ABB 1SBX306321R1222 Contactor - 1000 V IEC/UL

Part Number: 1SBX306321R1222
Manufacturer
ABB
Part number
1SBX306321R1222

Quick Summary

ABB 1SBX306321R1222 Contactor is a high‑reliability DC reversing contactor designed for industrial drives and conveyor systems. Engineers often struggle with compact footprints, panel space, and wiring complexity; this model helps simplify installation while delivering robust performance. It is built to meet key standards such as IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40, and CSA listings, ensuring safe, compliant operation across global specs. The unit also supports DIN rail mounting and easy wiring with screw terminals, delivering predictable lifecycle performance and lower maintenance costs. In addition to its core DC reversing capability, the device serves as a versatile picker for motor control in modern automation architectures, supporting your uptime and efficiency goals with reliable control power and signaling options.

Product Information

Extended Description

1SBX306321R1222 ABB: AF80N3R-30-22-12 48-130V50/60HZ-DC Reversing Contactor
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Instructions and Manuals (Part 2)
Contactors and Overload relays guide
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
140 mm
Product Net Depth / Length
149 mm
Product Net Height
151 mm
Product Net Weight
2.738 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
2
Number of Auxiliary Contacts NC
2
Number of Poles
3P
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22
Rated Operational Voltage
Auxiliary Circuit 690 V | Main Circuit 1000 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 Hz | Control Circuit 50 / 60 Hz | Main Circuit 50 / 60 Hz
Rated Operational Current AC-1 (Ie)
(1000 V) 60 °C 100 A | (690 V) 40 °C 125 A | (690 V) 70 °C 85 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 80 A | (440 V) 60 °C 80 A | (500 V) 60 °C 65 A | (690 V) 60 °C 49 A | (1000 V) 60 °C 25 A | (380 / 400 V) 60 °C 80 A | (220 / 230 / 240 V) 60 °C 80 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 80 A | (440 V) 60 °C 80 A | (500 V) 60 °C 65 A | (690 V) 60 °C 49 A | (380 / 400 V) 60 °C 80 A | (220 / 230 / 240 V) 60 °C 80 A
Rated Operational Current AC-15 (Ie)
(500 V) 2 A | (690 V) 2 A | (24 / 127 V) 6 A | (220 / 240 V) 4 A | (400 / 440 V) 3 A
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W | (48 V) 2.8 A / 134 W | (72 V) 1 A / 72 W | (110 V) 0.55 A / 60 W | (125 V) 0.55 A / 69 W | (220 V) 0.27 A / 60 W | (250 V) 0.27 A / 68 W | (400 V) 0.15 A / 60 W | (500 V) 0.13 A / 65 W | (600 V) 0.1 A / 60 W
Rated Operational Power AC-3 (Pe)
(415 V) 45 kW | (440 V) 45 kW | (500 V) 45 kW | (690 V) 45 kW | (1000 V) 35 kW | (380 / 400 V) 37 kW | (220 / 230 / 240 V) 22 kW
Rated Operational Power AC-3e (Pe)
(415 V) 45 kW | (440 V) 45 kW | (500 V) 45 kW | (690 V) 45 kW | (380 / 400 V) 37 kW | (220 / 230 / 240 V) 22 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 780 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 140 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 300 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1200 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 450 A | for 0.1 s 140 A | for 1 s 100 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1150 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 750 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 1000 V | acc. to IEC 60947-5-1 690 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
8 kV
Maximum Electrical Switching Frequency
(AC-15) 1200 cycles per hour | (DC-13) 900 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 48 ... 130 V | 60 Hz 48 ... 130 V | DC Operation 48 ... 130 V
Power Loss
at 6 A per Pole 0.1 W | at Rated Operating Conditions AC-1 per Pole 7.6 W | at Rated Operating Conditions AC-3 per Pole 3 W
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 6 ... 50 mm² | Flexible with Insulated Ferrule 1/2x 6 ... 50 mm² | Rigid Stranded 1x 6 ... 70 mm² | Rigid Stranded 2x 6 ... 50 mm²
Wire Stripping Length
Auxiliary Circuit 10 mm | Control Circuit 10 mm | Main Circuit 17 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Tightening Torque
Auxiliary Circuit 1.2 N·m | Control Circuit 1.2 N·m | Main Circuit 6 N·m
Terminal Type
Screw Terminals
Product Name
Contactor Starter
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
Connecting Capacity Main Circuit UL/CSA
Rigid Stranded 1/2x 6-1 AWG
Tightening Torque UL/CSA
Auxiliary Circuit 11 in·lb | Control Circuit 11 in·lb | Main Circuit 53 in·lb
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -40 ... 70 °C | Close to Contactor without Thermal O/L Relay -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C
Pollution Degree
3
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
A2L Certificate – UL
UL-US Certificate of Compliance AF40 ... AF96 3-pole contactors - UL 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers | UL-CA Certificate of Compliance AF40 ... AF96 3-pole contactors - CSA C22.2 No. 60335-2-40 Household and Similar Electrical Appliances - Safety - Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers
UL Certificate
UL-US-L312527-1141-10303102-9 | UL-CA-L312527-4141-10303102-9
Package Level 1 Units
box 1 piece
Package Level 1 Gross Weight
4.238 kg
Package Level 1 EAN
3471523020443
ETIM 7
EC000010 - Combination of contactors
ETIM 8
EC000010 - Combination of contactors
ETIM 9
EC000010 - Combination of contactors
eClass
V11.0 : 27371003
UNSPSC
39121529
Feature → Business Impact → Application: Three main NO contacts with zero NC main contacts delivers clean, uninterrupted power switching for three‑phase DC motors commonly found in drives and conveyors; this reduces arcing and wear while preserving motor control precision in a compact 3P package. Benefit: extended motor life and reduced maintenance intervals in harsh industrial environments; Application: DC drive starter circuits in material handling lines. Feature → Business Impact → Application: Two NO and two NC auxiliary contacts provide flexible signaling and interlocking for safe start/stop logic and fault signaling; Application: integrated control panels for automated lines, enabling reliable interlocks and status reporting. Feature → Business Impact → Application: 3P design with DIN rail TH35-15 mounting plus screw-terminal connections offers rapid field installation and straightforward retrofit; Benefit: shorter commissioning times and lower installation labor costs; Application: space‑constrained control cabinets in packaging and bottling lines. Feature → Business Impact → Application: Rated operational voltage main circuit up to 1000 V, auxiliary up to 690 V, with 50/60 Hz compatibility; Benefit: broad motor and load compatibility for mixed voltage environments; Application: high‑voltage DC motor drives and multi‑voltage plants. Feature → Business Impact → Application: DC‑13 and AC‑3/AC‑3e ratings support a wide range of load types with predictable switching performance; Benefit: documented fault tolerance and better protection against nuisance trips; Application: switching of DC motors, hoists, and pump drives. Feature → Business Impact → Application: High breaking capacity and defined power loss characteristics allow precise thermal management and safe enclosure design; Benefit: improved energy efficiency and reduced cooling needs in panel assemblies; Application: control panels in manufacturing lines. Feature → Business Impact → Application: Robust UL/CSA and IEC conformity with RoHS/REACH declarations; Benefit: regulatory compliance and easier supplier audits; Application: global deployments requiring certified components.

Get a Quick Quote for a ABB 1SBX306321R1222

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SBX306321R1222? Enquire Now

FAQs

This 3P contactor supports TH35-15 DIN rail mounting and screw mounting (2 x M4 or 2 x M6 screws placed diagonally), enabling flexible integration into compact control panels and retrofit projects.
Main circuit rated up to 1000 V, auxiliary circuit up to 690 V, 50/60 Hz. Main contacts: 3 NO; auxiliary contacts: 2 NO and 2 NC. AC-3/AC-3e and DC-13 performance vary by voltage; see datasheet for exact current values across voltages.
Yes, it is a DC reversing contactor with DC-13 and AC-3/AC-3e ratings, designed for motor control in drive systems and conveyors, with appropriate contact configurations for reversing and interlocking.
It carries IEC/EN 60947-1 and 60947-4-1, UL 60335-2-40, and CSA listings (with related LZGH2 A2L markings), plus RoHS/REACH declarations to support global installations and audits.