Package Level 1 Units
box 1 piece
Package Level 1 Width
48 mm
Package Level 1 Depth / Length
78 mm
Package Level 1 Height
79 mm
Package Level 1 Gross Weight
0.34 kg
Package Level 1 EAN
3471522394811
Package Level 2 Units
30 piece
Package Level 2 Width
240 mm
Package Level 2 Depth / Length
295 mm
Package Level 2 Height
145 mm
Package Level 2 Gross Weight
10.2 kg
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4755 >> Contactors
E-Number (Finland)
3707310
Feature: 3 main poles and 1 built-in auxiliary contact. Business Impact: Simplifies motor control wiring and enables front or side mounting of add-on accessories, reducing panel size and assembly time. Application: Suitable for controlling 3‑phase motors in conveyors, pumps, and machine tools. Long-tail keywords: 3-pole block contactor, auxiliary contact, front mounting accessories.Feature: AC operated control circuit with 24 V coil (50/60 Hz). Business Impact: Seamless integration with standard PLC control systems and low control power requirements, improving reliability and panel heat management. Application: Industrial control panels and automation cabinets. Long-tail keywords: 24 V control coil, AC operated coil, PLC integration.Feature: Rated operational currents for AC-3 and AC-1 across voltages up to 690 V. Business Impact: Predictable motor starting and running performance, reducing downtime and impedance mismatches in heavy-duty loads. Application: Pumps, fans, and conveyors in high-voltage systems. Long-tail keywords: AC-3 current ratings, AC-1 current ratings, 690 V systems.Feature: Power loss and thermal performance (0.8 W AC-1 per pole; 0.1 W AC-3 per pole). Business Impact: Lower energy waste and cooler control cabinets, enabling higher duty cycles with less cooling. Application: Continuous-duty machines and shifting workloads. Long-tail keywords: Power loss per pole, thermal efficiency, energy savings.Feature: Compact dimensions (44 mm width, 74 mm depth, 74 mm height) and IP20 protection at terminals. Business Impact: Easier installation in densely packed switchgear and safer wiring environments, with straightforward maintenance access. Application: Panel installations in compact automation rooms. Long-tail keywords: compact motor control, IP20 terminals, panel mounting convenience.Feature: Screw terminals with 1 N·m tightening torque and robust mechanical switching. Business Impact: Reliable, vibration-resistant connections and long service life in factory environments. Application: High-vibration assembly lines and automated lines. Long-tail keywords: screw terminal blocks, tightening torque, vibration resistance.

Get a Quick Quote for a ABB 1SBL911074R8101

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SBL911074R8101? Enquire Now

FAQs

The ABB 1SBL911074R8101 is designed for standard 3-pole panel mounting with a compact 44 mm width. Connect the main terminals using 1 N·m torque screws, then wire the 24 V control coil to the control circuit at 50/60 Hz. For best results, use front or side-mounted add-on auxiliary blocks as needed and ensure IP20 terminal protection during assembly.
Key ratings include a main circuit up to 690 V AC with rated frequencies at 50/60 Hz. Rated operational currents for AC-3 include 12 A at 415 V and 7 A at 690 V, with higher Ie values at lower voltages. The coil operates at 24 V for both 50 Hz and 60 Hz, and auxiliary contacts include 1 NC for signaling, ensuring compatible control logic and safe interlocking.
Yes. The 3 NO main contacts plus 1 NC auxiliary contact arrangement suits 3‑phase motor control in conveyors, pumps, and machine tools. Its 24 V control coil integrates with standard PLC outputs, and its 690 V insulation rating supports typical conveyor drive voltages. The device’s compact frame and IP20 protection aid in safe, space-efficient cabinet installations.
This ABB contactor is CE and UL/CSA certified, with RoHS compliance for restricted substances. It also features UL certification for general use and a CE Declaration of Conformity, aligning with EU and North American installation standards. These certifications help ensure regulatory compliance in global manufacturing environments and facilitate cross-border procurement.
Expect low operating power loss per pole (0.8 W AC-1, 0.1 W AC-3), contributing to cooler panels and reduced cooling costs. The solid 3600 cycles/hour mechanical life and compact footprint reduce replacement intervals and wiring complexity. Overall, this translates to improved reliability, easier maintenance, and lower total cost of ownership in automated lines.