ABB 1SBX304311R1422 Contactor Starter - IEC 60947-4-1
Part Number: 1SBX304311R1422
Quick Summary
ABB 1SBX304311R1422 Contactor Starter is a DC reversing contactor that simplifies motor control in industrial automation environments. Engineers often grapple with limited panel space, complex wiring, and the need for reliable switching under demanding duty cycles. It complies with IEC/EN 60947-1 and IEC/EN 60947-4-1, and carries UL and CSA safety certifications, delivering robust protection in compact footprints. With DIN rail TH35 mounting and flexible terminal options, it minimizes installation time and total cost of ownership while integrating easily into existing control architectures. This combination supports efficient, safe, and scalable motor control across conveyors, pumps, and processing lines.
Product Information
Extended Description
1SBX304311R1422 ABB: AF26N1R-30-22-14 250-500V50/60HZ-DC Reversing Contactor
Minimum Order Quantity
1 piece
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
90 mm
Product Net Depth / Length
119.5 mm
Product Net Height
112.5 mm
Product Net Weight
0.848 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
2
Number of Auxiliary Contacts NC
2
Number of Poles
3P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-4-1
Rated Operational Voltage
Auxiliary Circuit 690 V | Main Circuit 690 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 Hz | Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Rated Operational Current AC-1 (Ie)
(1000 V) 60 °C 40 A | (690 V) 40 °C 45 A | (690 V) 70 °C 32 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 26 A | (440 V) 60 °C 26 A | (500 V) 60 °C 23 A | (690 V) 60 °C 17 A | (380 / 400 V) 60 °C 26 A | (220 / 230 / 240 V) 60 °C 26 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 26 A | (440 V) 60 °C 26 A | (500 V) 60 °C 23 A | (690 V) 60 °C 17 A | (380 / 400 V) 60 °C 26 A | (220 / 230 / 240 V) 60 °C 26 A
Rated Operational Current AC-15 (Ie)
(500 V) 2 A | (690 V) 2 A | (24 / 127 V) 6 A | (220 / 240 V) 4 A | (400 / 440 V) 3 A
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W | (48 V) 2.8 A / 134 W | (72 V) 1 A / 72 W | (110 V) 0.55 A / 60 W | (125 V) 0.55 A / 69 W | (220 V) 0.27 A / 60 W | (250 V) 0.27 A / 68 W | (400 V) 0.15 A / 60 W | (500 V) 0.13 A / 65 W | (600 V) 0.1 A / 60 W
Rated Operational Power AC-3 (Pe)
(415 V) 11 kW | (440 V) 15 kW | (500 V) 15 kW | (690 V) 15 kW | (380 / 400 V) 11 kW | (220 / 230 / 240 V) 6.5 kW
Rated Operational Power AC-3e (Pe)
(415 V) 11 kW | (440 V) 15 kW | (500 V) 15 kW | (690 V) 15 kW | (380 / 400 V) 11 kW | (220 / 230 / 240 V) 6.5 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 350 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 50 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 150 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 700 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 225 A | for 0.1 s 140 A | for 1 s 100 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 500 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 200 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 V | acc. to IEC 60947-5-1 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
6 kV
Maximum Electrical Switching Frequency
(AC-15) 1200 cycles per hour | (DC-13) 900 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 250 ... 500 V | 60 Hz 250 ... 500 V | DC Operation 250 ... 500 V
Power Loss
at 6 A per Pole 0.1 W | at Rated Operating Conditions AC-1 per Pole 1.8 W | at Rated Operating Conditions AC-3 per Pole 0.6 W
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 1.5 ... 10 mm² | Flexible with Insulated Ferrule 1x 1.5 ... 10 mm² | Flexible with Insulated Ferrule 2x 1.5 ... 4 mm² | Rigid Solid 1/2x 2.5 ... 4 mm² | Rigid Stranded 1/2x 2.5 ... 10 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | Rigid Solid 1/2x 1 ... 2.5 mm² | Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Auxiliary Circuit 10 mm | Control Circuit 10 mm | Main Circuit 14 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Tightening Torque
Auxiliary Circuit 1.2 N·m | Control Circuit 1.2 N·m | Main Circuit 2.5 N·m
Terminal Type
Screw Terminals
Product Name
Contactor Starter
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
Connecting Capacity Main Circuit UL/CSA
Rigid Solid 1/2x 14-10 AWG | Rigid Stranded 1/2x 14-8 AWG
Connecting Capacity Auxiliary Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG | Rigid Stranded 1/2x 18-14 AWG
Connecting Capacity Control Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG | Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSA
Auxiliary Circuit 11 in·lb | Control Circuit 11 in·lb | Main Circuit 22 in·lb
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -25 ... 60 °C | Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C
Pollution Degree
3
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
A2L Certificate – UL
UL-US A2L LZGH2 Certificate of Compliance AF09 ... AF38 3-pole contactors with screw terminals - UL 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers | UL-CA A2L LZGH2 Certificate of Compliance AF09 ... AF38 3-pole contactors with screw terminals - CSA C22.2 No. 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers
CB Certificate
CB Certificate AF26(Z)(B), AF30(Z)(B), AF(Z)(B)38 3-pole contactors, AFS26, AFS30, AFS38 safety contactors
UL Certificate
UL-US Certificate of Compliance AF(C)(S)09(R/M/N)-..(L)(S)(K)...AF(C)(S)38(R/M/N)..(K) 3-pole contactors screw, spring and push-in spring terminals; LDC4 additional coil terminal block; LF16-4, LG16-4, LF38-4 and LH38-4 connecting strips, LD38-4 additional terminal block | UL-CA Certificate of Compliance AF(C)(S)09(R/M/N)-..(L)(S)(K)...AF(C)(S)38(R/M/N)..(K) 3-pole contactors screw, spring and push-in spring terminals; LDC4 additional coil terminal block; LF16-4, LG16-4, LF38-4 and LH38-4 connecting strips, LD38-4 additional terminal block
Package Level 1 Units
box 1 piece
Package Level 1 Gross Weight
2.348 kg
Package Level 1 EAN
3471523020382
ETIM 7
EC000010 - Combination of contactors
ETIM 8
EC000010 - Combination of contactors
ETIM 9
EC000010 - Combination of contactors
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4762 >> Nema Contactors
Feature: 3-pole DC reversing contactor with 3 NO main contacts and 2 NO auxiliary contacts. Business impact: Enables compact, reliable motor switching for multi-speed or reversing applications, reducing panel size and wiring complexity while delivering predictable duty performance. Application: Conveyor drives, pumps, and processing line motors requiring robust DC switching. Long-tail keyword integration: 3-pole DC reversing contactor for compact automation, DC coil 250–500 V control, and 690 V main circuit compatibility. Feature: DC operation coil 250–500 V and 50/60 Hz rated across control and auxiliary circuits. Business impact: Flexible power supply compatibility supports global installations and retrofits, lowering installation risk and downtime. Application: Control circuits in diverse automation environments with unified voltage requirements. Feature: DIN rail mounting TH35-15 or TH35-7.5 and screw mounting option. Business impact: Fast, tool-friendly installation with secure retention in cabinets, speeding commissioning and service transitions. Application: New panel builds and retrofits where space is constrained. Feature: Wiring and terminal capacity: suitable for Flexible with Ferrule 1/2x 0.75–2.5 mm², 1/2x 1.5–10 mm² main, auxiliary, and control circuits. Business impact: Simplifies harnessing and makes field termination robust, cutting maintenance time. Application: General purpose industrial control panels with mixed conductor sizes. Feature: Electrical ratings: AC-3 and DC-13/AC-3e across a wide voltage range including 415–690 V ranges; 26 A AC-3 at 415–440 V and 17 A at 690 V. Business impact: Supports higher power loads with proven endurance, enabling energy-efficient motor control and lower lifecycle costs. Application: Heavy-duty conveyors and pump drives. Feature: Protection and compliance: IP20, UL/CSA, and IEC/EN 60947-1 and 60947-4-1 certifications. Business impact: Assures regulatory compliance, safer operation, and easier supplier qualification in regulated projects. Application: Global installations requiring recognized safety standards. End-to-end value: The product’s combination of compact footprint, versatile mounting, and broad electrical ratings delivers installation efficiency, reliability, and cost savings in modern industrial facilities.
Get a Quick Quote for a ABB 1SBX304311R1422
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SBX304311R1422?
Enquire Now
FAQs
This unit supports DIN rail mounting TH35-15 and TH35-7.5, plus a screw mounting option with 2 x M4 screws for secure panel installation. This flexibility speeds retrofits into existing cabinets and minimizes hardware changes.
AC-3 ratings include up to 26 A at 415–440 V and 17 A at 690 V, with AC-3e values matching the same ranges. DC-13 ratings are specified per coil voltage and load, enabling reliable operation of inductive and motor loads across a wide voltage spectrum.
Yes. It is a 3-pole DC reversing contactor with a 250–500 V DC coil, 690 V main circuit voltage, and 3 NO main contacts plus 2 NO auxiliary contacts, designed for reversing or direct switching in conveyors, pumps, and similar drives.
It carries IEC/EN 60947-1 and 60947-4-1 standards, along with UL 60335-2-40 and CSA equivalents, ensuring safety, appliance protection, and broad market acceptance for global installations.
With low idle power loss per pole (0.1 W) and robust terminal interfaces, this device reduces energy waste and maintenance time. Its DIN-rail compatibility and standardized terminals expedite replacements and commissioning, delivering lower total cost of ownership over lifecycle.