ABB 1SCA022713R4930 Switch-Disconnectors - IEC 60947-3
Part Number: 1SCA022713R4930
Quick Summary
ABB 1SCA022713R4930 is a 4-pole switch-disconnector for safe isolation in electrical panels. Maintenance teams often face downtime from difficult access and unreliable handles, which this unit mitigates with a front-operated mechanism and a robust base-mounted design built to withstand daily switchgear use. It meets IEC 60947-3 standards and carries a CE Declaration of Conformity, RoHS compliance, and SCIP disclosures for traceability, offering clear regulatory alignment. Designed for base mounting in industrial switchgear and motor control centers, it integrates with OT200-250 family devices to support compact, modular installations that reduce downtime, improve safety, and simplify spare-part planning across a plant fleet.
Product Information
Extended Description
1SCA022713R4930 ABB: 4-pole, front operated, base mounted switch-diconnector with black IP65 handle and shaft, terminal bolt kit included
End Of Life Disassembling Instructions
OT160-250 Disassembling Instruction
Environmental Information
PEI OT160-250
Environmental Product Declaration - EPD
PEP, EPD, OT160-250
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
Reach Declaration / AC Switches and Fusegear
RoHS Information
RoHs Declaration / AC Switches and Fusegear
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
73b50007-7370-43db-b632-afd2ace9a2b9 Finland (FI)
Simplified SCIP
952db535-b9e7-4396-b9b9-d0ae3329ff06 Germany (DE) | b78b7276-fe9b-429c-b65b-36f700172cce Denmark (DK) | 375a8369-6160-40d4-9525-433b2acf8149 Portugal (PT) | a02fd67d-ccda-4e37-814e-a1148db8ce02 Germany (DE) | 87ca0995-48f3-4a43-9bdf-7565ac79d418 Croatia (HR) | 2c75adff-151b-40c9-bf33-2220120f038e Czech Republic (CZ) | dc91e6ad-049a-4a50-8380-142781afceab Poland (PL) | a4904f14-714c-4260-ba71-4197be9d93a5 Germany (DE) | c8d1c055-b3a7-4fa4-bb8f-2737d211e0da Germany (DE) | 65575a92-bc32-47ee-b5b9-aa5a71a420a7 France (FR) | 618a4795-20cb-44a0-9b1e-9ae6ae56b9f7 Poland (PL) | a6366ead-4bd6-49e4-9622-bb2cbbbacad8 France (FR) | 3a5c8eb6-3c9e-4be6-b236-dfc33d1d27ea Hungary (HU) | 7d49eee1-723e-4329-9967-ea010edd81bd Belgium (BE) | 3b8ad121-d0ed-47f1-b813-36123f33803c Germany (DE) | ca4322a6-9641-4a42-a2b4-df92b33f5ca9 Italy (IT) | aefbd3f2-b2f9-450c-9340-986382782842 Estonia (EE) | a6d290d1-388e-470e-b24b-26d9dc90e168 Netherlands (NL) | 4b90fa76-c2e4-49c2-b6e8-e52ee95165b6 Hungary (HU) | 336a54bd-4b03-499e-a2e1-fd822433210a Sweden (SE) | 545cd6c8-10d1-4f0e-89e8-6fe45f2b546f Bulgaria (BG) | 8db9c867-fcc2-4f86-b9ab-e121047fc173 Greece (GR) | 2af4ef85-f079-4bec-a1c1-905def916101 Sweden (SE) | e6843545-ee86-45df-bcad-d07e1c31f3a5 Poland (PL) | cd01ed60-90e7-4d7c-b512-894d0f636181 Spain (ES) | 9a0d5582-d9b5-4f43-a34b-0a582f472284 Belgium (BE) | 80ce273c-c2b4-4506-8ced-14def07043d3 Norway (NO)
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) Declaration / AC Switches and Fusegear
Data Sheet, Technical Information
Switches, Switch-disconnectors OT and OTM. Catalogue OT8GB 07-07
Instructions and Manuals
Switch Disconnectors OT200-250
Mechanical Drawings
OT200-250E04, dwg-file | OT200-250E04, dxf-file | OT200-250E04.igs
Environmental Product Declaration - EPD
PEP, EPD, OT160-250
Degree of Protection
Front IP00
Environmental Information
PEI OT160-250
Pollution Degree
3
Minimum Order Quantity
1 piece
Customs Tariff Number
85365080
Country of Origin
Finland (FI)
Product Net Width
180.5 mm
Product Net Height
150 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.8 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
170 mm | 6.69 in
Package Level 1 Depth / Length
190 mm | 7.48 in
Package Level 1 Height
145 mm | 5.71 in
Package Level 1 Gross Weight
2.1 kg | 0.93 lb
Package Level 1 EAN
6417019228747
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 200 A
Conventional Thermal Current (Ithe)
Fully Enclosed 200 A
Degree of Protection
Front IP00
Distance Between Phases
Standard
Fourth Pole Position
Right Side
Fourth Pole Type
Switched - Simultaneous Function
Handle Color
Black
Handle Type
Handle and shaft included
Lock Type
Yes
Mechanical Durability
20000
Mounting Type
Base mounting
Number of Poles
4P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out | Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 4.0 W
Rated Conditional Short-Circuit Current (Inc)
(315 A fuse, 500 V) 100 kA | (355 A fuse, 690 V) 80 kA | (250 A fuse, 690 V) 100 kA
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 200 A | (500 V) 200 A | (690 V) 200 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 200 A | (500 V) 200 A | (690 V) 200 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 200 A | (500 V) 200 A | (690 V) 200 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 60 kW | (400 ... 415 V) 110 kW | (500 V) 132 kW | (690 V) 200 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 8 kA
Special Functions
No
Standards
IEC 60947-3
Switches Operating Mechanism
Mechanism at the End of the Switch | 04 (Left Side)
Terminal Type
Lug terminals
Terminal Width
20 mm
Tightening Torque
acc. IEC 60947-1 15 … 22 N·m
Tightening Torque
acc. IEC 60947-1 15 … 22 N·m
A2L Certificate – IEC
A2L Refrigerant Declaration of Conformity / OT160-800
ATEX Certificate
No certification needed
BV Certificate
1SCC301103D0201
Declaration of Conformity - CE
Declaration of Conformity / OT160EV_, OT200E_, OT250E_, OT200U_
DNV GL Certificate
DNV GL Certificate / OT100-160G_OT160EV-400
GL Certificate
1SCC301139D0201
LR Certificate
1SCC301144D0201
UL Certificate
No certification needed
VDE Certificate
No certification needed
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Finland)
3661306
E-Number (Norway)
4337851
E-Number (Sweden)
3171157
Feature → Business Impact → Application: The 4P, front-operated design enables quick, safe isolation during maintenance, reducing downtime and operator exposure in busy panels, especially in MCCs and distribution enclosures. This translates to measurable productivity gains and lower risk during routine line changes or fault isolation. Feature → Business Impact → Application: Ith of 200 A and Ui of 1000 V ensure reliable performance across common industrial voltages, supporting motor feeders and feeders with mixed voltage requirements while maintaining a consistent safety margin. This is critical for applications where uptime and electrical safety are prioritized. Feature → Business Impact → Application: 12 kV impulse withstand and 30 kA short-circuit making capacity at 690 V provide robust protection during transient events, safeguarding downstream equipment and reducing the likelihood of collateral damage in high-energy systems. Feature → Business Impact → Application: Lug terminals with 20 mm width and a tightening torque of 15–22 N·m enable straightforward installation and secure connections, reducing commissioning time and the risk of loose-term issues in high-load environments. Feature → Business Impact → Application: A durable handle (black, IP65-rated) supports safer manual operation in challenging environments, while the base-mount construction ensures stable integration into control panels and switchgear racks. Feature → Business Impact → Application: Compliance with IEC 60947-3, along with CE DoC, RoHS, and SCIP reporting, streamlines procurement and regulatory onboarding for global projects, minimizing supplier risk and accelerating audits.
Get a Quick Quote for a ABB 1SCA022713R4930
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SCA022713R4930?
Enquire Now
FAQs
This unit is a 4P, front-operated switch-disconnector intended for base mounting with lug terminals width of 20 mm. Plan for torque during connections of 15–22 N·m and ensure clear access for the front-operated mechanism. The fourth pole is positioned on the right side, which influences panel layout and wiring routing in tight MCC compartments.
Key specs include Conventional Free-air Thermal Current Ith of 200 A, Rated Insulation Voltage Ui of 1000 V, Rated Operational Current Ie of 200 A (AC-21A/22A/23A across 380–415 V, 500 V, and 690 V), Rated Impulse Withstand Voltage Uimp of 12 kV, Short-Circuit Making Capacity Icm up to 30 kA at 690 V, and a Short-time Withstand Current Icw of 8 kA for 1 s. These enable reliable operation in demanding industrial applications.
Yes. The 4P front-operated switch-disconnector is designed for isolation of feeder circuits in MCCs and industrial switchgear. Its base-mounting configuration, robust handle, and high current/voltage ratings make it suitable for motor feeders and sectionalizing tasks in challenging environments, while meeting IEC 60947-3 standards for interoperability with other OT200-250 family components.
It carries IEC 60947-3 as the primary standard, along with CE Declaration of Conformity, RoHS compliance, and SCIP reporting for environmental and supply-chain transparency. Additional declarations such as CMRT and TSCA are provided in the product data to support global procurement and regulatory reviews.
With a mechanical durability rating of 20,000 cycles and robust build for base mounting, maintenance cycles are predictable and downtime is minimized. The combination of reliable operation, straightforward lug-terminal installation, and compliance documentation reduces spare-part inventories, accelerates commissioning, and improves asset longevity in heavy-use panels.