ABB 1SBL931074R7510 Block Contactor - 690V AC-3 32A

Part Number: 1SBL931074R7510
Manufacturer
ABB
Part number
1SBL931074R7510

Quick Summary

ABB 1SBL931074R7510 block contactor provides reliable motor control for three‑phase systems up to 690 V. In demanding installations, engineers seek compact, robust devices that tolerate ambient conditions and inrush without compromising performance. This model is CE and UL certified, rated for insulation up to 690 V and IP20 coil terminals, and supports front or side add-on auxiliary blocks for flexible wiring. Its AC-operated control circuit at 50/60 Hz and a 3-pole main contact assembly deliver dependable switching with minimal power loss. With straightforward mounting and compatible accessory options, it reduces integration time and supports scalable control schemes for evolving plant needs.

Product Information

Extended Description

1SBL931074R7510 ABB: AX09...AX25 contactors are mainly used for controlling 3-phase motors and power circuits up to 690 V AC. These contactors are of the block type design with: – 3 main poles and 1 built-in auxiliary contact – control circuit: AC operated – add-on auxiliary contact blocks for front or side mounting and a wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
1SBC100187L0203
Instructions and Manuals
AX 06~40A instructions
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
44 mm
Product Net Depth / Length
74 mm
Product Net Height
74 mm
Product Net Weight
0.326 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
0
Rated Operational Voltage
Auxiliary Circuit 690 V | Main Circuit 690 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 32 A | acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)
(220 / 240 V) 55 °C 27 A | (690 V) 40 °C 32 A | (690 V) 70 °C 23 A
Rated Operational Current AC-3 (Ie)
(415 V) 55 °C 25 A | (440 V) 55 °C 16 A | (500 V) 55 °C 14 A | (690 V) 55 °C 10 A | (380 / 400 V) 55 °C 25 A | (220 / 230 / 240 V) 55 °C 25 A
Rated Operational Current AC-15 (Ie)
(690 V) 2 A | (24 / 127 V) 6 A | (220 / 240 V) 4 A | (380 / 400 V) 3 A | (400 / 440 V) 2 A
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W | (110 V) 1.1 A / 121 W | (125 V) 1.1 A / 138 W | (220 V) 0.55 A / 121 W | (250 V) 0.55 A / 138 W | (400 V) 2.8 A / 134 W | (500 V) 2 A / 144 W
Rated Operational Power AC-3 (Pe)
(415 V) 11 kW | (440 V) 9 kW | (500 V) 9 kW | (690 V) 9 kW | (380 / 400 V) 11 kW | (220 / 230 / 240 V) 6.5 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 200 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 32 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 85 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 105 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 90 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
Rated Impulse Withstand Voltage (Uimp)
Auxiliary Circuit 6 kV
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour | (AC-15) 1200 cycles per hour | (AC-3) 1200 cycles per hour | (DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 200 V | 60 Hz 200 ... 220 V
Power Loss
at Rated Operating Conditions AC-1 per Pole 1.2 W | at Rated Operating Conditions AC-3 per Pole 0.35 W
Operate Time
Between Coil De-energization and NC Contact Closing 9 ... 16 ms | Between Coil De-energization and NO Contact Opening 4 ... 11 ms | Between Coil Energization and NC Contact Opening 7 ... 21 ms | Between Coil Energization and NO Contact Closing 10 ... 26 ms
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
Tightening Torque
Auxiliary Circuit 1 N·m | Control Circuit 1 N·m | Main Circuit 1.2 N·m
Terminal Type
Screw Terminals
Product Name
Block Contactor
General Use Rating UL/CSA
(600 V AC) 30 A
Horsepower Rating UL/CSA
(120 V AC) Single Phase 2 hp | (200 ... 208 V AC) Three Phase 7.5 hp | (220 ... 240 V AC) Three Phase 7.5 hp | (240 V AC) Single Phase 3 hp | (440 ... 480 V AC) Three Phase 15 hp | (550 ... 600 V AC) Three Phase 15 hp
Tightening Torque UL/CSA
Auxiliary Circuit 9 in·lb | Control Circuit 9 in·lb | Main Circuit 11 in·lb
Full Load Amps Motor Use
(120 V AC) Single Phase 24 A | (200 ... 208 V AC) Three Phase 25.3 A | (220 ... 240 V AC) Three Phase 22 A | (240 V AC) Single Phase 17 A | (440 ... 480 V AC) Three Phase 21 A | (550 ... 600 V AC) Three Phase 17 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -25 ... 55 °C | Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C | Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
Maximum Operating Altitude Permissible
Without Derating 3000 m
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
CB Certificate
AX 06~25A CB certification
CCC Certificate
9AKK107492A7089
CCS Certificate
CCS Certificate of AFC09 ... AFC96 , AX09-AX370 contactors
CQC Certificate
CQC Certificate, Contactor, AX06, AX09, AX12, AX18, AX25, Made in China
Declaration of Conformity - CCC
CCC Declaration of Conformity, Contactor, AX06, AX09, AX12, AX18, AX25, Made in China
Declaration of Conformity - CE
EU Declaration of Conformity AX06, AX09, AX12, AX18, AX25, AX32, AX40, AX50, AX65, AX80 3-pole Contactors
UL Certificate
UL Certificate of Compliance – AX06, AX09, AX12, AX18, AX25
Package Level 1 Units
box 1 piece
Package Level 1 Width
48 mm
Package Level 1 Depth / Length
78 mm
Package Level 1 Height
79 mm
Package Level 1 Gross Weight
0.34 kg
Package Level 1 EAN
3471522397751
Package Level 2 Units
30 piece
Package Level 2 Width
240 mm
Package Level 2 Depth / Length
295 mm
Package Level 2 Height
145 mm
Package Level 2 Gross Weight
10.2 kg
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4755 >> Contactors
Feature: Three main NO contacts and one built-in auxiliary NO contact. Business Impact: Enables simultaneous control of a three‑phase motor with a compact footprint, reducing panel complexity and component count. Application: Suitable for 3‑phase conveyors, fans, and pumps in medium‑to‑high duty workloads, especially where space is at a premium. Long-tail keywords: block contactor 3-pole, motor control 690 V, AC-3 load switching. Feature: AC-operated control circuit with 50 Hz/60 Hz compatibility and control voltage of 200 V. Business Impact: Simplifies integration with standard plant controls and minimizes control wiring errors. Application: Use in dashboards and control cabinets powered from common 200 V control networks. Long-tail keywords: 200 V coil, AC control voltage 50/60 Hz, control circuit compatibility. Feature: Up to IP20 protection on coil terminals and a robust degree of protection for industrial environments. Business Impact: Improves reliability in dusty or challenging factory floors while easing installation in open panels. Application: Panel mounting in packaging lines, material handling, and process automation. Long-tail keywords: IP20 coil terminals, enclosure protection, panel mounting. Feature: Compact footprint — 44 mm width, 74 mm depth, 74 mm height, weight 0.326 kg. Business Impact: Saves panel space, reduces shipping weight, and accelerates retrofit projects. Application: Small control enclosures and modular starter assemblies. Long-tail keywords: small footprint contactor, compact motor starter, ergonomic installation. Feature: Low power loss — 1.2 W per pole (AC-1) and 0.35 W per pole (AC-3). Business Impact: Low heat generation, improved energy efficiency, and lower cooling requirements in switchgear. Application: Continuous operation in high‑duty motor drives and energy‑conscious machinery. Long-tail keywords: low power loss contactor, energy efficient motor control, thermal management. Feature: Compatibility with add-on auxiliary contact blocks and front/side mounting options. Business Impact: Flexible expansion for signaling, interlocking, and interface customization without full replacement. Application: Industrial automation projects requiring scalable control logic. Long-tail keywords: add-on auxiliary contacts, modular contactor, front/side mounting.

Get a Quick Quote for a ABB 1SBL931074R7510

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SBL931074R7510? Enquire Now

FAQs

Ensure a 44 mm wide footprint fits the panel; use screw terminals with a tightening torque of 1 N·m for auxiliary and control circuits and 1.2 N·m for the main circuit. The device supports front or side auxiliary blocks and is designed for IP20 protection on coil terminals, simplifying wiring in standard control cabinets.
For AC-3 at 690 V, the rated operational current Ie is 10 A at 55 °C. This rating reflects practical performance when switching motor loads with limited thermal rise and aligns with the device’s power handling at higher voltages.
Yes. The rated operational power AC-3 at 380/400 V is 11 kW, making this interlockable contactor appropriate for controlling an 11 kW, 400 V AC motor under typical industrial duty conditions.
The product carries CE and UL/CSA certifications, with CCC/CQC in some regional fulfillments, plus RoHS and WEEE compliance. This mix supports global appliance standards and regulatory requirements for industrial equipment in many markets.
Power loss is 1.2 W per pole for AC-1 and 0.35 W per pole for AC-3. This reduces heat generation, lowers cooling load, improves panel efficiency, and contributes to overall energy savings in continuous motor control applications.