ABB 1SCA022722R9640 Switch-Disconnectors - IEC 60947-3

Part Number: 1SCA022722R9640
Manufacturer
ABB
Part number
1SCA022722R9640

Quick Summary

ABB 1SCA022722R9640 switch-disconnectors provide safe, front-operated isolation for 3-pole power circuits in control panels. This design reduces maintenance downtime by delivering accessible terminals and straightforward field service. It supports IEC 60947-3 compliance, CE declarations, and RoHS/REACH conformity, with documented environmental data for sustainable sourcing. In practice, it integrates smoothly with ABB EcoSolutions and the OT200-250 family, offering reliable performance under frequent operation and variable V across industrial environments. For engineers and procurement teams, this translates to lower lifecycle risk, faster commissioning, and predictable fault modes that simplify diagnostics and spare-part planning.

Product Information

Extended Description

1SCA022722R9640 ABB: 3-pole, front operated, base mounted switch-diconnector, handle and shaft are not included, terminal bolt kit included
End Of Life Disassembling Instructions
OT160-250 Disassembling Instruction
Environmental Information
PEI OT160-250
Environmental Product Declaration - EPD
PEP, EPD, OT160-250
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
Reach Declaration / AC Switches and Fusegear
RoHS Information
RoHs Declaration / AC Switches and Fusegear
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) Declaration / AC Switches and Fusegear
Data Sheet, Technical Information
Switches, Switch-disconnectors OT and OTM. Catalogue OT8GB 07-07
Instructions and Manuals
Switch Disconnectors OT200-250
Mechanical Drawings
OT200-250E12, dwg-file | OT200-250E12, dxf-file | OT200-250E12.igs
Environmental Product Declaration - EPD
PEP, EPD, OT160-250
Degree of Protection
Front IP00
Environmental Information
PEI OT160-250
Pollution Degree
3
Minimum Order Quantity
1 piece
Customs Tariff Number
85365080
Country of Origin
Finland (FI)
Product Net Width
145.5 mm
Product Net Height
150 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.3 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
170 mm | 6.7 in
Package Level 1 Depth / Length
190 mm | 7.5 in
Package Level 1 Height
145 mm | 5.7 in
Package Level 1 Gross Weight
1.4 kg | 3.2 lb
Package Level 1 EAN
6417019232584
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 200 A
Conventional Thermal Current (Ithe)
Fully Enclosed 200 A
Degree of Protection
Front IP00
Distance Between Phases
Standard
Handle Type
Handle and shaft not included
Lock Type
No
Mechanical Durability
20000
Mounting Type
Base mounting
Number of Poles
3P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out | Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 4.0 W
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 200 A | (500 V) 200 A | (690 V) 200 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 200 A | (500 V) 200 A | (690 V) 200 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 200 A | (500 V) 200 A | (690 V) 200 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 60 kW | (400 ... 415 V) 110 kW | (500 V) 132 kW | (690 V) 200 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 8 kA
Special Functions
No
Standards
IEC 60947-3
Switches Operating Mechanism
Mechanism Between the Poles | 12 (Between the Poles)
Terminal Type
Lug terminals
Tightening Torque
acc. IEC 60947-1 15 … 22 N·m
Tightening Torque
acc. IEC 60947-1 15 … 22 N·m
A2L Certificate – IEC
A2L Refrigerant Declaration of Conformity / OT160-800
Declaration of Conformity - CE
Declaration of Conformity / OT160EV_, OT200E_, OT250E_, OT200U_
DNV GL Certificate
DNV GL Certificate / OT100-160G_OT160EV-400
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature: 3-pole, front-operated design with base mounting enables safe isolation of three-phase circuits in control cabinets. Business impact: simplifies commissioning and reduces fault-detection time, thanks to clear top-to-bottom terminal access and a robust lug-terminal connection. Application: ideal for motor feeders, distribution boards, and line-side disconnects in manufacturing environments. Feature: 200 A conventional thermal current (Ith) per pole with a fully enclosed operating range up to 690 V. Business impact: supports high-duty switching with predictable thermal performance, lowering the risk of nuisance trips during start-up, and enabling tighter protection coordination. Application: suitable for medium-to-high power drives and high-inertia loads within automation systems. Feature: Rated insulation voltage Ui of 1000 V and short-circuit capacity Icm up to 30 kA; Icw up to 8 kA for 1 s. Business impact: ensures resilience against surges, improves selectivity, and reduces spare parts inventory due to higher fault tolerance. Application: panel feeders, distribution blocks, and end-of-line disconnects in IEC 60947-3 compliant equipment. Feature: Tightening torque 15–22 N·m for reliable lug connections; weight 1.3 kg with compact 145.5 x 150 x 82.5 mm footprint. Business impact: simplifies field installation with predictable torque specs and minimal enclosure modification, improving install times and serviceability. Application: suitable for base-mounted assemblies in new builds or retrofits. Feature: IP00 front protection, 3 pollution degree, and 3P design with handle and shaft not included; supports RoHS, REACH, CMRT and EPD declarations. Business impact: supports safe indoor operation, environmental compliance, and streamlined documentation for audits. Application: standard in modern industrial control panels and ABB EcoSolutions line. Feature: Comprehensive technical package including datasheet, mechanical drawings (OT200-250E12), and OEM-related manuals; 3P operation, 12 kV impulse withstand voltage; 690 V rated operational voltage; compatible with lug terminals and 3-pole front operation. Business impact: reduces design risk by providing ready-to-install components and clear installation instructions. Application: engineering procurement and panel-building teams seeking compliant, durable switch-disconnectors.

Get a Quick Quote for a ABB 1SCA022722R9640

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SCA022722R9640? Enquire Now

FAQs

The 1SCA022722R9640 is designed for base-mounted, 3-pole front-operated isolation in panel installations. It suits control panels, motor feeders, and distribution boards within industrial automation setups. With lug terminals and 3P configuration, it integrates with OT200-250 families and ABB EcoSolutions ecosystems, enabling straightforward wiring, commissioning, and future upgrades without enclosure redesign.
Key ratings include Ith of 200 A per pole, Ui of 1000 V, Icm up to 30 kA, and Icw up to 8 kA for 1 s. The device operates at 380–415 V, 500 V, or 690 V as appropriate, with a rated operational current of 200 A and a 12 kV impulse withstand. These specs support reliable protection and quick fault isolation in medium to high power panels.
This model features front IP00 protection and is intended for indoor panel use. It is designed for controlled environments with Pollution Degree 3. For outdoor installations or harsher environments, additional enclosure protection or a device rated for higher IP/pollution conditions would be required to meet system reliability targets.
The product carries IEC 60947-3 compliance, CE Declaration of Conformity, RoHS and REACH declarations, TSCA considerations, and CMRT for conflict minerals. It also aligns with EPD data and A2L certificate references. This combination supports regulatory audits, responsible sourcing, and environmental reporting within industrial control projects.
With a mechanical durability of around 20,000 cycles and predictable lug-terminal torque (15–22 N·m), maintenance planning becomes straightforward and downtime is minimized. The device’s modular data (datasheets and drawings) accelerates commissioning, reducing project risk and spare-parts inventory, thereby delivering lower total cost of ownership in panel-buildouts and long-term reliability of power circuits.