ABB 1SBX210321R1422 Contactor Starter - IEC 60947-4-1

Part Number: 1SBX210321R1422
Manufacturer
ABB
Part number
1SBX210321R1422

Quick Summary

ABB AF65R-30-22-14 DC Reversing Contactor enables rapid motor reversal in DC-powered automation panels. This design addresses space and wiring challenges common in control cabinets, delivering reliable operation in dense installations. It complies with IEC/EN 60947-1, IEC/EN 60947-4-1, and UL 60335-2-40, underpinning safety and performance across regions. For panel builders and integrators, the DIN rail mounting option, screw-terminal connections, and broad control-voltage range support flexible deployments, streamlined maintenance, and consistent procurement across global projects in industrial automation.

Product Information

Extended Description

1SBX210321R1422 ABB: AF65R-30-22-14 250-500V50/60HZ-DC Reversing Contactor
Minimum Order Quantity
1 piece
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
110 mm
Product Net Depth / Length
144 mm
Product Net Height
151 mm
Product Net Weight
2.382 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
2
Number of Auxiliary Contacts NC
2
Number of Poles
3P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22
Rated Operational Voltage
Auxiliary Circuit 690 V | Main Circuit 690 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 Hz | Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Rated Operational Current AC-1 (Ie)
(1000 V) 60 °C 90 A | (690 V) 40 °C 105 A | (690 V) 70 °C 80 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 65 A | (440 V) 60 °C 65 A | (500 V) 60 °C 55 A | (690 V) 60 °C 39 A | (380 / 400 V) 60 °C 65 A | (220 / 230 / 240 V) 60 °C 65 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 65 A | (440 V) 60 °C 65 A | (500 V) 60 °C 55 A | (690 V) 60 °C 39 A | (380 / 400 V) 60 °C 65 A | (220 / 230 / 240 V) 60 °C 65 A
Rated Operational Current AC-15 (Ie)
(500 V) 2 A | (690 V) 2 A | (24 / 127 V) 6 A | (220 / 240 V) 4 A | (400 / 440 V) 3 A
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W | (48 V) 2.8 A / 134 W | (72 V) 1 A / 72 W | (110 V) 0.55 A / 60 W | (125 V) 0.55 A / 69 W | (220 V) 0.27 A / 60 W | (250 V) 0.27 A / 68 W | (400 V) 0.15 A / 60 W | (500 V) 0.13 A / 65 W | (600 V) 0.1 A / 60 W
Rated Operational Power AC-3 (Pe)
(415 V) 37 kW | (440 V) 37 kW | (500 V) 37 kW | (690 V) 37 kW | (380 / 400 V) 30 kW | (220 / 230 / 240 V) 18.5 kW
Rated Operational Power AC-3e (Pe)
(415 V) 37 kW | (440 V) 37 kW | (500 V) 37 kW | (690 V) 37 kW | (380 / 400 V) 30 kW | (220 / 230 / 240 V) 18.5 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 600 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A | for 0.1 s 140 A | for 1 s 100 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 V | acc. to IEC 60947-5-1 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
6 kV
Maximum Electrical Switching Frequency
(AC-15) 1200 cycles per hour | (DC-13) 900 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 250 ... 500 V | 60 Hz 250 ... 500 V | DC Operation 250 ... 500 V
Power Loss
at 6 A per Pole 0.1 W | at Rated Operating Conditions AC-1 per Pole 7 W | at Rated Operating Conditions AC-3 per Pole 2.7 W
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 4 ... 35 mm² | Flexible with Insulated Ferrule 1/2x 4 ... 35 mm² | Rigid Stranded 1/2x 6 ... 35 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Auxiliary Circuit 10 mm | Control Circuit 10 mm | Main Circuit 16 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Tightening Torque
Auxiliary Circuit 1.2 N·m | Control Circuit 1.2 N·m | Main Circuit 4 N·m
Terminal Type
Screw Terminals
Product Name
Contactor Starter
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
Connecting Capacity Main Circuit UL/CSA
Rigid Stranded 1/2x 10-2 AWG
Connecting Capacity Control Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG | Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSA
Auxiliary Circuit 11 in·lb | Control Circuit 11 in·lb | Main Circuit 35 in·lb
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -40 ... 70 °C | Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C
Pollution Degree
3
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
A2L Certificate – UL
UL-US Certificate of Compliance AF40 ... AF96 3-pole contactors - UL 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers | UL-CA Certificate of Compliance AF40 ... AF96 3-pole contactors - CSA C22.2 No. 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers
CB Certificate
CB Certificate AF(S)40(B), (S)AF52(B), AF(S)65(B) 3 and 4-pole contactors
CCC Certificate
CQC Certificate, Contactor, AF*40-30-**-**, AF40-40-**-**, AF40-22-**-**, AF*52-30-**-**, AF52-40-**-**,AF*65-30-**-**, Made in France
UL Certificate
UL-US-L312527-1141-10303102-9 | UL-CA-L312527-4141-10303102-9
Package Level 1 Units
box 1 piece
Package Level 1 Gross Weight
2.582 kg
Package Level 1 EAN
3471523020054
ETIM 7
EC000010 - Combination of contactors
ETIM 8
EC000010 - Combination of contactors
ETIM 9
EC000010 - Combination of contactors
eClass
V11.0 : 27371003
UNSPSC
39121529
Feature → Business Impact → Application: The device provides three main NO contacts with no main NC contacts, plus two NO and two NC auxiliary contacts, enabling comprehensive motor control and status signaling for conveyors, pumps, and process lines. This arrangement improves control reliability and reduces wiring complexity in panel assemblies, leading to quicker commissioning and lower risk of mis-wiring during revisions. Feature → Business Impact → Application: Rated for auxiliary and main circuits up to 690 V and 50/60 Hz, with a robust 6 kV impulse withstand and a high breaking capacity, delivering safe operation in high-energy loads and surge events. This supports consistent uptime in packaging lines and material handling systems. Feature → Business Impact → Application: Control circuit voltage ranges from 250 to 500 V for 50/60 Hz and DC operation, offering flexibility across global plants and varied supply schemes. This simplifies stocking and cross-site installations in automotive and food & beverage applications. Feature → Business Impact → Application: DIN rail mounting TH35-15 or TH35-7.5 and screw-terminal connections enable fast, tool-friendly installations with reliable terminations and straightforward field maintenance in metalworking and water treatment facilities. Feature → Business Impact → Application: Wire sizing and torque data (main circuit 1/2x 4–35 mm²; control 1/2x 0.75–2.5 mm²) plus rated insulation voltage of 690 V provide robust, vibration-tolerant connections suitable for noisy factory environments and where panel space is premium. Feature → Business Impact → Application: Dimensions (110 mm width, 144 mm depth, 151 mm height) and weight (2.382 kg) support compact, ergonomic panel layouts and predictable spoilage-free logistics in OEM builds and machine builders. Feature → Business Impact → Application: Compliance with IEC/EN 60947-1, IEC/EN 60947-4-1, UL/CSA safety standards, RoHS and WEEE declarations ensure regulatory alignment and easier supplier qualification for industrial automation deployments in process plants and material handling systems.

Get a Quick Quote for a ABB 1SBX210321R1422

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SBX210321R1422? Enquire Now

FAQs

This device supports DIN rail mounting on TH35-15 or TH35-7.5 rails and can also be secured with 2 x M4 or 2 x M6 screws placed diagonally. The combination gives flexible mounting in compact panels while maintaining vibration resistance and easy service access for maintenance and upgrades.
Main circuit rated operational current AC-3 is up to 65 A across broad voltage bands, with insulation rated at 690 V and impulse withstand of 6 kV. It provides AC-3/AC-3e performance suitable for 415–690 V networks and DC-13 compatibility for auxiliary DC loads, supporting reliable motor control and switchgear coordination.
Yes. The AF65R-30-22-14 is a 3P reversing contactor with 3 main NO contacts and 2 NO/2 NC auxiliary contacts, designed specifically for reversing motor direction in belt conveyors, mixers, and packaging lines. Its ratings support frequent switching and safe operation under typical conveyor duty cycles.
The device complies with IEC/EN 60947-1 and IEC/EN 60947-4-1, UL 60335-2-40, and CSA listings, along with RoHS and WEEE commitments. These certifications simplify global procurement, ensure safety in household and commercial appliance contexts, and support regulatory compliance for industrial automation projects.
Control voltage spans 250–500 V for both 50/60 Hz and DC operation, supporting diverse supply schemes. Main circuit connections use screw terminals rated for 1/2x 4–35 mm², while control circuit connections accept 1/2x 0.75–2.5 mm² with correct stripping lengths. This enables flexible integration with existing control cabinets and PLC I/O networks.