ABB 1SBL921074R8601 Block Contactor is a three-pole, AC-operated switch designed to control 3-phase motors in industrial power circuits. This compact solution helps minimize downtime by delivering reliable switching with correct coil voltage and an integrated auxiliary contact. It carries critical CE and UL/CSA certifications and RoHS compliance, with IP20 protection ensuring safe operation in standard panels. For OEMs, it integrates seamlessly into ABB AX-series control schemes, offering straightforward installation, accessible CAD resources, and easy maintenance. With a 44 mm net width and 74 mm depth, it maximizes panel density while maintaining serviceability, delivering tangible efficiency gains and lower lifecycle costs across production lines.

Product Information

Extended Description

1SBL921074R8601 ABB: AX09...AX25 contactors are mainly used for controlling 3-phase motors and power circuits up to 690 V AC. These contactors are of the block type design with: – 3 main poles and 1 built-in auxiliary contact – control circuit: AC operated – add-on auxiliary contact blocks for front or side mounting and a wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
1SBC100187L0203
Instructions and Manuals
AX 06~40A instructions
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
44 mm
Product Net Depth / Length
74 mm
Product Net Height
74 mm
Product Net Weight
0.326 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
1
Rated Operational Voltage
Auxiliary Circuit 690 V | Main Circuit 690 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 28 A | acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)
(220 / 240 V) 55 °C 25 A | (690 V) 40 °C 27 A | (690 V) 70 °C 20 A
Rated Operational Current AC-3 (Ie)
(415 V) 55 °C 18 A | (440 V) 55 °C 12 A | (500 V) 55 °C 12 A | (690 V) 55 °C 9 A | (380 / 400 V) 55 °C 18 A | (220 / 230 / 240 V) 55 °C 18 A
Rated Operational Current AC-15 (Ie)
(500 V) NC 2 | (500 V) 2 A | (690 V) 2 A | (24 / 127 V) 6 A | (220 / 240 V) 4 A | (380 / 400 V) 3 A | (400 / 440 V) 2 A
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W | (110 V) 1.1 A / 121 W | (125 V) 1.1 A / 138 W | (220 V) 0.55 A / 121 W | (250 V) 0.55 A / 138 W | (400 V) 2.8 A / 134 W | (500 V) 2 A / 144 W
Rated Operational Power AC-3 (Pe)
(415 V) 9 kW | (440 V) 5.5 kW | (500 V) 7.5 kW | (690 V) 7.5 kW | (380 / 400 V) 7.5 kW | (220 / 230 / 240 V) 4 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 145 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 28 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A | for 0.1 s 140 A | for 1 s 100 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 90 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
Rated Impulse Withstand Voltage (Uimp)
Auxiliary Circuit 6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-15) 1200 cycles per hour | (AC-3) 1200 cycles per hour | (DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 400 ... 415 V | 60 Hz 415 ... 440 V
Power Loss
at Rated Operating Conditions AC-1 per Pole 1 W | at Rated Operating Conditions AC-3 per Pole 0.2 W
Operate Time
Between Coil De-energization and NC Contact Closing 9 ... 16 ms | Between Coil De-energization and NO Contact Opening 4 ... 11 ms | Between Coil Energization and NC Contact Opening 7 ... 21 ms | Between Coil Energization and NO Contact Closing 10 ... 26 ms
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Tightening Torque
Auxiliary Circuit 1 N·m | Control Circuit 1 N·m | Main Circuit 1 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
General Use Rating UL/CSA
(600 V AC) 30 A
Horsepower Rating UL/CSA
(120 V AC) Single Phase 1 hp | (200 ... 208 V AC) Three Phase 5 hp | (220 ... 240 V AC) Three Phase 5 hp | (240 V AC) Single Phase 3 hp | (440 ... 480 V AC) Three Phase 10 hp | (550 ... 600 V AC) Three Phase 15 hp
Tightening Torque UL/CSA
Auxiliary Circuit 9 in·lb | Control Circuit 9 in·lb | Main Circuit 9 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 16 A | (200 ... 208 V AC) Three Phase 17.5 A | (220 ... 240 V AC) Three Phase 15.2 A | (240 V AC) Single Phase 17 A | (440 ... 480 V AC) Three Phase 14 A | (550 ... 600 V AC) Three Phase 17 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -25 ... 55 °C | Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C | Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
Maximum Operating Altitude Permissible
Without Derating 3000 m
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
CB Certificate
AX 06~25A CB certification
CCC Certificate
9AKK107492A7089
CCS Certificate
CCS Certificate of AFC09 ... AFC96 , AX09-AX370 contactors
CQC Certificate
CQC Certificate, Contactor, AX06, AX09, AX12, AX18, AX25, Made in China
Declaration of Conformity - CCC
CCC Declaration of Conformity, Contactor, AX06, AX09, AX12, AX18, AX25, Made in China
Declaration of Conformity - CE
EU Declaration of Conformity AX06, AX09, AX12, AX18, AX25, AX32, AX40, AX50, AX65, AX80 3-pole Contactors
UL Certificate
UL Certificate of Compliance – AX06, AX09, AX12, AX18, AX25
Package Level 1 Units
box 1 piece
Package Level 1 Width
48 mm
Package Level 1 Depth / Length
78 mm
Package Level 1 Height
79 mm
Package Level 1 Gross Weight
0.34 kg
Package Level 1 EAN
3471522396860
Package Level 2 Units
30 piece
Package Level 2 Width
240 mm
Package Level 2 Depth / Length
295 mm
Package Level 2 Height
145 mm
Package Level 2 Gross Weight
10.2 kg
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4755 >> Contactors
Feature → Business Impact → Application: The contactor uses 3 main NO contacts plus 1 NC auxiliary contact, controlled by an AC coil rated up to 690 V, enabling direct, robust control of three-phase motors with minimal wiring. This reduces panel complexity and wiring errors while improving reliability in conveyors, pumps, and machine tools. Feature → Business Impact → Application: Built-in auxiliary contact blocks allow front or side mounting without additional modules, shrinking installation time and simplifying wiring for safety interlocks and remote signaling in automated lines. Feature → Business Impact → Application: Dimensions of 44 mm width, 74 mm depth, and 74 mm height support high panel density, enabling compact control cabinets in compact machine designs such as packaging, material handling, and processing lines. Feature → Business Impact → Application: IP20 protection and 690 V insulation rating provide durable operation in standard indoor environments, reducing maintenance and extending service life for factory floor equipment. Feature → Business Impact → Application: Screw terminals and a 1 N·m tightening torque simplify installation and improve vibration resistance in demanding environments, ensuring reliable terminations for long-term operation. Feature → Business Impact → Application: Wide compatibility with the AX06–AX25 family and the availability of CAD drawings (2D/3D) accelerate engineering workflows, shorten project timelines, and reduce design risk for machine builders. Feature → Business Impact → Application: UL/CSA, CE, CCC, and RoHS certifications give compliance confidence and faster customer acceptance, helping distributors and OEMs meet regulatory and supplier requirements while controlling total cost of ownership.

Get a Quick Quote for a ABB 1SBL921074R8601

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SBL921074R8601? Enquire Now

FAQs

Install using the screw terminals with a tightening torque of 1 N·m for auxiliary, control, and main circuits. Ensure the coil is supplied at the appropriate 50/60 Hz voltage (400-415 V or 415-440 V) and mount the device so the main terminals remain accessible for wire termination and inspection.
Rated Operational Current AC-3 at 690 V is 9 A (55 °C). AC-1 rating at 690 V is 27 A (40 °C) and 20 A (70 °C). These values support starting and running of 3-phase motors with appropriate overload protection.
Yes. It carries CE and UL/CSA approvals, plus RoHS compliance and other certifications (CCC, CQC). This ensures regulatory conformity, safer operation, and easier supplier qualification for industrial applications.
The unit has a net width of 44 mm, net depth of 74 mm, and net height of 74 mm, with screw terminals for reliable terminations. Weight is approximately 0.326 kg. It supports compact panel layouts and straightforward mounting in standard 3-pole control circuits.
Key benefits include reliable 3-pole motor control with integrated auxiliary contact, space-saving 44x74 mm footprint, IP20 protection, and long mechanical life. Availability of CAD files and compatibility with AX06–AX25 families reduces engineering time, lowers install costs, and improves uptime, contributing to lower total cost of ownership.